- Hamilton01698 829711
- Leeds0113 235 1356
- Belfast02890 830302
Chauvin CA8345 Class A Qualistar Power Analyser
Includes: CA 8345 with its battery, SD card, 5x black straight-straight banana-banana safety leads attached with a Velcro tie, 5x black crocodile clips, 5x cable reels, hand strap, USB A-B cord, specific mains power unit with mains cord, PA40W-2 or PA32ER depending on the order, 12 sets of inserts and rings to mark the current leads and sensors according to their phases, carrying bag, carrying bag for the instrument, multilingual safety data sheet, test report, multilingual quick start guide.
Buy the Qualistar 8345 power quality analyser bundle and get the DataView data analysis software
and 4 Ampflex A193-450 clamps included!
The Chauvin CA 8345 Qualistar is a portable three-phase power quality analyser with built-in rechargeable battery. It is in compliance with the standard governing the methods of measurement of power quality, IEC 61000-4-30, class A.
Equally well suited for diagnostic fault finding on electrical installations, auditing electricity consumption and validating the quality of electrical supplies, the CA 8345 power quality analyser from Chauvin Arnoux combines exceptional flexibility with ease of use, extensive communication options and full compliance with IEC 61000-4-30 Class A. The CA 8345 sets new standards for versatility and convenience, and is suitable for use on all types of single-and three-phase systems up to 1,000 V.
Measurements supported by the Chauvin CA 8345 include all standard parameters such as voltage, current and frequency, together with P, N, Q1, S and D power values. Total and per-phase energy values can also be measured, along with details about harmonics from DC up to the 63rd order, and inter-harmonic subgroups from 0 to the 62nd order. TrueInrush technology is supported, and all measurements take DC components fully into account.
Results are shown in real time on a 7-inch colour touch-screen display which, according to the measurement in progress, can be configured to show numerical data, graphs, oscillograms or phasor diagrams. All results can be captured at user-defined intervals and stored for later analysis and reporting. To ensure accurate timing of the measurements, the CA 8345 has an internal GPS system which provides precise UTC synchronisation. Support for up to 20,000 user-configurable alarm conditions is also provided.
For communication, the CA 8345 offers USB 2.0, Ethernet 100 Mbps and Wi-Fi 802.11b/g interfaces. It also incorporates a webserver that provides a remote user interface when used in conjunction with Android, Microsoft and iOS apps. Software for real-time data access using a PC is freely available from the Chauvin Arnoux website.
Featuring compact yet robust construction and a magnetic hook to facilitate mounting, the new Chauvin Arnoux CA 8345 power quality analyser is easy to accommodate and install within distribution cabinets when making measurements over extended periods. It has an IP54 ingress protection rating and offers safety features that include automatic recognition of current sensors and a CAT IV 1,000 V rating in line with IEC 61010.
FEATURES
1000V three-phase analyser.
IEC 61000-4-30 Class Ed3, IEC 61000-4-7, IEC 61000-4-15.
Internal GPS clock.
Works on all existing electrical networks (single phase, three phase star, delta, ...).
7" WVGA colour TFT display with touch screen.
Always easy to use, automatic recognition of current sensors.
Compatible with Qualistar current sensors.
Low level currents: 100mA in miniFlex.
Recorder for EN50160 campaign.
Main signalling detection.
Wifi wireless communication for accessibility issues.
Ethernet communication for real time remote and/or multi-station.
USB communication for local data transfer.
Data saved on SD card for transport flexibility.
Phase powered (option PA32ER).
Webserver for remote control.
SCPI commands.
Data in JSON format.
Very small enclosure footprint for easy cabinet placement.
Magnetic hook for easy mounting.
IP54 to IEC 60529.
IEC 61010 CAT IV 1000V.
3 year warranty.
Inputs | Voltage/current, isolated. |
Voltage | 5 V to 1,000 Vac and Vdc. |
IEC 61000-4-30 (Ed 3) | Class A (Full). |
Screen | 7" colour LCD touch screen: 800 x 480 (WVGA). |
Clock/GPS | Yes, built-in. |
Real-time mode | Yes. |
Sampling rate | Voltage 400 kSps / Current 200 kSps / Surge 2 MSps. |
Power mode | Yes. |
Energy mode | Yes. |
Unbalance mode | composite. |
Harmonics mode | DC to 63rd order. |
Interharmonics mode | 0 to 62nd order. |
Trend recording | >900 parameters. |
Alarm mode (types/number) | 52 / 20,000. |
Carrier current detection mode | Yes. |
Inrush capture (number) | 100. |
2.5 μs transients (number) | No maximum (SD card). |
Shockwaves | Up to 12 kV sampled every 500ns. |
EN50160 monitoring mode | With PAT3 software. |
USB communication | Yes. |
SD card | Accessible, external. |
Ethernet | Yes. |
Wifi | Yes. |
Web server | Yes. |
USB key port (Type A) | Yes. |
Battery cartridge | Li-ion – 5800 Ah. |
EC 61010 safety | CAT IV 1000V. |
Protection | IP54. |
Operating temperature | [+0 °C; +40 °C]. |
Environmental compliance | IEC 61557-12 & IEC 62586. |
Dimensions (H x L x D) | 200 x 285 x 55 mm. |
Weight | 1.9 kg. |
Chauvin CA 8345 warranty | 3 years. |
No customer reviews for the moment.
COMPONENT |
DESCRIPTION | PART No. | ||
PA32ER | Mains power supply/charger. | P01160658 | ||
PA40W-2 | The PA40W power supply with charger can power the instrument when it is used over long periods. | P01102155 | ||
Hook | Magnetised hook mounting system. | P01103079 | ||
Strap | Wrist strap. | HX0122 | ||
Battery | Li-ion battery. | P01296047 | ||
C193 | Clamp. | P01120323B | ||
MN93 | Clamp. | P01120425B | ||
MN93A | Clamp. | P01120434B | ||
AmpFlex | AmpFlex® A193-450 mm clamp. | P01120556B | ||
AmpFlex | AmpFlex® A193-800 mm clamp. | P01120531B |