Seba HV Tester 25 kV DC
Includes: Tester, incl. rechargeable battery and leather case, Mains lead, Battery lead for external DC battery, approx. 3m, Ground lead, approx. 3m, for connection to station ground, Ground lead, approx. 3m, for connection to protective ground High voltage lead, approx. 3m, with terminal, Seba HV Tester 25 kV Operating manual.
The HV Tester 25 kV is a high-voltage generator with a variable negative DC output voltage of 0 - 25 kV. The condition of the test object with regard to electrical strength and insulation quality can be determined on the basis of the unit's readings for output voltage and current. Due to its small size and internal battery this test-system is ideal for test-conditions where no external power supply is available.
FEATURES
Compact and light
DC and insulation testing for cables, joints, electrical installations etc.
Highly flexible use thanks to built-in battery.
Internal discharge.
Short-circuit-proof output.
Input voltage (selectable) | Mains 115 V / 230 V 50 / 60 Hz (115 V) internal rechargeable battery external battery 11 ... 15V DC. |
Output Voltage | 0 ... 25kV DC, negative polarity. |
Measuring range | 0 ... 30kV. |
Precision | 1.5%. |
Output current | 1.5mA at max. output voltage. |
Measuring range | 0 ... 0,2mA and 0 ... 2mA. |
Precision | 1.5%. |
Battery operating time | approx. 45 min at full load. |
Max. discharge energy | 3000J. |
Operating temperature | -25°C ... +55°C. |
Storage temperature | -40°C ... +70°C. |
Dimensions (W x H x D) | 467 x 168 x 284 mm. |
Weight | approx. 13.5 kg (incl. batteries). |
HV Tester 25 warranty | One-year. |