- Hamilton01698 829711
- Leeds0113 235 1356
- Belfast02890 830302
Metrel MI 3280 DT Analyser
Includes: Metrel MI 3280, 4 wire test lead with Kelvin clips, 2.5 m 4 pcs, USB cable, Mains cable, Soft carrying bag, Metrel ES Manager BASIC license*, Instruction manual, Calibration certificate. *Metrel ES Manager can be downloaded free of charge from Metrel Web server.
The Metrel MI 3280 Digital Transformer Analyser is a multi-function, portable battery (Li-ion) powered test instrument with excellent IP protection: IP65 (case closed), IP54 (case open), intended for diagnosing of: turn ratio, phase deviation and excitation current of single and three phase transformers and winding resistance of single and three phase transformers.
It is used for verification of electrical safety and functional testing of EVSE. It is intended for testing Mode 3 EV supply equipment with a type 2 connector. If used together with Metrel AUTOSEQUENCES®, prebuilt in the newer multifunctional testers, the complete EVSE charging station can be tested (state-by-state) electrically and functionally with a push of a button. It is possible to create a professional station-based report with MESM.
FEATURES
Turn ratio measurement of single and three phase transformers.
Phase deviation between high voltage and low voltage winding.
Excitation current.
Winding resistance measurement of single and three phase transformers (Power Transformers up to 1,6 MVA).
A 3.4' color LCD display with touch screen.
Easy to operate.
Test results can be stored on the instrument.
Built-in help screens for referencing on site.
Autotest sequences.
Built-in charger and rechargeable batteries as standard accessory.
BT communication with PC, Android tablets and smart phones via built-in BT.
PC SW Metrel ES Manager for creation of test structures and uploading, downloading of test results, autotest editor and report creation.
High degree of protection IP 65 (case closed), IP 54 (case open).
TURN RATIO r, rA, rB, rC | |||
Function | Measuring Range | Resolution | Accuracy |
Excitation voltage 80 V | 0.8000 ... 9.9999 | 0.0001 | ±(0.2% of reading + 2 digits). |
10.000 ... 99.999 | 0.01 | ±(0.2% of reading + 2 digits). | |
100.00 ... 999.99 MΩ | 0.01 | ±(0.2% of reading + 2 digits). | |
1000.0 MΩ ... 1999.9 MΩ | 0.1 | ±(0.5% of reading + 2 digits). | |
2000.0 ... 3999.9 | 0.1 | ±(0.5% of reading + 2 digits) | |
4000.0 ... 8000.0 | 0.01 | ±(1.0 % of reading + 2 digits). | |
Excitation voltage 40 V | 0.8000 ... 9.9999 | 0.0001 | ±(0.2% of reading + 2 digits) |
10.000 ... 99.999 | 0.001 | ±(0.2% of reading + 2 digits) | |
100.00 ... 999.99 | 0.01 | ±(0.2% of reading + 2 digits). | |
1000.0 Ω ... 1999.9 | 0.01 | ±(0.% of reading + 2 digits). | |
2000.0 Ω ... 3999.9 | 0.1 | ±(0.% of reading + 2 digits). | |
4000.0 ... 8000.0 | 0.1 | n/a | |
Excitation voltage 5 V | 0.8000 ... 9.9999 | 0.0001 | ±(0.2% of reading + 2 digits) |
10.000 ... 99.999 | 0.001 | ±(0.2% of reading + 2 digits) | |
100.00 ... 999.99 | 0.01 | ±(0.5% of reading + 2 digits). | |
1000.0 Ω ... 8000.0 | 0.1 | n/a. | |
Excitation voltage 1 V | 0.8000 ... 9.9999 | 0.0001 | ±(0.2% of reading + 2 digits) |
10.000 ... 99.999 | 0.001 | ±(0.5% of reading + 2 digits) | |
100.00 ... 999.99 | 0.01 | n/a. | |
1000.0 Ω ... 8000.0 | 0.1 | n/a. | |
EXCITATION CURRENT i, iA, iB, iC | |||
Test frequency 55, 65 or 70 Hz | 0.10 mA ... 9.99 mA | 0.01 mA | ±(2.% of reading + 2 digits). |
10.0 mA ... 99.9 mA | 0.1 | ±(2.% of reading + 2 digits). | |
100 mA ... 999 mA | 1 mA | ±(2.% of reading + 2 digits). | |
1.00 A ... 1.10 A | 0.01 A | ±(2.% of reading + 2 digits). | |
PHASE DEVIATION fi, jA, jB, jC | |||
Test frequency 55, 65 or 70 Hz | -180.00 ... 180.00 ° | 0.01° | ±(0.05°) |
WINDING RESISTANCE R, RA, RB, RC | |||
Test current 10 mA ... 1000 mA | 1.0 mΩ ... 999.0 mΩ | 0.1 mΩ | ±(2.% of reading + 3 digits). |
1.000 Ω ... 9.999 Ω | 0.001 Ω | ±(2.% of reading + 3 digits). | |
10.00 Ω ... 99.99 Ω | 0.01 Ω | ±(2.% of reading + 3 digits). | |
100.0 Ω ... 999.9 Ω | 0.1 Ω | ±(2.% of reading + 3 digits). | |
General Specifications | |||
Battery power supply | 14.4 V DC (4.4Ah Li-ion). | ||
Battery charging time | ypical 4.5 h (deep discharge). | ||
Mains power supply | 90-260 VAC, 45-65 Hz, 100 VA (300 V CAT II). | ||
Protection classification | reinforced insulation. | ||
Measuring category | 50 V CAT IV. | ||
Pollution degree | 2 | ||
Degree of protection | IP 65 (case closed), IP 54 (case open). | ||
Dimensions (w x h x d) | 360 x 160 x 330 mm. | ||
Weight | 8.8 kg, (with battery and accessories). |
No customer reviews for the moment.
COMPONENT |
DESCRIPTION | PART No. | ||
Test Lead 2.5m | Test leads with large Kelvin clips to connect on H0-H1 terminal of MI 3280. Jaw opening 35 mm and cable length of 2.5 m. | A 1615 2M5 | ||
Test Lead 5m | Test leads with large Kelvin clips to connect on H0-H1 terminal of MI 3280. Jaw opening 35 mm and cable length of 5 m. | A 1615 5M | ||
Set of Test Leads with Clips | Set of 8 test leads with Kelvin clips with jaw opening 35 mm and 5 m long. | S 2102 | ||
Test leads with large Kelvin clips | Test leads with large Kelvin clips to connect on H2-H3 terminal of MI 3280. Jaw opening 35 mm and cable length of 2.5 m. | A 1618 2M5 |