loading spinner
Metrel MI 3155 EurotestXD Standard
  • Metrel MI 3155 EurotestXD Standard
  • Metrel MI 3155 EurotestXD Standard
  • Metrel MI 3155 EurotestXD Standard
  • Metrel MI 3155 EurotestXD Standard

Metrel MI 3155 EurotestXD Standard

metrel authorised distributor

Includes: MI3155 Eurotest XD-STD, 4400 mAh Battery Pack, 12V/ 3A Power Supply Adapter, Plug Commander: 1.5 m, Test Lead: 4-wire, 1.5 m, Test Lead: 3-wire, 1.5 m, Test Lead: 2-wire, 2.5 kV, 1.5 m, Test probes, Crocodile Clips, 2x red, Earth Set 20 m, USB cable, Soft Carrying Bag, Neck Belt, Metrel ES Manager BASIC license*, Short Instruction Manual, Instruction Manual (CD), Calibration Cert, Metrel ES Manager Basic (CD), *Metrel ES Manager can be downloaded free of charge from the Metrel web server.

20992755
Metrel UK

The Metrel MI 3155 EurotestXD is the newest flagship of Metrel’s most advanced line of multi-functional measuring instruments and is designed specifically for testing in industry.

What differentiates this instrument from the rest is its ergonomic design and an intuitive user interface, encompassing a memory organizer and fully programmable AUTO SEQUENCEs, managed through a large colour touch screen display.

It is fully compliant with functionality standards (e.g. IEC/EN 61557) and other reference standards for testing (e.g. IEC/EN/HD 60364-4-41,...) as is required for any instrument that performs TRMS current measurements, RCD tests, line and loop impedance tests with 3 (and 4) wires and earth resistance measurements.

Besides those, the instrument supports a wide range of tests and measuring functions, including on-line voltage monitoring, phase sequence testing, varistor testing, PI/DAR calculation, luminance measurement, discharge time testing, ISFL measurements, IMD tests as well as functional and visual inspections.

MEASURING FUNCTIONS

Live Transformer’s Impedance Measurement with Four Wire Test.
Hi-precision Short Circuit Current evaluation with Calculated Hot factor.
3-wire test of PE (RPE function) without extension lead conductor.
Autotest insulation function between L-N, N-PE and L-PE (R ISO ALL function).
4 wire continuity test.
Insulation resistance with DC voltage from 50 V to 2500 V and PI, DAR calculation.
Varistor test.
Continuity of PE conductors with 200 mA DC test current with polarity change.
Continuity of PE conductors with 7 mA test current without RCD tripping.
2-wire and 3-wire high-current loop impedance (L-PE) measurement.
3-wire loop impedance (L-PE) measurement with Trip Lock RCD function.
Touch voltage / Contact voltage measurement with external P/S probe.
2-wire and 3-wire line impedance (L-L, L-N) measurement.
1-phase / 3-phase TRMS voltage and frequency measurements.
Line, loop and RCD measurements at frequency range 16 ... 400 Hz.
Phase sequence.
Power and THD measurement (up to the 12th harmonic).
RCD testing (general and selective, type AC, A, F, B, B+, MI RCD, EV RCD, PRCD, PRCD-K, PRCD-S).
Earth resistance (3-wire and 2-clamps method).
Specific earth resistance with Ro-adapter (option).
TRMS leakage and load currents (option).
First fault leakage current (ISFL).
Testing of Insulation Monitoring Devices (IMDs).
Machine mode support with time discharge.
Illumination (option).
High resolution Loop impendance (mΩ) (option).
EVSE (Electrical Vehicle Supply Equipment) support (option).
Determining location of cables (option).
QR and/or barcode scanner support (option).

