loading spinner
Megger PAT450 Dual Voltage PAT Tester with Flash
  • Megger PAT450 Dual Voltage PAT Tester with Flash
  • Megger PAT450 Dual Voltage PAT Tester with Flash
  • Megger PAT450 Dual Voltage PAT Tester with Flash
  • Megger PAT450 Dual Voltage PAT Tester with Flash

Megger PAT450 Dual Voltage PAT Tester with Flash

Megger approved distributor and service centre.

Includes: Megger PAT450 Downloadable PAT Tester, Printed Quick Start Guide, PAT 450 Full User Guide on CD, Calibration Certificate, Continuity/Earth Bond Lead + Probe, Extension Lead Adaptor (13A), Carry Case w/ Lead/Document Pouch, Plug Adaptor IEC C6 - C13 (3 Way 5A PSU).

1000-755
Megger
£1435.00
£1722 Inc. VAT

The PAT400 series from Megger is a new generation of downloading portable appliance testers, fully testing portable electrical equipment to the latest edition of the Code of Practice for the In-Service Inspection and Testing of Electrical Equipment.

The Megger PAT450, the top of the range, has all of the features of the Megger PAT420 and includes 1.5 kV and 3 kV flash testing. The Megger PAT450 is particularly suitable for use in tool hire shops where equipment is routinely tested prior to hire, or service workshops where deep disassembly is routine, and will perform a flash test in addition to standard PAT tests.

FEATURES

Vast on-board memory to keep you the job longer.
Continuous operation, no need to stop and wait for the tester to cool down.
Instant re-start as you move from room to room testing.
Soft keys to speed you through the testing process.
Full PAT testing including RCD testing.
Most productive tester in its class.
Selectable PASS/FAIL limits provide instant indication of a faulty asset.
230 & 110V operation for industrial, commercial and residential applications.
Ideal for tool hire shops and servicing workshops.

Megger PAT400 Series Product Video

Megger PAT450 Specifications
Electrical Supply Range
PAT410, PAT420, PAT450 230 V ±10 @ 50/60 Hz.
PAT420, PAT450 110 V ± 10% + 110 V ±10% @50Hz.
Bond Test (10A and 25A) Not PAT410
Open Circuit Voltage 9 V AC ±10% ± 0.1 V (supply: 230 V 50 Hz).
Earth Bond Resistance Accuracy ±5% ± 3 digits (0 to 0.49 Ω)
±5% ±5 (0.5 to 0.99 Ω).
Display Range 0 to 1.99 Ω.
Continuity Test (200mA)
Continuity Test Voltage 9 V AC ± 10% ± 0.1 V (supply: 230 V 50 Hz).
Continuity Resistance Accuracy ±5% ± 3 digits (0 to 0.49 Ω)
±5% ± 5 digits (0.5 to 0.99 Ω).
Continuity Resistance Resolution 10 mΩ (1 to 19.99 Ω).
Display Range 0 to 19.99 Ω.
Insulation Test (250V and 500V)
Insulation Resistance Accuracy (230 V) ±2% ± 5 digits (0 to 19.9 MΩ)
±5% ± 10 digits (20 to 99.99 MΩ).
Insulation Resistance Resolution 0.01 MΩ.
Display Range 0 to 99.99 MΩ.
Substitute Leakage Test
Test Voltage and Frequency 40 V AC ±10% nominal mains frequency.
Leakage Current Accuracy ±5% ± 5 digits.
Leakage Current Resolution 0.01 mA.
Display Range 0 to 19.99 mA.
Differential Leakage Current
Test Voltage Nominal mains 110/230 V AC.
Test Frequency Nominal mains 50/60 Hz.
Differential Leakage Current Accuracy ±5% ± 0.05 mA (1.0 mA to 9.99 mA)
±5% ± 0.1 mA (0.1 mA to 0.99 mA).
Resolution 0.01 mA.
Display/Measurement Range 0.10 mA to 19.99 mA.
Touch Current Test
Test Voltage and Frequency Nominal mains supply.
Touch Current Accuracy ±5% ± 5 digits.
Touch Current Resolution 0.01 mA.
Display 0 to 10 mA.
Operational Test
Test Voltage and Frequency Nominal mains supply.
VA Rating 230 V 3700 VA
110 V 1800 VA.
VA Accuracy ±5% ± 10 digits (0 to 99 VA)
±5% ± 50 digits (100 VA to 999 VA)
±5% ± 100 digits (1000 VA to 3700 VA).
Resolution 1 VA (0 to 3700 VA).
Display Range 0 to 3990 VA.
Extension Lead Test
Tests Performed Bond, insulation and polarity.
Polarity Test Voltage 12 V.
Polarity checks Lead ok
Live neutral S/C
Live neutral reversed
Live/neutral O/C.
Flash Test (PAT450 only)
Flash Test Voltage 1500 V AC nominal for class 1
3000 V AC nominal for class 2.
Flash Test Current <3.5 mA short circuit @ 253 V primary supply voltage.
Flash Test Breakdown Current Accuracy ±5% ±5 digits.
Flash Test Breakdown Current Resolution 0.01 mA.
Display Range 0 to 3.0 mA.
Portable RCD Test
Test Voltage and Frequency Nominal mains supply.
Test Current Accuracy -8% to -2% (1/2 x I)
+2 to +8% (1 x I, 5 x I).
Trip Time Accuracy ±1% ± 5 digits.
Trip Time Resolution 0.1 ms.
Display Range 0 to 1999 ms (1/2 x I)
0 to 300 ms (1 x I)
0 to 40 ms (5 x I).
Fuse Test
Test Voltage 3.3 V.
Warning Audible beep if fuse is OK.
Environmental
Operating Temperature -10 to 50°C.
Storage Temperature -20 to 60°C.
Humidity 90% RH @ -10 to 30°C
75% RH @ +30 to 50°C.
Maximum Altitude 2000m.
Ingress Protection IP40.
General
Weight 4.4 kg.
Dimensions 180 (H) x 255 (W) x 320 mm (L).
Safety IEC 61010-1: CAT II 300 V.
EMC IEC 61326-1: 2006
IEC 61326-2-2: 2005.
Megger PAT450 warranty One-year.

Download

Megger PAT400 Series Datasheet

PDF Specifications of the Megger PAT410, PAT420 & PAT450 Portable Appliance Testers.

Download (309.25k)

No customer reviews for the moment.

Write your review

Megger PAT450 Dual Voltage PAT Tester with Flash
COMPONENT
DESCRIPTION PART No.
110V Adapt 110 V Extension lead adaptor. 6220-639
110V Mains Adapt 10 V mains lead adaptor. 1000-766
415V Adapt 415 V adaptor lead (4-pin) to BS1363 (16 A). 1000-767
415V Adapt 415 V adaptor lead (5 pin) to BS1363 (16 A) . 1000-770
Scanner Barcode reader, USB. 1001-047
USB Printer Barcode Label Printer (Brother P700) (USB). 1005-423
USB Cable Lead USB Type A to Type B, Data/Printer cable. 1004-610
Cartridge Barcode printer label refills (cartridge). 90001-010
Barcode Labels Appliance barcode labels (1-1000). 6121-483
Pass Labels Roll of 1000 PASS test labels (Green). 1000-971
Fail Labels Roll of 1000 FAIL test labels (Red). 1001-227

10 other products in the same category: