Metrel MI3108ST Eurotest Solar PV Tester
Includes: MI 3108 Eurotest PV, Soft carrying bag, Tip commander, Test lead, 3 x 1.5 m, Test probe x3, Crocodile clip x3, PV Safety Probe, PV MC3/4 male/female adapters, AC/DC current clamp, PV reference cell + cable adapter, Temperature probe + cable adapter, Power supply adapter + 6 NiMH AA batteries, USB and RS232 - PS/2 cable, PC SW EuroLink PRO, Carrying straps, Instruction manual and handbook on CD, Calibration certificate.
The Metrel MI 3108 EurotestPV is a combined photovoltaic tester and electrical installations safety tester. It enables complete testing of electrical installations according to EN 61557 standards and in addition performs all necessary tests required on single-phase photovoltaic (PV) installations.
This includes all of the tests as required by EN 62446, but also includes I - U characteristic, Calculation of STC values as required by EN 61829 and power measurements on Inverter’s DC and AC sides.
The unit is designed for the demanding working conditions (up to 1000 V, with 15 A DC). To greatly improve user safety the MI 3108 EurotestPV comes with the PV Safety Probe which ensures safe disconnection every time.
MEASURING FUNCTIONS
Photovoltaic installations.
Measurements on DC side of PV installation.
Voltage, current, power.
Uoc (Open Circuit Voltage) and Isc (Short Circuit Current).
I - U curve of PV modules and strings.
Irradiance.
Module temperature.
Measurements on AC side of PV installation.
Voltage, current, power.
Efficiency of PV module, inverter, PV system calculation.
Photovolyaic Installation Measurements | ||
Function | Measuring Range | Basic Accuracy |
Voltage | 0 V DC ... 999 V DC 0 V AC ... 999 V AC I-V m.: 0 V DC ... 999 V DC |
±(1.5 % of reading + 5 digits) ±(1.5 % of reading + 3 digits) ±(2 % of reading + 2 digits) |
Current | Panel m.: 0.0 mA ... 300 A DC Invert. m.: 0.0 mA ... 300 A AC I-V m.: 0.00 A ... 15 A DC |
±(1.5 % of reading + 5 digits) ±(1.5 % of reading + 3 digits) ±(2 % of reading + 3 digits) |
Power | Panel m.: 0 ... 200 kW I-V m.: 0 ... 15 kW |
±(2.5 % of reading + 6 digits) ±(3 % of reading + 5 digits) |
Energy | 0.000 Wh - 1999 kWh | |
U/I Curve | 1000 V / 15 A / 15 kW | |
Harmonics | up to 11th | |
Irradiation | 0 ... 2000 W/m2 | ±(5 % of reading + 5 digits) |
Temperature | -10 °C ... + 85 °C | ± 5 digits |
Electrical Installation Measurements |
||
Function | Measuring Range | Basic Accuracy |
Insulation Resistance (EN61557-2) | U = 50, 100, 250 VDC: R: up to 199.9 MΩ U = 500 VDC, 1 kVDC: R: up to 999 MΩ |
±(5 % of reading + 3 digits) ±(5 % of reading + 3 digits) |
Continuity, 200 mA (EN 61557-4) |
0.00 Ω ... 1999 Ω | ±(3 % of reading + 3 digits) |
Continuity, 7 mA | 0.0 Ω ... 1999 Ω | ±(5 % of reading + 3 digits) |
Loop impedance (EN 61557-3) | 0.00 Ω ... 9.99 kΩ | ±(5 % of reading + 5 digits) |
Line impedance (EN 61557-3) | 0.00 Ω ... 9.99 kΩ | ±(5 % of reading + 5 digits) |
Voltage | 0 VAC ... 550 VAC | ±(2 % of reading + 2 digits) |
Frequency | 0.00 Hz ... 499.9 Hz | ±(0.2 % of reading + 1 digits) |
Phase Sequence | 1.2.3 or 3.2.1 | |
RCD Testing (EN 61557-6) | IΔN: 10 mA, 30 mA, 100 mA, 300 mA, 500 mA, 1 A | |
Contact Voltage UC | 0.0 V ... 99.9 V | (-0 % / +15 %) of reading |
Trip Out Time | 0 ms ... max. time | ±1 ms |
Trip-out current | 0.2 x IΔN ... 2.2 x IΔN | ±0.1 x IΔN |
Earth resistance (EN 61557-5) | 0.00 Ω ... 9999 Ω | ±(5 % of reading + 5 digits) |
General | Main Unit | Remote Unit |
Display | 128 x 64 dots matrix display with backlight | |
Power Supply | 6 x 1.2 V NiMH batteries, type AA | |
Overvoltage Category | 1000 V DC / CAT II 600 V / CAT III; 300 V / CAT IV |
|
Protection Class | Double Insulation | |
COM Port | RS232 and USB | RS232 |
Dimensions | 230 x 103 x 115 mm | 140 x 230 x 80 mm |
Weight | 1.3 kg | 1.0 kg |
No customer reviews for the moment.
COMPONENT |
DESCRIPTION | PART No. | ||
EurotestPV Remote | PV remote unit for measurement and logging of irradiance and temperature values. | A 1378 | ||
Current Clamp (low range, leakage) | High accuracy current clamp 1000 A / 1 A with jaw opening 52 mm and fixed 1.5 m cable for both load and low range / leakage current . |
A 1018 | ||
Three Phase Adapter | 3-phase test adapter for installation safety testing on 3-phase sockets type 16 A 3CEE. | A 1110 | ||
PV Fused Test Lead | Test cable for simultaneous AC/DC power and efficiency measurements of PV inverters. | A 1385 | ||
AC/DC Current Clamp | Universal RTD A. | A 1391 |