- Hamilton01698 829711
- Leeds0113 235 1356
- Belfast02890 830302
T&R PCU1-SP mk2 Primary Current Injection System
Includes: Mains lead (5m), loading unit power and metering leads (5m), PCU1-SP operating manual and spare fuses.
The T&R PCU1-SP mk2 is a medium powered primary current injection system offering output currents up to 5000A (11.5kVA for 40seconds). The system consists of a separate control unit containing all metering and control functions and a loading unit that provides the high current output. In addition, the SP version offers direct-reading CT ratio and polarity tests and a 100A secondary injection output.
Two loading units are available, delivering a maximum output current of 2000A or 5000A. Each loading unit has three output taps to allow for a wide range of load impedances. For example, the NLU5000 may be configured to either give a maximum current of 5000A on the 2.3V range, 2500A on the 4.6V range or 1250A on the 9.2V range.
FEATURES
5kA maximum output current (higher overload currents for 2s).
Multi-function digital timing system.
Digital true RMS memory ammeter.
Solid state switching.
200A, 2000A and 5000A loading units.
Three range outputs on loading units.
Rugged, compact design.
Optional trolley mounting of system.
Secondary injection up to 100A.
Auxiliary metering input.
Direct reading CT ratio and polarity.
Feature | PCU1-SP mk2 | PCU2 | ||
Primary Injection | ||||
Max Output Power | 11.5 kVA / 40s | 20kVA / 5 min. | ||
Secondary Injection | ||||
CT Ratio / Polarity Test |
Range | Full Scale | Resolution | Accuracy | ||
NLU2000 | |||||
---|---|---|---|---|---|
10% | 200.0 A | 0.1 A | ±0.5%rdg+5d | ||
50% | 1000 A | 1 A | ±0.5%rdg+5d | ||
100% | 2000 A | 1 A | ±0.5%rdg+5d | ||
200% | 4000 A. | 1 A | ±1%rdg+5d | ||
NLU5000 | |||||
Range | Full Scale | Resolution | Accuracy | ||
10% | 500.0 A | 0.1 A | ±0.5%rdg+5d | ||
50% | 2500 A | 1 A | ±0.5%rdg+5d | ||
100% | 5000 A | 1 A | ±0.5%rdg+5d | ||
200% | 10 kA | 10 A | ±1.5%rdg+5d | ||
Timing System | |||||
Timer Resolution | 1 ms. | ||||
Timer Full Scale | 999.999s. | ||||
Timer Accuracy | ±0.01%rdg+2d (4 current mode). | ||||
Contact O/C Voltage | 24 V | ||||
Contact S/C current | 20 mA | ||||
Vdc Input Range | 24 - 240 Vdc. | ||||
PCU1-SP Dimensions & Weight | 450(w) x 275(h) x 305(d) mm / 26 kg. | ||||
NLU2000 Dimensions | 450(w) x 275(h) x 370(d) mm / 49 kg. | ||||
NLU5000 Dimensions | 450(w) x 275(h) x 370(d) mm / 58 kg. |