T&R NLU2000 & NLU5000 Loading Unit Specifications
Supply Requirements
Loading UnitOpen Circuit Voltage Load CurrentMax Time For Load CurrentSupply Current
NLU50002.3 V3000 A5 minutes30 A
5000 A40 seconds50 A
4.6 V1500 A5 minutes30 A
2500 A40 seconds50 A
9.2 V750 A5 minutes30 A
1250 A50 seconds50 A
NLU20003.5 V1200 A5 minutes18 A
2000 A40 seconds30 A
6.9 V600 A5 minutes18 A
1000 A40 seconds30 A
13.8 V300 A5 minutes18 A
500 A40 seconds30 A
Loading Unit Outputs
Loading UnitOpen Circuit VoltageContinous CurrentIntermittent Current
5 Min On/15 Min Off1 Min On/15 Min Off40s On/15 Min Off
NLU50002.3 V1500 A3000 A4500 A5000 A
4.6 V750 A1500 A2250 A2500 A
9.2 V375 A750 A1125 A1250 A
NLU20003.5 V600 A1200 A1800 A2000 A
6.9 V300 A600 A900 A1000 A
13.8 V150 A300 A450 A500 A

No customer reviews for the moment.