Megger MFT1741 Multifunction Tester
Includes: Printed quick start guide, Full user guide on CD, Calibration certificate, Switched probe SP5, Neck strap - Megger embroidered, 3 Wire lead set with prods and clips, Mains plug test lead, AC battery charger, Large soft pouch with extra storage.
The Megger MFT1741 multifunction tester is an instrument designed for testing low voltage electrical installations and especially in locations that suffer from high electrical noise.
The MFT1741 offers all of the facilities needed to test electrical installations in line with the requirements of the IET Wiring Regulations, as well as valuable additional functionality such as the earth electrode resistance measurement.
As well as three-wire non-trip loop impedance testing, the MFT1741 offers two-wire testing, which is invaluable when tests must be carried out at locations where no neutral connection is available. High-current testing which delivers the fastest possible results for circuits that are not protected by an RCD or RCBO is also available.
New Loop Impedance testing technology
The MFT1741 includes a new non-trip loop testing technology that:
Prevents any influence the RCD may present to the total loop impedance value.
Faster non-trip loop testing down to 8 seconds.
This technique also allows testing of loop impedance through 10mA type AC and Type A RCDs.
Overlaying the new non-trip loop impedance measurement is the new Megger “Confidence meter”. As loop impedance values can be dramatically affected by circuit noise, the Confidence Meter displays the degree of confidence in the accuracy of the measured loop impedance. Using the digital ARC to indicate the analytical process, the measurement is continually monitored and adjusted when circuit noise is present, resulting in a dramatically improved and repeatable test result.
FEATURES
Enhanced non-trip loop impedance measurement technology.
“Confidence meter” measurement analysis (patent pending).
Full single and 3 phase compliant installation testing.
10 mA to 1 A single and 3 phase RCD testing.
Simple colour-coded test selection.
Ambidextrous operation.
Insulation ranges | |||
100 V | |||
250 V, 500 V | |||
1000 V | |||
Test voltage display | |||
Adjustable buzzer threshold | |||
Continuity and resistance ranges | |||
200 mA test | |||
15 mA test | |||
Adjustable buzzer threshold | |||
Loop testing | |||
2 and 3 wire non-tripping L-PE 50 V ~ 280 V | |||
2 wire Hi current L-N 50 V ~ 280 V | |||
2 wire phase to phase L-L 50 V ~ 500 V | |||
PSCC and PFC (20 kA max.) | |||
Max. Zs display | |||
R1 + R2 value | |||
Touch voltage display on faulty earth | |||
Earth electrode test | |||
2 and 3 pole * | |||
3 pole ART and Stakeless method * | |||
RCD tests | |||
1/2, 1, 5 x I and ramp RCD test | |||
Auto RCD test | |||
Type AC, A and S RCDs | |||
Type B (pure DC) RCDs | |||
Programmable RCD | |||
3-phase RCD (no earth) | |||
30, 100, 300 and 500 mA RCD | |||
10 mA and 1000 mA RCD | |||
Other features | |||
Supply measurement | |||
True RMS | |||
Phase rotation | |||
Hard moulded case | |||
Confidence meter noise reduction | |||
New hardware loop test platform | |||
* requires optional accessory |
Insulation | |||
Output voltage | -0% +20% at rated load or less. | ||
Voltage display | ±3% ±3 digits ±0.5% of rated voltage. | ||
Resolution | 0.1 A. | ||
Internal current measurement | 0 to 220 A. | ||
Resistance & Continuity | |||
Accuracy |
0.01 Ω ~ 99.9 Ω - ±2% ±2 digits
100 Ω ~ 99.9 kΩ - ±5% ±2 digits.
|
||
Open circuit voltage | 5 V ±1 V. | ||
Test current |
(0 Ω ~ 2 Ω)
205 mA ±5 mA
15 mA ±5 mA
(user selectable).
|
||
Loop Test | |||
Live to earth/neutral supply | 48 V ~ 280 V (45 Hz ~ 65 Hz). | ||
Live to live supply | 48 V ~ 500 V (45 Hz ~ 65 Hz). | ||
L-N/L-L tests | ±5% ±5 digits. | ||
L-E tests†
|
0.1 Ω ~ 39.9 Ω: ±5% ±5 digits ± noise margin 40.0 Ω ~ 1000 Ω: ±10% ±5 digits. |
||
† Reference conditions apply | |||
RCD Tests | |||
Supply up to 100 mA | 48 V ~ 480 V (45 Hz ~ 65 Hz). | ||
Supply up to 1 A | 48 V ~ 280 V. | ||
RCD type | Type AC, A, S Type B (pure dc). |
||
No trip test | (1/2xI) –10% ~ –0%. | ||
Trip test |
(1xI, 2xI and 5xI) +0% ~ +10%.
|
||
General Specifications | |||
Power supply | IEC LR6 type AA alkaline (6 cells - supplied) or 1.2 V NiMH (rechargeable pack of 6 – supplied) Mains charger for on-board re-charging (4 hours typical). |
||
Data storage | 1000 results. | ||
EMC | IEC61326 edition 2 location class B. | ||
Operating temperature range | -10 °C ~ +55 °C. | ||
IP rating | IP54. | ||
Dimensions | 220 mm H x 390 mm W x 285 mm D. | ||
Weight | 1 kg (with batteries, excluding case). | ||
Megger MFT1741 warranty | One year (upgradeable to 3 years FREE). |
No customer reviews for the moment.
COMPONENT |
DESCRIPTION | PART No. | ||
PowerSuite Lite | 17th Edition software. | 1000-631 | ||
Test lead set | Fused 10 A test lead set (red/blue/green) with prods and clips. | 1001-975 | ||
ETL30 | Extension Test Lead 30 m. | 1000-215 | ||
ETL50 | Extension Test Lead 50 m. | 1000-217 | ||
ICLAMP | Current measuring clamp. | 1001-012 | ||
VCLAMP | Voltage inducing clamp, calibration check pcb (for stakeless test) and lead. | 1001-013 | ||
Earth kit | 3 Pole Earth Test Kit. | 6210-160 | ||
Car charger | Cigar lighter adapter for battery charging. | 6280-332 |