T&R NLU2000 2000A Loading Unit
Loading unit for the T&R PCU1-SP primary current injection test system. 600A continuous output, upto 2000A intermittent.
The T&R NLU2000 Primary Current Injection Loading Unit is to be used in conjunction with the T&R PCU1-SP Primary Current Injection System. The NLU2000 delivers a maximum output of 2000A with three output taps to allow for a wide range of load impedance.
T&R NLU2000 & NLU5000 Loading Unit Specifications
Supply Requirements | |||||
---|---|---|---|---|---|
Loading Unit | Open Circuit Voltage | Load Current | Max Time For Load Current | Supply Current | |
NLU5000 | 2.3 V | 3000 A | 5 minutes | 30 A | |
5000 A | 40 seconds | 50 A | |||
4.6 V | 1500 A | 5 minutes | 30 A | ||
2500 A | 40 seconds | 50 A | |||
9.2 V | 750 A | 5 minutes | 30 A | ||
1250 A | 50 seconds | 50 A | |||
NLU2000 | 3.5 V | 1200 A | 5 minutes | 18 A | |
2000 A | 40 seconds | 30 A | |||
6.9 V | 600 A | 5 minutes | 18 A | ||
1000 A | 40 seconds | 30 A | |||
13.8 V | 300 A | 5 minutes | 18 A | ||
500 A | 40 seconds | 30 A | |||
Loading Unit Outputs | |||||
Loading Unit | Open Circuit Voltage | Continous Current | Intermittent Current | ||
5 Min On/15 Min Off | 1 Min On/15 Min Off | 40s On/15 Min Off | |||
NLU5000 | 2.3 V | 1500 A | 3000 A | 4500 A | 5000 A |
4.6 V | 750 A | 1500 A | 2250 A | 2500 A | |
9.2 V | 375 A | 750 A | 1125 A | 1250 A | |
NLU2000 | 3.5 V | 600 A | 1200 A | 1800 A | 2000 A |
6.9 V | 300 A | 600 A | 900 A | 1000 A | |
13.8 V | 150 A | 300 A | 450 A | 500 A |