Includes: Megger MIT410/2, Red/Black Silicone test leads with Probes + Clips, SP5 remote switch probe, Owners information CD, Batteries 6 x AA Alkaline, Hard carry case.
The Megger MIT400 mk2 series insulation and continuity testers are designed not just for Electrical and Industrial, but with an exceptionally wide range of applications from electrical installations, cable testing, motor testing, automotive, ESD, panel building, avionics, maintenance etc.
The stabilised insulation test voltage is now accurate to +2% -0%. This compares to the industry standard +20%, providing a more accurate test voltage without the risk of over-voltage damage to circuits or components. The output voltage is maintained between 0 & 2% throughout the test range.
The MIT410/2 adds additional features required for engineers working on more demanding applications. Functions such as PI and DAR, capacitance measurement and a greater range of test voltages increase the suitability for applications such as manufacturing/production testing, panel building, railway and other transportation, motor testing, cable inspection/quality control, street lighting maintenance, avionics ground testing and maintenance, military applications.
DUAL DIGITAL DISPLAY
Large main digital readout for good visibility of all main measurement results.
Second digital display for additional data such as:
Insulation test voltage.
Insulation leakage current.
Supply frequency (when measuring volts).
Test mode eg. PI, DAR or t ( t = Timer mode).
FEATURES
Stabilised insulation testing.
Auto hold on continuity tests.
Analogue arc with pointer.
200Gohm test range.
Continuous continuity range.
Rechargeable options.
Contoured ergonomic design.
Increased battery life.
IP54 ingress protection.
CAT IV safety design.
600V measurement.
MIT400/2 | MIT410/2 | MIT420/2 | MIT430/2 | |
Insulation | ||||
50/100 V | - | |||
250/500/1000 V | ||||
Variable | - | - | ||
PI-/DAR/Timed | - | |||
Lock Button on MΩ | ||||
Continuity | ||||
Continuity 0.01 Ω to 1 MΩ | 100 Ω | |||
Auto Reverse Polarity (setup ON-OFF) | - | |||
Lead Null (<10 Ω) | ||||
Voltage | ||||
AC/DC Volts 600 V | ||||
mV AC/DC Range | ||||
Frequency Measurements 15 to 400 Hz | - | |||
Input Impedance | 0.25 MΩ | 0.25 MΩ | 0.25 MΩ | 0.25 MΩ |
Capacitance | ||||
Capacitance 0.1 nF to 10 μF | - | - | ||
Other Features | ||||
PASS/FAIL on Limit Alarms | - | |||
Auto Power Down (setup) | ||||
On-Board Memory | - | - | ||
Bluetooth Download + Software | - | - | - | |
AA Alkaline or NIMH | Both | Both | Both | Both |
Recharger Ready | - | - | - | |
CAT IV 600V / CAT III 1000V |
Test Voltage | ||
MIT 400/2 | 250, 500 and 1000 V. | |
MIT 410/2, 420/2 and 430/2 | 50, 100, 250, 500 and 1000 V. | |
Insulation Accuracy | ||
---|---|---|
Test Voltage | Range | Accuracy |
50 V | 10 GΩ | ±2% ± 2 digits ± 4.0% per GΩ. |
100 V | 20 GΩ | ±2% ± 2 digits ± 2.0% per GΩ. |
250 V | 50 GΩ | ±2% ± 2 digits ± 0.8% per GΩ. |
500 V | 100 GΩ | ±2% ± 2 digits ± 0.4% per GΩ. |
1000 V | 200 GΩ | ±2% ± 2 digits ± 0.2% per GΩ. |
Display Range | Analogue 1 GΩ full scale. |
|
Resolution | 0.1 kΩ. | |
Short Circuit/Charge Current | 2 mA +0% to -50% to EN 61557-2 (2007). | |
Open Circuit Voltage Insulation | -0 +2% ±2 V. | |
Test Current | 1 mA at min pass value of insulation to a max of 2 mA max. | |
Leakage | 10% ± 3 digits. | |
Voltage | 3% ±3 digits ±0.5% of rated voltage. | |
Timer Control | 60 second countdown timer. | |
Note: Above specifications only apply when high quality silicone leads are being used. | ||
Continuity | ||
Continuity Measurement | 0.01 Ω to 999 kΩ (0 to 1000 kΩ on analogue scale). | |
Continuity Accuracy | ± 3% ± 2 digits (0 to 100 Ω ) ±5% ±2 digits (100 to 500 kΩ) (500 kΩ to 1 MΩ unspecified) Service Error: BS EN 61557-4 (2007) - ± 2.0%, 0.1 Ω - 2 Ω ± 6.8%. |
|
Open Circuit Voltage | 5V ±1 V. | |
Test Current | 200 mA (-0 mA to +20 mA) (0.01 Ω to 4 Ω). |
|
Polarity | Single polarity (default) / Dual polarity (configurable on setup). | |
Lead Resistance | Null up to 9.00 Ω. | |
Voltage | ||
Voltage Range | AC: 10mV to 600V RMS sinusoidal (15Hz to 400Hz) DC: 0 to 600V. |
|
Volt Range Accuracy | AC: ±2% ±1 digit DC: ±2% ±2 digit Service Error: BS EN 61557-1 (2007) - ± 2.0% ± 2d, 0 V - 300 V AC/DC ± 5.1%. |
|
Waveform | Unspecified range: 0 – 10 mV (15 to 400 Hz) For non-sinusoidal waveforms additional specifications apply. Non-sinusoidal waveforms: ±3% ± 2 digits >100 mV to 600 V TRMS ±8% ± 2 digits 10 mV to 100 mV TRMS. |
|
Frequency | ||
Frequency Measurement Range | 15 Hz to 400 Hz. | |
Frequency Measurement Accuracy | ±0.5% ±1 digit (100 Hz to 400 Hz unspecified). | |
Capacitance Measurement (MIT420/2 and MIT430/2) | ||
Capacitance Measurement | 1 nF to 10 μF. | |
Capacitance Measurement Accuracy | ±5.0% ± 2 digits (0.1 nF to 1 nF unspecified). | |
Storage (MIT420/2 and MIT430/2) | ||
Storage Capacity | >1000 test results. | |
Data Download | Bluetooth wireless Bluetooth Class II. |
|
Range | Up to 10m. | |
General Specifications | ||
Battery Life | 3000 insulation tests with duty cycle of 5 seconds ON/55 sec off @ 1000 V into 1 MΩ. | |
Dimensions | Instrument: 228 x 108 x 63 mm (9.00 x 4.25 x 2.32 inches). | |
Weight | 600g (MIT400/2) (1.32lbs). |
No customer reviews for the moment.
COMPONENT |
DESCRIPTION | PART No. | ||
Test Leads | Red/Black Silicone test leads with Probes + Clips. | 1007-781 | ||
SP5 Probe | Remote switch probe (not MIT400/2). | 1007-157B | ||
Test Leads | Unfused lead set, Red/Black.Long & short prods and croc clips. Boxed. | 1002-001B | ||
Strap | Magnetic hanging strap. | 1010-013 | ||
Case | Blow moulded case. | 1007-169 | ||
Pouch | Test and carry pouch (MIT400 Mk2 Series). | 1007-887 |