loading spinner
Megger PAT420 Business In A Box
  • Megger PAT420 Business In A Box
  • Megger PAT420 Business In A Box
  • Megger PAT420 Business In A Box

Megger PAT420 Business In A Box

Megger approved distributor and service centre.

Includes: Printed quickstart guide, Full User guide on CD, Megger PAT420 Calibration certificate, PowerSuite software, Continuity / earth bond lead + probe (black), Extension lead adaptor 13A, Carry case with lead/document pouch, Plug adaptor IEC C6 - C13 (3 way 5A PSU), Roll of 1000 PASS test labels, Screen protector.

1001-411
Megger
Call For Price

The Megger PAT420 ‘Business in a Box’ from Megger includes everything an electrical contractor needs to diversify into PAT Testing. Any competent person can benefit from this package. It includes comprehensive guides on performing PAT testing, and marketing a PAT testing business to help any business or entrepreneur launch and promote this new venture.

The Megger PAT420 provides the same extensive memory and downloading capability as the Megger PAT410, but has the added features of 110 V operation, and also 10 A and 25 A earth bond testing. The large 5.7" colour LCD display allows for a clear, menu driven test process. The full QWERTY keypad on the PAT420 ensures asset data and descriptions can be easily added, and that test settings can be manually adjusted.

KEY BIAB FEATURES

Clear step by step instructions on how to do it.
Details of why they need to be testing their electrical assets.
Pre-designed adverts and brochures for you to use.
Pre-written letters for you to send to potential customers.
Arrange appointments.
Diary management.
Billing.
Automatic testing.
Printing certificates.
Repairs estimates.
A guide to PAT testing.
A guide to identifying customers.
Fast PAT420 tester that will give you years of service.
The leads and adaptors you need to test 230 V appliances.
1000 Pass labels.
PowerSuite Contractor PAT certification software to manage: Customers Assets.

Megger PAT400 Series Product Video

Megger PAT420 Specifications
Electrical Supply Range
PAT410, PAT420, PAT450 230 V ±10 @ 50/60 Hz.
PAT420, PAT450 110 V ± 10% + 110 V ±10% @50Hz.
Bond Test (10A and 25A) Not PAT410
Open Circuit Voltage 9 V AC ±10% ± 0.1 V (supply: 230 V 50 Hz).
Earth Bond Resistance Accuracy ±5% ± 3 digits (0 to 0.49 Ω)
±5% ±5 (0.5 to 0.99 Ω).
Display Range 0 to 1.99 Ω.
Continuity Test (200mA)
Continuity Test Voltage 9 V AC ± 10% ± 0.1 V (supply: 230 V 50 Hz).
Continuity Resistance Accuracy ±5% ± 3 digits (0 to 0.49 Ω)
±5% ± 5 digits (0.5 to 0.99 Ω).
Continuity Resistance Resolution 10 mΩ (1 to 19.99 Ω).
Display Range 0 to 19.99 Ω.
Insulation Test (250V and 500V)
Insulation Resistance Accuracy (230 V) ±2% ± 5 digits (0 to 19.9 MΩ)
±5% ± 10 digits (20 to 99.99 MΩ).
Insulation Resistance Resolution 0.01 MΩ.
Display Range 0 to 99.99 MΩ.
Substitute Leakage Test
Test Voltage and Frequency 40 V AC ±10% nominal mains frequency.
Leakage Current Accuracy ±5% ± 5 digits.
Leakage Current Resolution 0.01 mA.
Display Range 0 to 19.99 mA.
Differential Leakage Current
Test Voltage Nominal mains 110/230 V AC.
Test Frequency Nominal mains 50/60 Hz.
Differential Leakage Current Accuracy ±5% ± 0.05 mA (1.0 mA to 9.99 mA)
±5% ± 0.1 mA (0.1 mA to 0.99 mA).
Resolution 0.01 mA.
Display/Measurement Range 0.10 mA to 19.99 mA.
Touch Current Test
Test Voltage and Frequency Nominal mains supply.
Touch Current Accuracy ±5% ± 5 digits.
Touch Current Resolution 0.01 mA.
Display 0 to 10 mA.
Operational Test
Test Voltage and Frequency Nominal mains supply.
VA Rating 230 V 3700 VA
110 V 1800 VA.
VA Accuracy ±5% ± 10 digits (0 to 99 VA)
±5% ± 50 digits (100 VA to 999 VA)
±5% ± 100 digits (1000 VA to 3700 VA).
Resolution 1 VA (0 to 3700 VA).
Display Range 0 to 3990 VA.
Extension Lead Test
Tests Performed Bond, insulation and polarity.
Polarity Test Voltage 12 V.
Polarity checks Lead ok
Live neutral S/C
Live neutral reversed
Live/neutral O/C.
Flash Test (PAT450 only)
Flash Test Voltage 1500 V AC nominal for class 1
3000 V AC nominal for class 2.
Flash Test Current <3.5 mA short circuit @ 253 V primary supply voltage.
Flash Test Breakdown Current Accuracy ±5% ±5 digits.
Flash Test Breakdown Current Resolution 0.01 mA.
Display Range 0 to 3.0 mA.
Portable RCD Test
Test Voltage and Frequency Nominal mains supply.
Test Current Accuracy -8% to -2% (1/2 x I)
+2 to +8% (1 x I, 5 x I).
Trip Time Accuracy ±1% ± 5 digits.
Trip Time Resolution 0.1 ms.
Display Range 0 to 1999 ms (1/2 x I)
0 to 300 ms (1 x I)
0 to 40 ms (5 x I).
Fuse Test
Test Voltage 3.3 V.
Warning Audible beep if fuse is OK.
Environmental
Operating Temperature -10 to 50°C.
Storage Temperature -20 to 60°C.
Humidity 90% RH @ -10 to 30°C
75% RH @ +30 to 50°C.
Maximum Altitude 2000m.
Ingress Protection IP40.
General
Weight 4.4 kg.
Dimensions 180 (H) x 255 (W) x 320 mm (L).
Safety IEC 61010-1: CAT II 300 V.
EMC IEC 61326-1: 2006
IEC 61326-2-2: 2005.
Megger PAT420 warranty One-year.

Download

Megger PAT420 BIAB datasheet

PDF Specifications of the Megger PAT420 Business In A Box Portable Appliance Tester.

Download (276.83k)

No customer reviews for the moment.

Write your review

Megger PAT420 Business In A Box
COMPONENT
DESCRIPTION PART No.
110V Adapt 110 V Extension lead adaptor. 6220-639
110V Mains Adapt 10 V mains lead adaptor. 1000-766
415V Adapt 415 V adaptor lead (4-pin) to BS1363 (16 A). 1000-767
415V Adapt 415 V adaptor lead (5 pin) to BS1363 (16 A) . 1000-770
Scanner Barcode reader, USB. 1001-047
USB Printer Barcode Label Printer (Brother P700) (USB). 1005-423
USB Cable Lead USB Type A to Type B, Data/Printer cable. 1004-610
Cartridge Barcode printer label refills (cartridge). 90001-010
Barcode Labels Appliance barcode labels (1-1000). 6121-483
Pass Labels Roll of 1000 PASS test labels (Green). 1000-971
Fail Labels Roll of 1000 FAIL test labels (Red). 1001-227