- Hamilton01698 829711
- Leeds0113 235 1356
- Belfast02890 830302
Fluke 1742 Three-Phase Power Quality Logger
Includes: Flexible current probe, USB stick, USB cable, 3PHVL-1730 3-Phase + neutral voltage test lead, Test lead set red/black 0.18 m, Test lead set red/black 1.5 m, Alligator clips, 173 x /174 x Soft Case, Cable marker kit, MP1-3R/1B-Magnet Probe 1 set (3 red, 1 black), 174x-Hanger Kit.
Power Quality Logger with 60 cm 1,500A iFlex
The Fluke 1742 Power Quality Logger is a compact device for technicians and engineers to troubleshoot, quantify energy usage, and analyse power distribution systems.
The Fluke 1742 is compliant with international standards such as IEC 61000-4 -30 and IEC 62586. The 1742 can simultaneously log up to 500 parameters and capture events to find intermittent and hard-to-find power quality issues.
An optimised user interface, flexible current probes, and an intelligent measurement verification function that allows you to digitally verify and correct connections makes setup easier than ever and reduces measurement uncertainty. Minimize your time in potentially hazardous environments and reduce the hassle of suiting up in PPE by using a wireless connection (WiFi) to view data directly in the field.
The included Energy Analyze Plus software enables thorough analysis of the captured data and reporting according to national and international standards such as EN 50160.
LICENSED FEATURES
License keys are available as optional accessories. The keys expand the functionality of the Logger with licensed features.
1742-6/UPGRADE
The upgrade license activates the advanced analysis features of the 1746 on a 1742 Logger. Features are:
Voltage and current unbalance.
Voltage and current interharmonics.
Events: Dips, swells, and interruptions.
Events: Rapid voltage change.
Events: Inrush current.
Events: Mains signaling.
The upgrade includes a Magnet Probe Set (3 red, 1 black).
1742-8/UPGRADE
The upgrade license activates the advanced analysis features of the 1748 on a 1742 Logger. Features are:
Voltage and current unbalance.
Voltage and current interharmonics.
Events: Dips, swells, and interruptions.
Events: Rapid voltage change.
Events: Inrush current.
Events: Mains signaling.
Events: Waveform deviation.
Event recordings: RMS profile.
Event recordings: Waveform.
Event recordings: Mains signaling RMS profile.
The upgrade includes a Magnet Probe Set (3 red, 1 black) and a Magnet Hanger Kit.
1742 Power Logger |
1746 Power Logger |
1748 Power Logger |
||
FUNCTIONS | ||||
Voltage, current, power, power factor, frequency | Y | Y | Y | |
Energy forward/reverse | Y | Y | Y | |
Peak Demand | Y | Y | Y | |
THD | Y | Y | Y | |
Voltage and current harmonics (to 50th)1
|
Y | Y | ||
Flicker | Y | Y | Y | |
Unbalance1
|
Y | Y | ||
Rapid voltage change events1
|
Y | Y | ||
Interharmonics (to 50th)1
|
Y | Y | ||
Dips, swells, interruption and transient events tables1
|
Y | Y | ||
Mains signaling1
|
Y | Y | ||
Inrush current1
|
Y | Y | ||
Transients (low frequency)/Waveform deviation events2
|
Y | |||
RECORDING | ||||
Trend
|
Y | Y | Y | |
Waveform snapshots2
|
Y | |||
RMS profile2
|
Y | |||
COMMUNICATION | ||||
Ethernet
|
Y | Y | Y | |
USB (mini B)
|
Y | Y | Y | |
WiFi download Instrument to device | Y | Y | Y | |
Wifi download via WiFi hub (requires registration) | Opt. | Opt. | Opt. | |
1Included with 1742-6/UPGRADE option 2Included with 1742-8/UPGRADE or 1746-8/UPGRADE option. |
Voltage | Range: 1000 V Maximum resolution: 0.1 V. |
|
Current: Direct input | See datasheet. | |
Frequency | Range: 42.5 Hz to 69 Hz Maximum resolution: 0.01 Hz. |
|
Auxiliary input | Range: ±10 V dc Maximum resolution: 0.1 mV. |
|
Electrical Specifications | ||
Power Supply | ||
Voltage range | 100 V to 500 V using safety plug input when powering from the measurement circuit. 100 V to 240 V MA-C8 and using standard power cord (IEC 60320 C7). |
|
Power consumption | Maximum 50 VA (max. 15 VA when powered using MA-C8 adapter). | |
Mains power frequency | 50/60 Hz ±15%. | |
Battery | Li-ion 3.7 V, 9.25 Wh, customer-replaceable. | |
On-battery runtime | Typically 4 hours. | |
Charging time | < 6 hours. | |
Data Acquisition | ||
Resolution | 16-bit synchronous sampling. | |
Sampling frequency | 10.24 kHz at 50/60 Hz, synchronized to mains frequency. | |
Input signal frequency | 50/60 Hz (42.5 to 69 Hz). | |
Circuit types | 1-Φ, 1-Φ IT, split phase, 3-Φ delta, 3-Φ wye, 3-Φ wye IT, 3-Φ wye balanced, 3-Φ Aron/Blondel (2-element delta), 3-Φ delta open leg, currents only (load studies). | |
