- Hamilton01698 829711
- Leeds0113 235 1356
- Belfast02890 830302
Martindale MARVIPDLOK138-S Voltage Indicator, Proving Device & Lock
The complete solution for safe isolation, the Martindale VIPDLOK138 Lock Out Kit contains the VI13800 voltage indicator, PD440S proving device, along with a complete lock out kit, supplied with soft carry cases.
The complete solution for safe isolation, the Martindale VIPDLOK138 Lock Out Kit contains the VI13800 voltage indicator, PD440S proving device, along with a complete lock out kit, supplied with soft carry cases.
The VI13800 voltage indicator and matching PD440V proving unit are supplied in the TC71 combination carry cases to ensure that the proving device is always at hand and provide the simplest solution for implementing safe isolation practices on-site in accordance the Electricity at Work Regulations. For convenience and to save time, the proving unit can be used without having to remove it from the case.
The kit comprises of 7 different locking devices for simple fitting to MCBs, RCBOs and fuse holders. There is a plastic body padlock with a 6mm hardened steel shackle for securing the locking devices and a steel safety hasp which allows multiple padlocks to be used. Multi-lock hasps ensure a circuit cannot be re-energised until each operator has finished work and removed their own padlock.
Features
50V – 600V AC/DC.Polarity & Voltage indication 50V.
Heavy duty double insulated cable with contrasting inner core to reveal any damage.
Bright LED AC/DC voltage and polarity indication.
GS38 and BS EN61243-3 compliant.
440V industry leading proving unit for all low and high impedance testers.
The full 15 piece kit includes: PD440S Proving device, VI13800 Voltage indicator, PAD11RD Padlock with unique key, LOKHASP25 Hasp, LOK1 MCB green isolation lock, LOK2 MCB yellow isolation lock, LOK3 MCB blue isolation lock, LOK4 MCB small red isolation lock, LOK5 MCB red isolation lock, LOK10 Yellow MCB lock, 10mm clip, LOK11 Red MCB lock, 8mm clip, 5 Locked out tags, LOKMP Black marker pen, TC55 Soft carry case,TC71 Soft carry case.
PD440S Specifications | |
---|---|
Output voltage | 440V nominal. |
Output frequency | 50Hz nominal. |
Output loading | See datasheet. |
Temperature (Operating & Storage) | -10°C to 40°C. |
Humidity (Operating & Storage) | Max. 70% R.H.. |
Pollution degree | 2. |
Power | 6 x 1.5V, AA alkaline batteries (IEC LR6, NEDA 15A). |
Dimensions | 150 x 80 x 35mm. |
Weight | 350g approx. with batteries. |
Martindale VI-13800 Voltage Indicator Specifications | |
Voltage range | 50-600V AC/DC. |
LED indication | ± 50, 100, 200, 400V. |
AC/DC voltage detection | automatic. |
Range detection | automatic. |
Response time | <0.1s. |
Frequency range | DC, 1-400Hz. |
Test current | 3.5mA max at 600V AC/DC. |
Duty ratio | 30s ON/240s OFF. |
Temperature range | -10°C to + 55°C ≤ 85% RH. |
IP rating | IP54. |
Supply | From circuit under test. |
Dimensions | 205 x 67 x 27mm. |
Weight | 130g approx. |
Complies with | BS EN 61243-3 GS38 CAT IV 600V Class II double insulation. |
No customer reviews for the moment.