LV Electrical Installations In Mobile Homes Video

Metrel MI 3155 EurotestXD Specifications
Function Specification Measuring Range Resolution Accuracy 
CONTINUITY Test Current 7 mA 2-wire 0.00 Ω ... 19.99 Ω
20.0 Ω ... 1999 Ω
0.1 Ω
1 Ω
±(5 % of r. + 3 digits)
Test Current 200 mA 2-wire, 4-wire 0.00 Ω ... 19.99 Ω
20.0 Ω ... 199.9 Ω
200.0 Ω ... 1999 Ω
0.01 Ω
0.1 Ω
1 Ω
±(3 % of r. + 3 digits)
±(5 % of r.)
±(5 % of r.)
INSULATION RESISTANCE R iso, R iso all 1
Test Voltage 50/100/250 V
0.00 MΩ ... 19.99 MΩ
20.0 MΩ ... 99.9 MΩ
100.0 MΩ ... 199.9 MΩ
0.01 MΩ
0.1 MΩ
0.1 MΩ
±(5 % of r. + 3 digits)
±(10 % of r.)
±(20 % of r.)
R iso, R iso all 1
Test Voltage 500/1000 V
0.00 MΩ ... 19.99 MΩ
20.0 MΩ ... 199.9 MΩ
200 MΩ ... 999 MΩ
0.01 MΩ
0.1 MΩ
1 MΩ
±(5 % of r. + 3 digits)
±(5 % of r.)
±(10 % of r.)
R iso, R iso all 1
Test Voltage 2500 V
0.00 MΩ ... 19.99 MΩ
20.0 MΩ ... 199.9 MΩ
200 MΩ ... 999 MΩ
1.00 GΩ ... 19.99 GΩ
0.01 MΩ
0.1 MΩ
1 MΩ
0.01 GΩ
±(5 % of r. + 3 digits)
±(5 % of r.)
±(10 % of r.)
±(10 % of r.)
DAR, PI 0.01 ... 9.99
10.0 ... 100.0
0.01
0.1
±(5 % of r. + 2 digits)
±(5 % of r.)
Varistor test AC, DC 2 0 V … 1000 V (DC)
0 V … 625 V (AC)
1V ±(3 % of r. + 3 digits)
RCD RCD Uc 0.00 V ... 19.99 V
20.0 V ... 99.9 V
0.1 V -0 %/+15 %) of r. ± 10 digits
(-0 %/+15 %) of r
RCD (t), 0.00 ms ... 40.0 ms
0.0 ms ... max. time
0.1 ms ±1 ms
±3 ms
RCD I Ramp 0.2xI∆N ... 1.1xI∆N (AC, MI, EV a.c.)
0.2xI∆N ... 1.5xI∆N (A, I∆N ≥30 mA)
0.2xI∆N ... 2.2xIvN (A, I∆N <30 mA)
0.2xI∆N ... 2.2xI∆N (B, MI, EV d.c.)
0.05xI∆N ±0.1xI∆N
IMPEDANCE Zline (L-L, L-N), Ipsc,
Zline 4-wire 3
0.00 Ω ... 9.99 Ω
10.0 Ω ... 99.9 Ω
100 Ω ... 999 Ω
1.00 kΩ ... 9.99 kΩ
0.01 Ω
0.1 Ω
1 Ω
10 Ω
±(5 % of r. + 5 digits)
>±(10 % of r.)
Zloop (L-PE), Ipfc,
Zloop 4-wire 3

