- Hamilton01698 829711
- Leeds0113 235 1356
- Belfast02890 830302
Kewtech KT66DL Digital 12-in-1 Multifunction Tester
Includes: KT66DL, ACC064SP G7 Test probe, with remote test button, ACC065 G7 Test lead set, Kamp12 Mains lead, USB cable, Test lead pouch, Batteries, Soft carry case, Padded strap, Instruction Manual, Calibration Certificate..
The KT66DL and KEWEVSE provides a comprehensive kit for all installation testing especially those with electrical vehicle charging points. Whether these are installed with Type B RCDs or with 6mA residual direct current devices and in either TN or TT configurations, this kit gives you the flexibility to test for electrical safety as well as EVSE functionality.
The KT66DL has an easy-to-use single rotary dial with four function softkeys and a colour LCD 3.5” dot matrix display. It also incorporates Anti-Trip Technology (ATT) which electronically bypasses RCDs when performing loop impedance tests. This saves time and money by not having to take the RCD out of the circuit during testing and is a safer procedure to follow.
With the ATT function enabled, a test of 15mA or less is applied between line & earth. It enables loop impedance measurements without tripping RCDs rated at 30mA and above. ATT supports measurements using three wires: Line, Earth, and Neutral and also two wires: Line and Earth.
FEATURES
Simultaneous display of L-N, L-N, L-E voltage (TRMS).
Three modes of starting a test: single press of the test button, continuous testing and by test button in the test probe.
Help display.
Advanced memory - assigns DB, circuit no. and type of test i.e. Zs or Ze.
Two continuity tests 200mA & 15mA .
55V loop test capability - suitable for 110V CTE systems.
Padded neck strap.
Supplied with G7 test leads and additional probe incorporating a test button.
Tests Type AC, ACS, A, AS, F, B, BS & EV.
UC - contact voltage test.
Touch voltage pad with selectable limits.
Heavy duty canvas carry case with extra room for you testing accessories.
The KT66DL has a lid to further protect your instrument. It easily folds under the instrument when in use.
KT63DL | KT63 Plus | KT65DL | KT66DL | |
---|---|---|---|---|
200mA Continuity Test | ✔ | ✔ | ✔ | ✔ |
Automatic Test Lead Null | ✔ | ✔ | ✔ | ✔ |
250, 500 & 1000V Insulation Resistance | ✔ | ✔ | ✔ | ✔ |
PAT Testing with optional PAT Adaptor 1 | ✔ | ✔ | ✔ | ✔ |
Continuous Live Warning | ✔ | ✔ | ✔ | ✔ |
High Voltage LED Light | ✔ | ✔ | ✔ | ✔ |
3 Wire No-Trip Loop Test | ✔ | ✔ | ✔ | ✔ |
2 Wire No-Trip Loop Test | ✔ | |||
High Current Loop Test | ✔ | ✔ | ✔ | ✔ |
PSC/PFC Test | ✔ | ✔ | ✔ | ✔ |
RCD Type AC & A: 10, 30, 100, 300 & 500 mA | ✔ | ✔ | ✔ | ✔ |
RCD Type ACS & A: 100 & 300 mA | ✔ | ✔ | ✔ | ✔ |
RCD Type AC: ACS, ACS & AS 10, 30, 100, 300, 500 & 1000 mA | ✔ | ✔ | ✔ | ✔ |
RCD Auto Test: 30 mA | ✔ | ✔ | ✔ | ✔ |
RCD Auto Test: 10, 30, 100, 300, 500 & 1000 mA | ✔ | ✔ | ||
RCD Auto Test All Results On One Screen | ✔ | ✔ | ✔ | |
6mA DC RCD Test (for EVSE) | ✔ | |||
'Hands Free' Testing | ✔ | ✔ | ✔ | ✔ |
Wiring & Lead Polarity Check | ✔ | ✔ | ✔ | ✔ |
Volts Measurement | ✔ | ✔ | ✔ | ✔ |
