Includes: TPI 717R Kit 1 contains all of the standard accessories and includes the A740 Infrared Printer.
The TPI 717R Kit 1 contains all of the standard accessories and includes the A740 Infrared Printer.
The TPI 717R flue gas combustion analyser features pre-calibrated, replaceable oxygen and carbon monoxide smart sensors to make sensor replacement in the field simple. Its built-in magnet enables hands-free use.
The 717R features a 10,000 ppm CO sensor with quick recovery time, an in-line water trap that protects the sensor from water damage and a pump filter that helps prevent the pump from becoming clogged with dirt/dust debris. The 3-line LCD makes readings easy to see, and the smart sensors are simple to replace in the field, so you can get back to finishing the job.
Fast purge and the ability to perform fuel selection during start-up enable tests to be performed quickly without requiring extra set-up time after initial startup. TPI analysers also use the last selected fuel as the default setting. This feature prevents the need to perform fuel selection every time the analyser is turned on. The instrument is ruggedly constructed and comes with a limited 6 Year Warranty*.
*Subject to annual servicing being carried out by TPI or one of their approved service centres.
FEATURESInstrument | ||
---|---|---|
Operating Temperature Range | -10˚C to +50˚C. | |
Battery / Battery Life | Rechargeable Ni-MH / > 6 Hours. | |
Charger Input Voltage | 115V or 230V : 50/60 Hz AC. | |
Fuels | Natural Gas, LPG, Light Oil, Heavy Oil, Bituminous Coal, Anthracite Coal, Coke, Butane Wood (Dry), Bagasse, Wood Pellet. | |
Pressure Ranges | mbar, kPa & inH2O. | |
Display | Backlit LCD. | |
Data Storage | 50 sets of readings. | |
Time and Date | 24 Hour Real Time Clock. | |
Dimensions | 200 x 90 x 60mm. | |
Weight | 500g. | |
Casing | Rubber Boot as Standard. | |
Switch Off | Failsafe. | |
Exhaust | Safety Spigot. | |
Conforms to | BS7927 (and the draft BS7967). |
Construction | Pistol Grip with Stainless Steel Shaft. |
Hose Length | 2500mm. |
Insertion Length | 200mm. |
'K' Type Thermocouple Accuracy | +/- 0.3%, +/- 1˚C. |
Maximum Temperature | 800°C. |
Gases | Range | Resolution | Accuracy |
Oxygen | 0-25% | 0.1% | +/- 0.3% |
Carbon Monoxide | 0-10,000 ppm | 1 ppm | <20 ppm : +/- 3 ppm >100 ppm : +/- 5 % |
Carbon Dioxide (calculated) | 0-25% | 0.1% | +/- 0.3% |
Combustion Efficiency | 0-100% | 0.1% |
Selectable Ranges | mbar, kPa and inH2O. |
Range | - 150 mbar to + 150 mbar. |
Resolution | 0.01 mbar & 0.1 mbar. |
Accuracy | +/- 0.5% fsd. |
Input Type | K-Type thermocouple | |
Range | -58°F to 1832°F (-50°C to 1000°C)* | |
Resolution | 1°F (1°C) | |
Accuracy | +/- (0.3% of rdg + 2°F) or +/- (0.3% of rdg + 1°C). | |
* The thermocouple supplied (GK11M) has the ability to measure temperatures in the -50°F to 950°F range. The 712 accepts industry standard K-type thermocouple probes with sub-mini connectors. |