T&R PT15-10S DC Cable Test System
Includes: Supply lead, spare fuse, operating manual, output lead, DP20 discharge probe, earth lead, shoulder strap.
The T&R PT15-10S high voltage dc test set is designed to perform tests on installed cable and jointing systems. The units have a variable output voltage with a maximum of ±15kVdc with a maximum charging capability of 10mA. A zero-volt interlock is fitted that prevents the output being switched on unless the output control is at zero.
The unit includes an automatic load discharge system that discharges the cable under test when the output is switched off or a breakdown occurs. The internal dumping system can discharge a maximum of 1.25kJ, corresponding to 7.5μF at 15kV. A DP20 discharge probe is also supplied as standard with the PT15-10S, allowing cables with a capacitance of up to 12μF to be discharged at 15kV.
The output voltage is metered by a large, linear, analogue instrument marked 0-15 kV. The current in the test object is metered by a second analogue instrument with 0-10 scale marking. The meter reads 0-10 mA directly, or 0-1 mA when the ÷10 push button is operated.
In the event of a test object failure, the overload circuit will automatically switch off the output voltage and earth the output via the internal discharge circuit.
FEATURES
0 to – 15kVdc output voltage.
10mA output capability.
Both voltage and current metered on HV output.
Automatic earth system for dumping capacitive loads.
HV output plug & socket.
Key operated supply switch to prevent unauthorised operation.
Zero-volt interlock.
Visual indication of test piece failure.
Compact unit with lightweight insulated case.
Output | |||
---|---|---|---|
Unit Type | Voltage | Continuous | 5 Minutes |
PT15-10S | 0 to - 15 kV. | 5 mA. | 10 mA. |
The above intermittent on times must be followed by an off time of 15 minutes and is based on ambient temperature of 25° C. | |||
Metering | |||
The positive and negative output voltages on the PT series are metered on the HV output by separate analogue instruments. | |||
Unit | Range | Accuracy | |
PT15-10S | 0 to 15 kV. | ±1.5% of full scale. | |
The output current on both of the outputs is metered by a dual range analogue instrument. The 1 mA range is selected by the 10 pushbutton adjacent to the mA meter. | |||
Unit | Range | Accuracy | |
PT15-10S | 10 mA. 1 mA. | ±2.5% of full scale. ±2.5% of full scale. | |
Overload Protection | |||
The PT15-10S is protected by an overload trip on the output that operates at 12mA. | |||
Supply Requirements | 115V/230 V±10% auto-selecting 50/60 Hz 1ph 250 VA max. | ||
Protection and safety | |||
The output of the unit is protected by an overload trip, and the input and control supplies are protected by fuses. | |||
General | |||
Storage temperature | -20° C to 60° C. | ||
Operating temperature | 0°C to 45° C. | ||
Dimensions | 340 x 230 x 330 mm. | ||
Weight | 11 kg. | ||
T&R PT15-10S warranty | 1 year. |