Backlight | ✔ | ✔ | ✔ | ✔ |
Soft Carry Case | ✔ | ✔ | ✔ | ✔ |
IP Rating | 54 | 54 | 40 | 40 |
All Auto RCD Results On One Screen | ✔ | ✔ | ✔ | |
Remote Test Probe Included | ✔ | ✔ | ✔ | |
0.001Ω Resolution High Current Loop Test | ✔ | ✔ | ✔ | |
55V Loop Test | ✔ | ✔ | ✔ | |
Phase Rotation | ✔ | ✔ | ✔ | |
Protective Lid On Instrument | ✔ | ✔ | ||
Touch Pad for Earth Potential Limits (25V or 50V) | ✔ | ✔ | ||
Lockout Test Button | ✔ | ✔ | ||
Earth Resistance Test | ✔ | ✔ | ||
PAT Test Firmware | ✔ | ✔ | ||
Download Memory | ✔ | ✔ | ||
Colour Screen | ✔ |
Continuity | ||||||
---|---|---|---|---|---|---|
Range | 20.00/200.0/2000Ω (auto-ranging). | |||||
Display range | 0.00 - 20.99Ω / 16.0 - 209.9Ω / 160 - 2099Ω. | |||||
Measuring range | 0 – 2000Ω. | |||||
Accuracy | ±2.0%rdg±8dgt. | |||||
Open-circuit voltage | 7 – 14V DC. | |||||
Test current | 200mA test: 200mA or more (2Ω or less) 15mA test: 15mA±3mA (short-circuit). |
|||||
Enabled if pre-set NULL value is 9Ω or less. Buzzer: Buzzer sounds when measured resistance is 2Ω or less. | ||||||
Volts | ||||||
Range | 300.0/600V (Auto-ranging) | |||||
Display range | Voltage: 2.0 – 314.9V, 240 – 629V Frequency: 40.0 – 70.0Hz (displayed at 2V or higher). |
|||||
Measuring range | Voltage: 2 – 600V | |||||
Accuracy | Voltage: ±2%rdg±4dgt Frequency: ±0.5%rdg±2dgt. |
|||||
Uc (RCD) | ||||||
Mains voltage range | 100-260V. | |||||
Range | 100V. | |||||
Display range | 0.0 - 104.9V. | |||||
Measuring range | 0 - 100V. | |||||
Accuracy | +5%to+15%rdg ±8dgt 230V. | |||||
Test current | 50 % or less of IΔn. | |||||
Earth | ||||||
Precise measurement. | Simplified measurement. | |||||
Range | 20.00 / 200.0 / 2000Ω (auto-ranging). | |||||
Accuracy | 20Ω range; ±2%rdg±0.08Ω The other ranges: ±2%rdg±3dgt (Aux. earth resistance: 100Ω). |
±2%rdg±0.08Ω The other ranges: ±2%rdg±3dgt. |
||||
Output current | 20Ω range: approx. 3mA, 200v range: approx. 1.7mA 2000Ω range: approx. 0.7mA Frequency: 825Hz. |
|||||
Phase Rotation | ||||||
Measuring Range | 48 – 600V / 45 - 65Hz. | |||||
Criteria of judgement | Correct sequence: Clockwise symbol and “1, 2, 3” are displayed Reversed sequence: Counter-clockwise symbol and “3, 2, 1” are displayed. |
|||||
Insulation | ||||||
Rated voltage | 100V | 250V | 500V | 1000V | SPD (Varistor) 1000V | |
Range | 2.000/20.00/200.0MΩ auto-ranging |
20.00/200.0/1000MΩ auto-ranging |
20.00/200.0/2000MΩ | 0 -1000V (increases in 1V steps) | ||
Display range | 0.000 - 2.099MΩ | 0.00 - 20.99MΩ | 0.00 - 20.99MΩ | 1049V | ||
1.60 - 20.99MΩ | 16.0 - 209.9MΩ | 16.0 - 209.9MΩ | ||||
16.0 - 209.9MΩ | 160 - 1049MΩ | 160 - 2099MΩ | ||||
Measuring range | 0 - 200MΩ | 0 - 1000MΩ | 0 - 2000MΩ | 0 - 1049V | ||
Accuracy | 2.000MΩ range: ±2%rdg±6dgt | 20.00MΩ range: ±(2%rdg+6dgt), 200.0MΩ range: ±(2%rdg+6dgt) | ±5%rdg±5dgt | |||
20.00MΩ range: ±2%rdg±6dgt | 1000MΩ range: ±(5%rdg+6dgt) | 2000MΩ range: ±(5%rdg+6dgt) | ||||
200MΩ range: ±5%rdg±6dgt | ||||||
Rated measurement current | 1.0 - 1.2mA at 100kΩ |
1.0 - 1.2mA at 250kΩ |
1.0 - 1.2mA at 500kΩ |
1.0 - 1.2mA at 1MΩ |
1.0 mA | |
Loop | ||||||
