Megger TXL870 Utility Load Unit
The Torkel TXL870 Telecom battery load unit is designed to provide higher load currents when used with the Megger TORKEL battery testers.
NB: The Megger TXL870 Utility (BS-59007) is supplied without accessories.
The Megger TXL870 load unit is designed for use together with TORKEL battery testers. Their purpose is to provide higher load currents for use in constant current or constant power tests. Together, TORKEL and the TXL extra loads form a system that can discharge batteries with currents of up to several kA. TXL extra loads are connected directly to the battery, and TORKEL measures the total current using a clamp-on ammeter.
The Torkel TXL870 extra load unit is shut down automatically when TORKEL is stopped.
AC/DC Voltage | ||||
---|---|---|---|---|
Voltage DC Max | Current Max | Power Max | ||
TXL830 | 28 V | 300 A | 8.3 kW | |
TXL850 | 56 V | 300 A | 16.4 kW | |
TXL870 | 280 V | 112 A | 15.8 kW | |
TXL890 | 480 V | 62 A | 15.4 kW | |
Internal Resistance, 3-Position Selector | ||||
Position 1 | Position 2 | Position 3 | ||
TXL830 | 0.275 Ω | 0.318 Ω | 0.092 Ω | |
TXL850 | 0.55 Ω | 0.275 Ω | 0.184 Ω | |
TXL870 | 4.95 Ω | 2.48 Ω | 1.24 Ω | |
TXL890 | 14.10 Ω | 7.05 Ω | 3.52 Ω | |
Maximal Currents, 3 Position Selector | ||||
Position 1 | Current | Voltage | Cells | Cell Voltage |
TXL830 | 100 A | 27.6 V | 12 | 2.3 V |
78.5 A | 21.6 V | 12 | 1.8 V | |
TXL850 | 100 A | 55.2 V | 24 | 2.3 V |
78.5 A | 43.2 V | 24 | 1.8 V | |
TXL870 | 50.1 A | 248.4 V | 108 | 2.3 V |
39.2 A | 194.4 V | 108 | 1.8 V | |
TXL890 | 32.3 A | 469.2 V | 204 | 2.3 V |
26.0 A | 367.2 V | 204 | 1.8 V | |
Position 2 | Current | Voltage | Cells | Cell Voltage |
TXL830 | 200 A | 27.6 V | 12 | 2.3 V |
156 A | 21.6 V | 12 | 1.8 V | |
TXL850 | 200 A | 55.2 V | 24 | 2.3 V |
156 A | 43.2 V | 24 | 1.8 V | |
TXL870 | 50.1 A | 124.2 V | 54 | 2.3 V |
39.2 A | 97.2 V | 54 | 1.8 V | |
TXL890 | 35.2 A | 248.4 V | 108 | 2.3 V |
27.8 A | 194.4 V | 108 | 1.8 V | |
Position 3 | Current | Voltage | Cells | Cell Voltage |
TXL830 | 300 A | 27.6 V | 12 | 2.3 V |
235 A | 21.6 V | 12 | 1.8 V | |
TXL850 | 300 A | 55.2 V | 24 | 2.3 V |
235 A | 43.2 V | 24 | 1.8 V | |
TXL870 | 100 A | 124.2 V | 54 | 2.3 V |
74.8 A | 97.2 V | 54 | 1.8 V | |
TXL890 | 70.5 A | 248.4 V | 108 | 2.3 V |
55.2 A | 194.4 V | 108 | 1.8 V | |
Environment | The instrument is intended for use in high voltage substations and industrial environments. | |||
Operating temperature | 0°C to +40°C (32°F to +104°F). | |||
Storage temperature | -40°C to +70°C (-40°F to +158°F). | |||
CE Marking | LVD: IEC61010-1:2010 EMC: IEC61326 -1. |
|||
Main Voltage | 100 – 240 V AC, 50 / 60 Hz. | |||
Power consumption | 75 W (max). | |||
Protection | Thermal cut-outs, automatic overload protection. | |||
Dimensions | Instrument: 210 x 353 x 600 mm (8.3” x 13.9” x 23.6”) Transport case: 265 x 460 x 750 mm (10.4” x 18.1” x 29.5”). |
|||
Weight | 13 kg (29 lbs) 21.4 kg (47 lbs) with transport case. | |||
Storage temperature | -40°C to +70°C (-40°F to +158°F). |