- Hamilton01698 829711
- Leeds0113 235 1356
- Belfast02890 830302
Martindale EasyPat2100 Dual Voltage PAT Tester
Includes: Removable earth bond lead, Flash Test pistol probe with trigger, 110 volt adaptor, 230V Extension Lead Adaptor, Carry bag for accessories, attached to Easy PAT 2100, Spare Fuses, Instruction manual, Certificate of Conformity.
For a high speed, fully specified manual PAT tester your choice is simple, the Martindale EPAT2100. Testing 110V and 240V as standard, the EPAT2100 can also be powered by 110V or 240V allowing you to run test a variety of appliances at either voltage. With 5 tests (earth bond, insulation, run current, run leakage and flash test) it really is the tester with everything. Perfect for production line and repair testing as well as any other PAT testing.
On power up the EasyPat 2100 monitors the supply voltage, adjusts its measurement circuits and selects the correct test socket accordingly. The display indicates the supply voltage on which tests will be carried out.
The Easypat2100 has a built in lead tester for testing IEC power leads and includes all accessories for fast testing of mains extension leads. The lead tester will perform a polarity test and clearly indicates any faults found during the test.
FEATURES
Suitable for onsite PAT testing and workshop applications.
Simple one button, one test operation.
Fast and easy Class I & Class II appliance testing.
Tests both 240V and 110V appliances based on supply voltage.
High and low current earth bond tests at 8A, 25A and 200mA.
Insulation test at 500V.
Extension & IEC lead testing built-in.
Run current & leakage tests for full appliance testing.
Hipot / Flash testing for tool hire and workshop service & repair applications.
Mains powered 110V/240V with instant on.
Hard case with storage and removable top.
Earth Continuity Test (8A) | ||
Test Voltage | 6 V AC nominal with no load. | |
Test Current | 8 A AC nominal @ 0.1Ω. 5 A nominal @ 0.5 Ω. | |
Range | 0.1 - 99 Ω. | |
Accuracy | ±10% of reading ± 2 digits. | |
Earth Continuity Test (25A) | ||
Test Voltage | 6 V AC nominal with no load. | |
Test Current | 25 A AC nominal @ 0.1 Ω. 10 A AC nominal @ 0.5 Ω. | |
Range | 0.1 - 99 Ω. | |
Accuracy | ±10% of reading ± 2 digits. | |
Earth Screen Test (100mA) | ||
Test Voltage | 130 mV DC nominal open circuit. | |
Test Current | 100 mA DC nominal constant current. | |
Range | 0.1 - 99 Ω. | |
Accuracy | ±10% of reading ± 1 digit. | |
Insulation Test | ||
Test Voltage | 500 V DC, -0%, +20%, at 2 MΩ and 7 MΩ. | |
Short Circuit Current | 1 mA DC nominal. | |
Display Range | 0 to 19.9 MΩ. | |
Accuracy of Indication | ±5% of reading ± 1 digit. | |
Run Current Test | ||
Range | 0 to 19 A. | |
Accuracy | ±10% of reading ± 1 digit. | |
Earth Leakage Test | ||
Range | 0 to 19.9 mA. | |
Accuracy | ±10% of reading ± 1 digit. | |
Flash Test | ||
Test Voltage | 1.5 kV AC - Class I. 3.0 kV AC - Class II. | |
Display Range | 0 to 19.9 mA AC. | |
Usable Range | 0-3 mA AC (current trip @ 4 mA nominal) (short circuit current 5 mA nominal). |
|
Accuracy | ±5% of reading ± 1 digit. | |
Leads | ||
Mains | 1.5 m fixed lead with 13 A moulded plug. | |
Earth Continuity | 1.5 m long, detachable lead with a heavy duty, shrouded crocodile clip. | |
Flash Gun | A safety gun, giving extra user protection for flash testing. Compatible with the EasyPAT and MicroPAT. 4 mm socket. | |
110/240V Adaptor | 110 V 16 A Plug (BS4343) to 240 V 13 A free socket (BS1363). | |
Sockets | ||
Mains | 240V 13A to Bs1363. 110V 16A to BS4343. | |
Flash | 4mm high voltage safety socket. | |
Lamps | ||
Flash | Neon lamp which illuminates when flash test is active. | |
Over Temperature | Red LED which illuminates when the temperature limit of the instrument is exceeded. | |
Fuses | ||
Front Panel | 16 A (FF), 1.25", HBC, ceramic. | |
Plug | 13 A, 1", HBC, ceramic. | |
Internal | 3.15 A (F), 5 x 20 mm, HBC, ceramic. | |
General Specifications | ||
Temperature | Operating: 0 to 35°C Storage: -10 to 50°C. |
|
Supply | Voltage: 110 V/240V ±10% 50/60 Hz Power Consumption: 10/220 V A (excluding run). |
|
LCD | 0.7" high, 2 ½ digit LCD with annuciators to indicate supply voltage of the mains and units of measurement in use. | |
Dimensions | Size: 330 x 263 x 144 mm. | |
Weight | 5.1 kg. | |
Martindale EPAT2100 warranty | 2 years. |
No customer reviews for the moment.
COMPONENT |
DESCRIPTION | PART No. | ||
Earth Bond Lead | Earth bond lead with XLR style connector, suitable for the Martindale EPAT1600, EPAT2100 & MicroPAT Plus. | MARTL66 | ||
TL151 | 4 pin, 16A 3 phase socket to UK mains plug, allows testing of earth bond and insulation from PAT testers. | MARTL151 | ||
TL152 | 5 pin, 16A 3 phase socket to UK mains plug, allows testing of earth bond and insulation from PAT testers. | MARTL152 | ||
TL153 | 4 pin, 32A 3 phase socket to UK mains plug, allows testing of earth bond and insulation from PAT testers. | MARTL153 | ||
TL154 | 5 pin, 32A 3 phase socket to UK mains plug, allows testing of earth bond and insulation from PAT testers. | MARTL154 | ||
EX331 | 110V Extension Lead Adaptor, use with PATs that have the IEC lead test built in to test 110V extension leads. | MAREX331 | ||
TL166 | A safety gun, giving extra user protection for flash testing. Supplied with the EasyPAT2100 and MicroPAT 4mm socket. | MARTL166 | ||
PAT Register Book | This handy A5 register allows you to keep manual records of PAT testing results for up to 315 appliances to ensure your system is fully compliant. | MARPATREG |