Function | LOOP ATT | LOOP HIGH | ||||
3-Wire L-PE | 2-Wire L-PE | L-PE0.01ΩRes | L-PE0.001ΩRes | L-N/L-L | ||
Mains input voltage range | 100 – 260V 50/60Hz (L-N < 20Ω) |
48 – 260V 50/60Hz | 100 - 260V 50/60Hz | 48 - 260V 50/60Hz | ||
Range | LOOP | 20.00/200.0/2000Ω (auto-ranging) | 20.00/200.0/2000Ω | 2.000Ω | 20.00Ω | |
PFC/PSC | 2000A/20kA | 2000A/20kA (PFC only) | 2000A/50kA (PFC only) | 2000A/20kA (PSC only) | 2000A/20kA (PSC only) | |
Display range | LOOP | 0.00 – 20.99Ω 21.0 – 209.9Ω 210 – 2099Ω |
0.00 –20.99Ω 21.0 –209.9Ω 210 –2099Ω |
0.00 - 20.99Ω 21.0 - 209.9Ω 210 –2099Ω |
0.000 - 2.099Ω | 0.00-20.99Ω |
PFC/PSC | 0 – 2099A 2.10 – 20.99kA |
0 – 2099A 2.10 – 20.99kA (PFC only) |
0 – 2099A 2.10 – 50.49kA (PFC only) |
0 – 2099A 2.10 – 20.99kA (PFC only) |
0 – 2099A 2.10 – 20.99kA (PSC only) |
|
Meas. range | LOOP | 0 – 2000Ω | 0 – 2000Ω | 0 – 2000Ω | 0 – 2Ω | 0 – 20Ω |
Accuracy | LOOP | ±(3%rdg+6dgt) | ±(3%rdg+10dgt) | ±(3%rdg+4dgt) | ±(3%rdg+25mΩ) | ±(3%rdg+4dgt) |
PFC/PSC | Depending on the accuracies of voltage and LOOP measurements. | |||||
Test current @ 230V | L-N:6A/60ms N-PE:10mA (5.3Hz) |
L-PE: 15mA | 20Ω: 6A/20ms, 200Ω: 0.5A/20ms 2000Ω: 15mA/500ms |
25A/20ms | 6A/20ms | |
RCD | ||||||
Mains input voltage range: 100V – 260V 50/ 60Hz. For Type AC and A RCDs rated at 100mA or higher: 190 – 260V. | ||||||
Mode | Rated residual operating current (mA)(IΔn) | Test current | Duration | |||
Current (mA) rms | Accuracy @230V | Meas. time | Accuracy | |||
x 1/2 | AC | G: 10/30/100/300/500/1000 S: 100/300/500 | IΔn×1/2 | -8% to-2% VAR:-10% to 0% | 2000ms | Trip Time ±(1%+2ms) Measuring time ±3% of FS |
A/F | G: 10/30/100/300/500 AS:100/300/500 | IΔn×1/2 | -10% to 0% | |||
B | G: 10/30/100/300 S:100/300 | IΔn×1/2 | -10% to 0% | |||
x 1 | AC | G:10/30/100/300/500/1000 S: 100/300/500 | IΔn | +2% to +8% VAR:0% to +10% | G:550ms S:1000ms |
|
A/F | G: 10/30/100/300/500 AS:100/300/500 | IΔn×1.4 (10mA: IΔn×2) | 0% to +10% | |||
B | G: 10/30/100/300 S:100/300 | IΔn×2 | 0% to +10% | |||
6 mA DC | IΔn | 0% to +10% | 10.5s | |||
x 5 | AC | G: 10/30/100 S: 100 | IΔn×5 | +2% to +8% VAR:0% to +10% | 410ms | |
A/F | G: 10/30/100 AS: 100 | IΔn×5×1.4 | 0% to +10% | |||
B | 10/30 | IΔn×2×5 | 0% to +10% | |||
Ramp 20 to 110% |
AC | 10/30/100/300/500 S: 100/300/500 | IΔn | -4% to +4% | by 10% G: 300ms S: 500ms |
Measuring time ±3% of FS |
A/F | G: 10/30/100/300/500 AS:100/300/500 | IΔn×1.4 (10mA:IΔn×2) | -10% to +10% | |||
B | G: 10/30/100/300 S: 100/300 | IΔn×2 | -10% to +10% | by 2% /150ms | ||
Ramp EV 30 to 100% | 6 mA DC | IΔn | -10% to +10% | by 2% / 500ms | - | |
General | ||||||
Applicable Standards | IEC 61010-1 CATIII (600V) CATIV (300V) pollution degree 2, IEC 61010 -Tester , -2-030, -2-034, IEC61557-1,2,3,4,5,6,7,10, IEC 60529 IP40, EN 61326-2-2 (EMC). |
|||||
Battery type | Size AA Alkaline battery (LR6) x 8. | |||||
Display | >Colour Dot Matrix LCD 320(W) X 240(H) pixels. | |||||
Operating temperature | -10 to +50°C. | |||||
Dimensions | 136 (L) x 235 (W) x 114 (D) mm. | |||||
Weight | 1300g including batteries (8 x AA / LR6). |
No customer reviews for the moment.