- Hamilton01698 829711
- Leeds0113 235 1356
- Belfast02890 830302
Chauvin CA 6528 Insulation & Continuity Tester
Includes: C.A6528 insulation tester, hands-free bag, 2 safety leads, 1x red and 1x black, 1x red crocodile clip, 1x black test probe, 1x protective sheath mounted on the instrument, batteries, 1x safety datasheet, 1x quick start guide, 1x verification certificate.
The Chauvin Arnoux C.A 6528 insulation and continuity tester is designed for use in the field: lightweight, compact, rugged and easy to handle, even when wearing gloves. Its ergonomics is intended to simplify its use.
The CA 6528 is mainly used to check the safety of electrical installations. It measures resistance, insulation and continuity in compliance with the applicable standards: IEC 60364, NF C 15-100, VDE 100, etc. It is also ideal for maintenance and repair of electrical equipment such as motors, cables, etc. It can measure insulation at 250V / 500V / 1,000V, making it ideal for a large number of applications.
It offers high-performance insulation resistance measurements up to 11 GΩ, while also measuring resistance up to 420 kΩ and voltage up to 700 VAC/DC. In compliance with the applicable standards, continuity measurement is performed with a test current ≥ 200 mA. This measurement directly integrates automatic compensation of cable resistance for greater accuracy.
FEATURES
Insulation at 250 / 500 / 1 000 V.
Insulation resistance up to 11 GΩ.
Manual, locked and timer modes.
AC and AC+DC voltage measurement up to 700 V.
Continuity at 200 mA.
Visual alarm, blue / red backlighting.
Automatic power-off function to optimise the battery life.
Stand for stability when used on a horizontal surface.
Voltage | |
---|---|
Measurement range/ resolution | 1-700 V/1 V. |
Accuracy / input impedance | ±1.2% R ± 1ct for AC+DC; ±1 R ± 1ct for DC / 25 MΩ. |
Operating frequency | DC; 30‐440 Hz. |
Insulation | |
Test voltage | 250 - 500 - 1000 V. |
Range at maximum test voltage | 11 GΩ. |
Compliance with the IEC 61557‐2 | 2 GΩ. |
Measurement range | 250 V -50 kΩ ‐ 4.2 GΩ 500 V - 100 kΩ ‐ 4.2 GΩ 1000 V - 200 kΩ ‐ 11 GΩ. |
Measurement range / resolution | 50 kΩ ‐ 3.999 / 1 kΩ; (0.2)* 3.6‐39.99 MΩ / 10 kΩ; 36‐399.9 MΩ / 100 kΩ; 360‐4,200 MΩ / 1 MΩ; (1 kV) 3.6 ‐ 11.00 GΩ / 10 MΩ. |
Accuracy | 0.05‐399.9 MΩ : ±1.5 R ± 10cts; 360 ‐4,200 MΩ: ±4 R ± 10cts ; ±4 R ± 5cts (at 1,000 V); 3.6‐11 GΩ: ±10 R ± 10cts. |
Test voltage (I <1 ma="" td=""> | 0%+20%. |
Timer (min:s) | 10s to 39min 59s. |
Alarms | 1 threshold / test voltage. |
Continuity | |
Measurement range / resolution | 0.02 Ω ‐ 40 Ω (200 mA). |
Accuracy / open-circuit voltage | ±1.2% R ±3cts / 6 VDC < U < 9 VDC. |
Measurement current | ≥ 200 mA (up to 2 Ω). |
Continuity threshold (fast beep) | 2 Ω / 1 Ω. |
Cable compensation | up to 5 Ω. |
Resistance | |
Measurement range / resolution | 1 ‐399.9 Ω / 0.1 Ω; 360‐3,999 Ω / 1 Ω; 3.60‐39.99 kΩ / 10 Ω; 36.0‐420.0 kΩ / 100 Ω. |
Accuracy | ±1.2% R ±3cts. |
General Specifications | |
Display | 2 x 4,000 cts. |
Power supply / Automatic power-off | 6 x LR 6 or AA batteries / 10 min deactivatable. |
Battery life | 1,000 measurements: at 1 MΩ @ 1 kV (5 s ON / 25 s OFF); >3,000 continuity measurements (5 s ON / 25 s OFF) at 1 Ω. |
EMC / electrical safety | IEC 61326‐1 / IEC 61010‐1, IEC 61010‐2‐030 and IEC 61010‐2‐034 / 600V CAT IV. |
IP rating | IP40. |
Compliance with standards | IEC 61557 parties 1, 2, 4 and 10. |
Dimensions | 218 x 95 x 63 mm. |
Weight | 760 g. |
Chauvin CA6528 warranty | 24-months. |
*at 1,000 V. |