- Hamilton01698 829711
- Leeds0113 235 1356
- Belfast02890 830302
Beha-Amprobe UAT-610-EUR Kit
Includes: UAT-600-R Receiver, UAT-600-T Transmitter, CC-UAT-600 Carrying Case, TL-UAT-600 Test Leads Kit (black test lead with detachable black alligator clip, red test lead with permanently attached red alligator clip, ground stake), 2 x FP-UAT-600 Replacement Fuses, 6 x AA Batteries, 8 x D Batteries.
Accidentally hitting a utility line during a project can lead to costly repairs and create hazardous public safety situations. Digging in the wrong place can also lead to unnecessary delays and costs for your project, and ultimately, your company. Avoid this disruption with the rugged and durable Amprobe UAT-610, designed to accurately pinpoint underground utilities and buried services up to 100 feet deep with accurate depth measurement to 20 feet.
The locating kit comes complete and ready for use with a Transmitter, Receiver, test lead kit, batteries and additional fuses, all in a mobile, protective duffle bag. The UAT-620 kit also includes a Signal Clamp for transmitting a signal when it is not possible to make electrical contact with the cable to be traced. For applications where ground fault locating is required, use the UAT-600 Transmitter in combination with the optional A-Frame accessory.
What truly sets the UAT-600 Series apart from other underground locators is its CAT IV 600 V safety rating. This allows you to safely connect the Transmitter directly to an energised line up to 600 V in a CAT IV environment. Previously, if a crew needed to trace a specific electrical line by transmitting a signal through it, the line had to be de-energised first, adding time and reducing productivity.
FEATURES
Multiple tracing modes allow you to locate and trace energised and de-energised utilities in a variety of applications.
Locate energised 50/60 Hz cables carrying current
Identify any point of leakage around a cable.
Locate cable and wire ground faults, sheath faults or pipeline coating defects, where the utility is in direct contact with the ground.
Find the exact point where metal is touching the ground and power is leaking.
2 frequency options: 8 kHz and 33 kHz.
Take depth and current measurements.
Measure voltage, resistance and output current.
Advanced locating with two people.
UAT-610 Kit | UAT-620 Kit | |
UAT-600-R Receiver | ||
UAT-600-T Transmitter | ||
CC-UAT-600 Carrying Case | ||
TL-UAT-600 Test Leads Kit | ||
FP-UAT-600 Replacement Fuse | ||
User Manual | ||
Quick Reference Guide | ||
6 x 1.5 V AA (IEC LR6) Batteries (Receiver, not installed) | ||
8 x D-Cell Batteries (Transmitter, not installed) | ||
SC-600 Signal Clamp |
Features | UAT-600-R Receiver | UAT-600-T Transmitter | SC-600 Signal Clamp (included with UAT-620, optional for UAT-610) |
Measurement category | CAT IV 600 V. | ||
Operating voltage/current | 0 to 600 V. | 0 to 600 V, 100 A max. | |
Operating frequency/tracing modes | Active tracing: 33 kHz and 8 kHz Passive tracing: 50/60 Hz and Radio. |
Energised circuit Induction mode: 33 kHz Direct connection modes: 8 kHz and 33 kHz Clamp mode: 8 kHz and 33 kHz De-Energised circuit Induction mode: 33 kHz Direct connection modes: 8 kHz, 33 kHz, A-Lo/A-Hi A-Frame: 8 kHz Clamp mode: 8 kHz and 33 kHz. |
33 kHz and 8 kHz. |
Locating modes | Peak and Null | – | – |
Depth measurement and accuracy | Up to 20 ft 4 in to 10 ft: pm; 3 % 10 ft to 20 ft: pm; 5 % |
– | – |
Display backlight | Automatic | Yes | – |
Audio indication | Increasing closer to the signal | Fast beeps showing the better signal is applied. | – |
Transmitting mode power output | – | Max. 3 watts. | – |
Output voltage | – | Max. 50 V rms. | – |
Output current | – | Max. 250 mA rms, constant current in 5 steps. | – |
Signal voltage output (nominal) | – | – | 23 V rms at 8 kHz 30 V rms at 33 kHz. |
Mains voltage measurement | – | 0 V to 600 V, 50 Hz to 60 Hz Resolution: 1 V Accuracy: pm; 10% |
– |
Resistance measurement (De-energised circuit) |
– | 0 ohm; to 999 k ohm; Range: 0 ohm; to 999 ohm; (resolution: 5 ohm;) Range: 1 k ohm; to 999 k ohm; (resolution: 1 k ohm;) Accuracy: pm; 10% |
– |
Output hazardous voltage warning | – | ≥ 30 V rms | – |
Mains hazardous voltage warning | – | ≥ 30 V rms | – |
Sensitivity adjustment (gain control) | Yes | – | – |
Sensitivity at 1 m (typical) | Power: 2 mA Radio: 20 μA 8 kHz: 5 μA 33 kHz: 5 μA |
– | – |
Display | 4.3 in, 320 x 240 BW outdoor LCD display with auto backlight | LCD display (LED backlight) 2.4 in x 1.3 in |
– |
Update rate | Instantaneous | Current (mA): 10 ms Voltage (V): 15 ms Resistance ( ohm;): 330 ms. |
– |
Operating temperature and humidity | -4 °F to 122 °F (-20 °C to 50 °C), ≤90% RH. | ||
Storage temperature and humidity | -40 °F to 140 °F (-40 °C to 60 °C), ≤90% RH | ||
Operating altitude | < 6561 ft (< 2000 m) | ||
Pollution degree | 2 | ||
Water and dust resistance | IP54 | ||
Drop proof | 3.28 ft (1 m) | ||
Power supply | (6) 1.5 V AA alkaline batteries | (8) 1.5 V D cell alkaline batteries. | – |
Auto power off | 15 minutes idle | – | – |
Battery life | Approx. 35 hours at 70 °F (21 °C) (Typical) | Approx. 16 hours at 70 °F (21 °C) (Typical) | – |
Overload protection | – | 600 V rms Fuse FF 500 mA, 1000 V, IR 30 kA, Φ6.3×32 mm |
– |
Safety compliance | IEC 61010-1, IEC 61010-2-033 CSA/UL 61010-1, CSA/UL 61010-2-033 |
IEC 61010-1, IEC 61010-2-033 CSA/UL 61010-1, CSA/UL 61010-2-033 IEC 61010-031, CSA/UL 61010-031 (test leads) |
IEC 61010-1, IEC 61010-2-033 CSA/UL 61010-1, CSA/UL 61010-2-033. |
Size (H x W x L) | Approx. 11.9 x 4.7 x 30.7 in (302 x 120 x 779 mm) | Approx. 14 x 9 x 4.7 in (355 x 230 x 120 mm) | Approx. 11.6 x 7.1 x 1.4 in (295 x 180 x 37 mm). |
Weight | Approx. 4.2 lb (1.9 kg) (batteries installed) | Approx. 7.0 lb (3.2 kg) (batteries installed) | Approx. 1.9 lb (0.85 kg). |
No customer reviews for the moment.
COMPONENT | DESCRIPTION | PART No. | ||
SC-600-Euro | Signal clamp for UAT-600 series. | 4994647 | ||
AF-600 | A-Frame cable ground fault locator. | 4994583 | ||
TL-UAT-600 | Test lead set for UAT-600 Series. | 4994446 | ||
CC-UAT-600EUR | Carrying case for UAT-600 Series. | 9027 | ||
FP-UAT-600 | Fuse, 2 pack for UAT-600 Series. | 4994468 |