- Hamilton01698 829711
- Leeds0113 235 1356
- Belfast02890 830302
Chauvin Arnoux CA8333 Qualistar+ Power Analyser
The multiple functions of the Qualistar+ C.A 8333 make it a versatile instrument. It is suitable for applications up to 1,000 V in CAT III and 600 V in CAT IV.
Designed for test and maintenance departments working in industrial or administrative buildings, the Qualistar+ C.A 8333 can be used to obtain a snapshot of the main features characterising the quality of the electrical network. The analyser's functions make it the ideal instrument for preventive or corrective maintenance. It can also be used to perform a complete energy survey of an installation.
The C.A 8333 captures and records all the parameters, transients, alarms and waveforms simultaneously. When current sensors are connected to the C.A 8333, it recognizes them automatically. It also offers the possibility of mixing different types of current sensors and configuration of the ratios allows direct reading of the measurements.
The CA8333 IS NOT SUPPLIED with current clamps, although the manufacturer recommends their MN93, MN93A, MA193, PAC93, A193-450, A193-800, C193 and E3N current clamps to carry out current measurements.
KEY FEATURES
Real-time display of wave forms (4 voltages and 4 currents).
Half-period RMS measurements of voltages and currents.
Intuitive use.
Automatic recognition of the different types of current sensors.
Measurement on any type of installation: three-phase, Aron, etc.
Integration of all the DC components.
Measurement, calculation and display of harmonics up to the 50th order.
Display of phasor diagram.
Measurement of P, Q, S and D power values (total and per phase).
Energy measurement (total and per phase).
Calculation of the K Factor & FHL.
Calculation of distorting voltages and currents.
Calculation of the cos φ displacement power factor (DPF) and the power factor (PF).
Inrush over up to 10 minutes.
Capture of hundreds of transients lasting several tens of µs.
Calculation of Pst & Plt flicker values.
Unbalance calculation (current and voltage).
Monitoring of the electrical network with setting of alarms.
IEC 61000-4-30 Class B.
Back-up and recording of screenshots (image and data).
Recording and export on PC.
Software for data recovery and real-time communication with a PC.
Technical Specification | CA8331 | CA8333 | CA8336 | CA8436 |
Number of Channels | 3U / 4I | 4U / 4I | ||
Number of Inputs | 4V / 3I | 5V 4I | ||
Voltage (TRMS AC+DC) | 2V to 1,000 V. | |||
Voltage Ratio | Up to 500 kV. | |||
Current (TRMS AC+DC) MN Clamps | MN93: 500 mA to 200 Aac; MN93A: 0.005 Aac to 100 Aac. | |||
C193 Clamp | 1 A to 1,000 Aac. | |||
AmpFlex® or MiniFlex® clamps | 100 mA to 10,000 Aac. | |||
PAC93 Clamp | 1 A to 1,300 Aac/dc. | |||
E3N Clamp | 50 mA to 100 Aac/dc. | |||
J93 | 50 A to 3,500 Aac / 5,000 Adc. | |||
Current Ratio | up to 60 kA. | |||
Frequency | 40 Hz to 69 Hz. | |||
Power Values | W, VA, var, VAD, PF, DPF, cos φ, tan φ. | |||
Energy Values | Wh, varh, VAh, VADh. | |||
Harmonics | Yes. | |||
THD | yes, orders 0 to 50, phase. | |||
Expert Mode | - | Yes. | ||
Transients | - | 50 | 210. | |
Flicker Pst | Yes. | |||
Plt | - | - | Yes. | |
Inrush Mode | - | Yes on 4 periods | Yes> 10 minutes. | |
Unbalance |
Yes. | |||
Recording Min/Max | Yes. | |||
of a selection of parameters at the Max sampling rate. | 4 hours to 2 weeks | Few days to several weeks | 2 weeks to several years. | |
Alarms | - | 4,000 of 10 different types | 10,000 of 40 different types. | |
Peak | Yes. | |||
Vectorial representation | Automatic. | |||
Display | Colour ¼ VGA TFT screen, 320 x 240, diagonal 148 mm. | |||
Capture of screens and curves | 12 | 50. | ||
Electrical safety | IEC 61010 1,000 V CAT III / 600 V CAT IV. | |||
Protection | IP53 / IK08 | IP67. | ||
Languages | More than 27. | |||
Communication interface | USB. | |||
Battery life | Up to 13 hours. | |||
Power supply | 9.6 V NiMH rechargeable battery or external mains charger. | |||
Dimensions | 240 x 180 x 55 mm | 270 x 250 x 180 mm. | ||
Weight | 1.9Kg | 3.7Kg. |
No customer reviews for the moment.
COMPONENT |
DESCRIPTION | PART No. | ||
MN93 | Current clamp. AC Measurement range: 500 mA to 200 A. | P01120425B | ||
MN93A | Current clamp. AC measurement range: 0.005 A to 100 A. | P01120434B | ||
MA193-200 | MiniFlex. 100 mA to 10 kA ac. 70 mm Ø. Single, black. | P01120580 | ||
MA193-350 | MiniFlex. 100 mA to 10 kA ac. 100 mm Ø. Single, black.. | P01120567 | ||
PAC93 | AC/DC. 1 to 1000 A ac/1400 dc. | P01120079B | ||
PA30W | Mains power supply. | P01102057 | ||
Dataviewer Pro | Software for 833* & 843* series. | P01102095 |