loading spinner
Martindale HPAT500/2 PAT Tester
  • Martindale HPAT500/2 PAT Tester
  • Martindale HPAT500/2
  • Martindale HPAT500/2
  • Martindale HPAT500/2

Martindale HPAT500/2 PAT Tester

martindale approved distributor

Includes: HPAT 500/2, Earth Bond Probe with Croc Clip, Calibration Certificate, 6 x 1800mAh NiMH Rechargeable Batteries, Mains Battery Charging Adaptor, 240V Extension Lead Adaptor, Soft Carry Case with Strap, Printed Instruction Manual.

MARHPAT500
£318.00
£381.6 Inc. VAT
The Martindale HPAT500/2 is a battery powered, hand held PAT tester with simple one-button test selection. It is ideal for use where there is no convenient power socket and provides a time saving solution when adopting a mobile approach to PAT testing.

Unlike similar PAT testers, the HPAT500/2 has a unique feature to counteract issues with testing appliances with long leads, or long extension leads, caused by the extra resistance added as a result of the lead length.

The HPAT500/2 has a new high contrast backlit display.

FEATURES

Simple One Button Operation.
Automatic Class I, Class II & power lead tests.
Pass / Fail Tester with Result.
Measured values displayed.
Selectable 250V insulation test for surge protected equipment.
I.T. safe 200mA DC earth bond test with two pass levels.
Rechargeable Batteries & Charger Included.
Low Current Bond Test for Sensitive IT Equipment.
Tests both 240V and 110V appliances.
Mains rechargeable with in-car option.
Ideal for Low Volume Testing.

Martindale HPAT500 Product Video

Martindale HPAT Comparison Chart
  HPAT400 HPAT500/2 HPAT600/2
Class I /II Test
Lead Test
Pass/Fail Indication
Test Values Displayed -
Selectable Limits - -
Test Mode Auto Auto Auto/Manual
Run Test - - Simulated
Earth Continuity Test Current 200 mA 200 mA 200m A
Insulation Test Voltage 500 V 250/500 V 250/500 V
110V Appliances With accessory With accessory With accessory
Memory - - 200 results for on-screen recall
Supply Alkaline batteries Rechargeable Rechargeable

Martindale HPAT500/2 Specifications
Earth Continuity
Test Voltage 4 V DC (into open circuit).
Test Current 200 mA DC (into short circuit).
Range 0 to 19.99 Ω.
Resolution 0.01 Ω.
Accuracy ± (5% of reading + 2 digits).
Fixed Pass Limits
Lead ≤ 0.10 Ω = PASS
≤ 0.20 Ω = NOTE x.xx PASS.
Class I Class I ≤ 0.10 Ω = PASS
≤ 0.20 Ω = NOTE x.xx PASS.
Insulation
Fixed Voltage >500 V DC at 1 mA (< 600 V DC into open circuit).
Test Current Test current: 1.5 mA (into short circuit).
Ranges 2.00 MΩ, 20.0 MΩ, 200 MΩ.
Resolution 0.01 MΩ.
Accuracy <100 MΩ ± (5% reading + 2 digits)
>100 MΩ ± (10% reading + 2 digits).
Fixed Pass Levels Lead: ≥ 1.0 MΩ
Class I: ≥ 1.0 MΩ
Class II: ≥ 2.0 MΩ.
Fuse Checks
Test Voltage 4V DC (into open circuit).
Test Current 200mA DC (into short circuit).
Pass Level >2mA.
General
Overload Protection 300 V AC/DC.
Protection Class IP20.
Safety Complies to BS EN 61010-1: 2001.
Temperature Range -10 to 40°C, non-condensing.
Batteries 6 x 1.2 V AA NiMH rechargeable batteries
1800mAh, or greater.
Battery Life Fully charged, minimum 600 complete
tests. The HPAT500 will operate fully from the battery
charger in the event of discharged batteries. Do not
remove batteries.
Auto Shut Down After 10 minutes of inactivity, or when battery low.
Battery Charger Input 230 V 50 Hz.
Battery Charger Output 12 V DC at 300mA, 5.5 jack x 2.5 bore centre
positive.
Dimensions 90 x 210 x 54 mm.
Weight Approx 700g (including batteries & leads).

Download

Martindale HPAT500 Datasheet

PDF Specifications of the Martindale HPAT500 Handheld PAT Tester.

Download (54.02k)

No customer reviews for the moment.

Write your review

Martindale HPAT500/2 PAT Tester
COMPONENT
DESCRIPTION PART No.
Earth Bond Lead Heavy duty earth bond lead with single 4mm banana plug connection, compatible with the Martindale HPAT500 & HPAT600. MARTL68
TL151 4 pin, 16A 3 phase socket to UK mains plug, allows testing of earth bond and insulation from PAT testers. MARTL151
TL152 5 pin, 16A 3 phase socket to UK mains plug, allows testing of earth bond and insulation from PAT testers. MARTL152
TL153 4 pin, 32A 3 phase socket to UK mains plug, allows testing of earth bond and insulation from PAT testers. MARTL153
TL154 5 pin, 32A 3 phase socket to UK mains plug, allows testing of earth bond and insulation from PAT testers. MARTL154
EX331 110V Extension Lead Adaptor, use with PATs that have the IEC lead test built in to test 110V extension leads. MAREX331
PAT Register Book This handy A5 register allows you to keep manual records of PAT testing results for up to 315 appliances to ensure your system is fully compliant. MARPATREG