Megger TTRU3 Transformer Turns Ratiometer
Includes: 3Ø Transformer Turns Ratio Test Set, AC Power Cord & Adapters, USB 2.0 Cable, Tap Changer, Canvas carrying bag for test leads, Ground Cable, Thumb Drive, Triple Function Pen.
The Megger TTRU3 ratio meter test set is a fully automatic, self-checking, menu-driven turns ratiometer. The test set measures the turns ratio, vector relationship, excitation current as well as transformer diagnostic health indicators of power, distribution, and instrument transformers. The design of this instrument is such that it operates properly, independent of line voltage quality and frequency. This allows use of any generator driven power source of 500W or higher.
The TTRU3 is designed to test ALL power, instrument, and distribution transformers without the need of traditional high voltage excitation. With our patent pending step up technique, you are no longer required to know the “proper” test voltage to apply to obtain a “good” result - the test set decides for you - all in a box that is up to 35% smaller and lighter than other turns ratio meters.
With 3Ø excitation, testing is up to five times faster than previous phase-by-phase switching single instruments, and errors due to loading of delta secondary and tertiaries are problems of the past.
The test set can be used to test single-phase and three-phase transformers, both with and without taps in accordance with the requirements of the IEEE C57.12.90 – 2013 and IEC 60076-1 standards. For three-phase measurements, the test set is connected to all three phases of the transformer to be tested. The TTRU3 applies all three phases simultaneously which permits automatic measurement of all phases without changing connections.
The TTRU3 is also designed to operate single phase on three phase transformers to help isolate transformer phase related issues. The TTRU3 measures turns ratio, phase deviation and excitation current readings which are displayed on the built in 7 inch color display or customer PC.
Unlike other transformer ratiometers, the TTRU3 operates in both step up and step down ratio mode. Step down ratio excites the primary and measures the induced voltage on the secondary, while step up excites the secondary and measures the induced voltage on the primary.
FEATURES
3Ø test voltage - fast testing of all transformers.
Patent pending 3Ø Step Up Testing.
Confirm expected nameplate vector configuration.
Ability to measure actual vs expected phase shift.
Unique kelvin clamps with adjustable 3-inch jaw.
Banana plug input for connection to terminal blocks.
Turns ratio % error vs nameplate with pass/fail.
PC interface via USB for remote control operation and downloading of test results.
MODEL |
TTRU3EXP | TTRU3PRO | TTRU3ADV |
Max Turns Ratio | 50,000 Down / 200 Up | 50,000 Down / 200 Up | 50,000 Down / 100 Up |
Max Induced Voltage | 250 V | 250 V | 125 V |
Ø Shifting TX’s Measurement | up to 50,000 records and 2,000 photos | up to 10,000 records | up to 2,000 records |
Magnetic Balance | Optional | Optional | |
Printer | Optional | Optional | |
Power DB Control | Optional | Optional | |
Clone facility to set up multiple testers | Optional | Optional |
Input Power | 90-264 VAC, 47-63 Hz, 250 VA Max. |
Output | |
---|---|
Voltage | 3Ø, 1-48 VAC, up to 250 V on Primary. |
Frequency | 50-480 Hz. |
Current | 0.1 mA - 1 A, Max 1 A @ 48 V. |
Turns Ratio Measurement Methods | 3Ø Step Up 3Ø Step Down 1Ø Step Up 1Ø Step Down. |
Turns Ratio Range and Accuracy - Guaranteed accuracy from -20°C to +50°C. | |
Step Down Excitation | |
25-48 V | ±0.05% 0.8 - 1000 ±0.10% 1001 - 2000 ±0.30% 2001 - 15000 ±1% 15001 – 50000. |
1-24 V | ±0.10% 0.8 - 1000 ±0.20% 1001 - 2000 ±0.60% 2001 - 15000. |
Step Up Measurement | |
25-250 V | ±0.05% 0.8 - 200 (most Power Tx). |
1-24 V | ±0.10% 0.8 - 200. |
Excitation Current Measurement | |
Resolution | 0.1 mA 0.1 mA - 100 mA - 1 mA 101-1000 mA. |
Accuracy | ± 1% ±0.1 mA. |
Frequency Measurement | |
Resolution | 0.1 Hz. |
Accuracy | ±0.1% ±0.1 Hz. |
Transformer Phase Measurement | |
Range | 0 - 360 Degrees. |
Accuracy | ± 0.05 Degrees. |
General Specifications | |
Operating Temperature | -20°C to +50°C (-4°F to +122°F). |
Storage Temperature | -30°C to +70°C (-22°F to +158°F). |
Relative Humidity | 0-90%, non-condensing. |
Safety | IEC 61010-1:2010 + AMD1:2016. |
EMI/EMC | IEC 61326-1:2012. |
RoHS2 | EN50581. |
Display | 180mm (7 in.) 800 x 480 Resolution 1100 NITS. |
Transformer Testing Standards | IEEE C57.152-2013 IEC 60076-1:2011 AS/NZS 6076 1:2014 CIGRE 445 2011. |
Internal/External Data Storage | Up to 2000 sets of 3 phase results internal storage Transferable via USB 2.0/3.0 thumb drive. |
Communication/Control Software | 180mm (7in) built it display running custom GUI USB Interface for PC Control running custom GUI. |
Printer Output | 51mm (2in) thermal printer Prints all measurement data displayed on GUI. |
Case | Ruggedized case with fold out feet Canvas carrying bag for leads and accessories. |
Weight | 6.5 Kg (14lbs). |
Dimensions | 406 x 304 x 254mm (16 x 12 x 8in.) |
Megger TTRU3 warranty | One-year. |