Data storage | Internal flash memory (not user replaceable). | |
Memory size | Typical 20 logging sessions of 4 weeks with 1-minute intervals and 500 events. | |
Basic Interval | ||
Measured parameters | Voltage, current, aux, frequency, THD V, THD A, power, power factor, fundamental power, DPF, energy. | |
Averaging interval | User selectable: 1 sec, 5 sec, 10 sec, 30 sec, 1 min, 5 min, 10 min, 15 min, 30 min. | |
Averaging time min/max values | Voltage, Current: Full cycle RMS updated every half cycle (URMS1/2 according to IEC61000-4-30 Aux, Power: 200ms). | |
Demand Interval (Energy Meter Mode) | ||
Measured parameters | Energy (Wh, varh, VAh), PF, maximum demand, cost of energy. | |
Interval | User selectable: 5 min, 10 min, 15 min, 20 min, 30 min, off. | |
Power Quality Measurements | ||
Measured parameter | Voltage, frequency, unbalance, voltage harmonics, THD V, current, harmonics, THD A, TDD, voltage interharmonics, TID V, current interharmonics, TID A, Flicker, Mains Signaling, under/over deviation. | |
Averaging interval | 10 min for all parameters 2 hrs (long term Flicker PLT) 150/180 cycles (3 s) for harmonics (requires software license IEEE519/REPORT). |
|
Individual harmonics | 2nd to 50th harmonic Grouping according to IEC 61000-4-7 user configurable depending on application: Sub-grouped (harmonics + interharmonics), grouped or harmonic bins only. |
|
Interharmonics | 1st to the 50th interharmonic. | |
Events | Voltage: dips, swells, interruptions, current: inrush current 1748: mains signaling, transients (low frequency). |
|
Inrush | RMS profile based on 1/2 cycle RMS steady state triggering. | |
Flicker | In accordance with IEC 61000-4-15 and IEEE 1453. | |
Programmable PQ limits | Enables user defined limits for local standards compliance. | |
Interfaces. | ||
USB-A | File transfer via USB flash drive, firmware updates, max. supply current: 120 mA. | |
WiFi | File transfer and remote control via direct connection or WiFi infrastructure. | |
Bluetooth | Read auxiliary measurement data from Fluke Connect® 3000 series modules (requires supported USB to BLE or WiFi/BLE adapter, check for availability). | |
USB-mini | Data download device to PC. | |
Voltage Inputs | ||
Number of inputs | 4 (3 phases referenced to neutral). | |
Maximum input voltage | 1000 Vrms, CF 1.7. | |
Input impedance | 10 MΩ. | |
Measurement category | 1000 V CAT III/600 V CAT IV. | |
Current Inputs | ||
Number of inputs | 4 (3 phases and neutral), mode selected automatically for attached sensor. | |
Input voltage | Clamp input: 500 mVrms/50 mVrms; CF 2.8. Rogowski coil input: 150 mVrms/15 mVrms at 50 Hz, 180 mVrms/18 mVrms at 60 Hz; CF 4 all at nominal probe range. |
|
Auxiliary Inputs | ||
Number of inputs | 2 (Analog with auxiliary adapter, or up to 2 BLE devices simultaneously). | |
Input range | 0 to ± 10 V dc, or 0 to ± 1000 V dc (with optional adapter), 1 reading/s. | |
Displayed units | User configurable (7 characters, for example, °C, psi, or m/s). | |
General Specifications | ||
Operating temperature | -25 °C to +50 °C (-13 °F to 122 °F)1. | |
Enclosure | IEC 60529: IP50. IEC 60529: IP65 with IP65 rated voltage connector. |
|
1Warm up the product to -10 °C (+14 °F) before you power the unit on | ||
Weight | Instrument: 1 kg (2.2 lb). | |
Dimensions | 23.0 cm x 18.0 cm x 5.4 cm (9.1 in x 7.1 in x 2.1 in). | |
Fluke 1742 warranty | Two-years (battery not included). Accessories: one-year. |
No customer reviews for the moment.
COMPONENT |
DESCRIPTION | PART No. | ||
1742-6/UPGRADE | Upgrade 1742 to 1746 functionality (includes magnetic probes). | 4920964 | ||
1742-8/UPGRADE | Upgrade 1742 to 1748 functionality (includes magnetic probes and hanger kit). | 4920973 | ||
i17XX-Flex6000/4PK | Fluke-17xx iFlexi 6000A 36 IN, 4 Pack. | 4637430 | ||
i17XX-Flex3000/4PK | Fluke-17xx iFlexi 3000A 24 IN, 4 Pack. | 4637427 | ||
i17XX-Flex1500/4PK | Fluke-17xx iFlexi 1500A 12 IN, 4 Pack. | 4637411 | ||
i17XX-flex6000/3pk | Fluke-17xx iFlexi 6000A 36 IN, 3 pack. | 4637370 | ||
i17XX-flex3000/3pk | Fluke-17xx iFlexi 3000A 24 IN, 3 pack. | 4637355 | ||
i17XX-flex1500/3pk | Fluke-17xx iFlexi 1500A 12 IN, 3 pack. | 4637337 | ||
i17XX-flex6000 | Fluke-17xx iFlexi 6000A 36 IN. | 4637362 | ||
i17XX-flex3000 | Fluke-17xx iFlexi 3000A 24 IN. | 4637343 | ||
i17XX-flex1500 | Fluke-17xx iFlexi 1500A 12 IN. | 4637328 | ||
Fluke 17XX-TL 0.18M | Test lead set; 1000V CAT III, Non-stack conn; 0.18 m; Red/Blk. | 4921125 | ||
i40S-EL | Fluke-17xx i40s-EL Clamp-on Current Transformer. | 4637396 | ||
F17XX Cable Markers | Cable Marker Kit for 173X an 174X. | 4921140 |