Zs RCD 4
0.00 Ω ... 9.99 Ω
10.0 Ω ... 99.9 Ω
100 Ω ... 999 Ω
1.00 kΩ ... 9.99 kΩ
0.01 Ω
0.1 Ω
1 Ω
10 Ω
±(5 % of r. + 5 digits)
±(10 % of r.)
VOLTAGE TRMS (0, 14 ... 500 Hz) 0 … 550 V 1 V ±(2 % of r. + 2 digits)
Frequency 0.00 Hz .. 9.99 Hz
10.0 Hz ... 499.9 Hz
0.01 Hz
0.1 Hz
±(0.2 % of r. + 1 digits)
CURRENT TRMS, AC with A 1018, range=20 A 0.0 mA ... 99.9 mA
100 mA ... 999 mA
1.00 A ... 19.99 A
0.1 mA
1 mA
0.01 A
±(5 % of r. + 5 digits)
±(3 % of r. + 3 digits)
±(3 % of r.)
TRMS, AC with A 1019, range=20 A 0.0 mA ... 99.9 mA
100 mA ... 999 mA
1.00 A ... 19.99 A
0.1 mA
1 mA
0.01 A
Indicative
±(5 % of r.)
±(3 % of r.)
TRMS, AC/DC with A 1391, range=40 A 0.00 A ... 1.99 A
2.00 A ... 19.99 A
20.0 A ... 39.9 A
0.01 A
0.01 A
0.1 A
±(3 % of r. + 3 digits)
±(3 % of r.)
±(3 % of r.)
TRMS, AC/DC with A 1391, range = 300 A 0.00 A ... 19.99 A
20.0 A ... 39.9 A
40.0 A ... 299.9 A
0.01 A
0.1 A
0.1 A
Indicative
Indicative
±(3 % of r. + 5 digits)
EARTH RESISTANCE 3 wire 5 0.00 Ω ... 19.99 Ω
20.0 Ω ... 199.9 Ω
200.0 Ω ... 9999 Ω
0.01 Ω
0.1 Ω
1 Ω
±(5 % of r. + 5 digits)
2 clamp 0.00 Ω ... 19.99 Ω
20.0 Ω ... 30.0 Ω
30.1 Ω ... 39.9 Ω
0.01 Ω
0.1 Ω
0.1 Ω
±(10 % of r. + 10 digits)
±(20 % of r.)
±(30 % of r.)
Specific earth resistance 0.0 Ωm … 99.9 Ωm
100 Ωm ... 999 Ωm
1.00 kΩm ... 9.99 kΩm
10.0 kΩm ... 99.9 kΩm
100 kΩm ... 9999 kΩm
0.1 Ωm
1 Ωm
0.01 kΩm
0.1 kΩm
1 kΩm
±(5 % of r.) for Re 1 Ω … 1999kΩ
±(10 % of r.) for Re 2 kΩ … 19.99kΩ
±(20 % of r.) for Re > 20 kΩ
POWER Power (P, S, Q) 0.00 W (VA, Var) ... 99.9 kW (kVA, kVar)
Power factor -1.00 ... 1.00
Voltage THD 0.1 % ... 99.9 %.
HARMONICS Voltage harmonics 0.1 V ... 500 V.
Voltage THD 0.1 % ... 99.9 %.
Current harmonics and Current THD 0.00 A ... 199.9 A.
FIRST FAULT LEAKAGE CURRENT (ISFL) ISC 1, ISC 2 0.0 mA ... 19.9 mA 0.1 mA ±(5 % of r. + 3 digits).
IMD TEST Threshold indicative insulation resistance 5 … 640 kΩ 5 kΩ Indicative values, up to 128 steps.
ILLUMINANCE Type B 0.01 lux ... 19.99 lux
20.0 lux ... 199.9 lux
200 lux ... 1999 lux
2.00 klux ... 19.99 klux
0.01 lux
0.1 lux
1 lux
10 lux
±(5 % of r. + 2 digits)
±(5 % of r.)
Type C 0.01 lux ... 19.99 lux
20.0 lux ... 199.9 lux
200 lux ... 1999 lux
2.00 klux ... 19.99 klux
0.01 lux
0.1 lux
1 lux
10 lux
±(10 % of r. + 3 digits)
±(10 % of r.)
DISCHARGING TIME Discharging time 0.0 s … 10.0 s 0.1 s ±(5 % of r. + 2 digits).
Peak voltage 0 V … 550 V 1 V ±(5 % of r. + 3 digits).
GENERAL Power supply 7.2 V (4400 mAh Li-Ion battery pack).
Overvoltage category 600 V CAT III; 300 V CAT IV.
Protection class Double insulation.
COM port BT, USB, RS232.
Weight 1.78 kg.
Size ( l x h x w ) 252 x 111 x 165 mm.
NOTES 1 Measuring current 1 mA ... 3 mA
2 Threshold current 1 mA
3 Itest = 20 A @ 230 V; 16 ... 400 Hz
4 Itest MAX = 0.5 x I∆N
5 UOC < 30 VAC, ISC < 30 mA, f = 15 Hz
Metrel A1532 Electric Vehicle Charger Tester Technical Specifications
Input voltage 400 V (3-phase).
Frequency 50 Hz.
Test current 13 A.
Proximity Pilot (PP) simulation Open circuit
13 A
20 A
32 A
63 A
Control Pilot (CP) simulation State A (not connected)
State B (connected, not charging)
State C (charging without ventilation)
State D (charging with ventilation)
State E (error - CP short to PE via diode)
Overvoltage category 300 V CAT II.
Protection degree IP 40.
Pollution degree 2.
Protection classification Double insulation.
Altitude 3000 m above sea level.
Dimensions (L x W x H) 200 x 100 x 70 mm.
Test lead length 0.5 m.
Weight 0.82 kg.
Working temperature range 0 °C … 40 °C @ 95 % RH, non-condensing
Storage temperature range -10 °C … +70 °C.
Maximum storage relative humidity 90 % RH (-10 °C … +40 °C)
80 % RH (40 °C … 60 °C).

Download

Metrel Mi 3155 Datasheet

PDF Specifications of the Metrel MI 3155 EurotestXD Standard Multifunction Tester.

Download (1.01M)

No customer reviews for the moment.

Write your review

Metrel MI 3155 EurotestXD Standard
COMPONENT
DESCRIPTION PART No.
Current Clamp High accuracy current clamp 1000 A / 1 A with jaw opening 52 mm and fixed 1.5 m cable. A1018
Three Phase Adapter 3-phase test adapter for installation safety testing on 3-phase sockets type 16 A 3CEE. A1110
Earth Test Set Earth test set for earth resistance measurement on distance up to 50 m. S2027
AC/DC Current Clamp AC/DC Current Clamp with 40 and 300 A range. A1391
Barcode Scanner Barcode scanner for identification of barcode labelled appliances. A1105
BLK Tip Commander Single phase, 3-wire tip commander with TEST, MEM and function buttons, RGB LED indicator and LED lamp. A401
1.5m Test Leads 3-wire test lead for measurements on single or three phase electrical installations. A1011

16 other products in the same category: