loading spinner
Kewtech SMARTPAT
  • Kewtech SMARTPAT
  • Kewtech SMARTPAT
  • Kewtech SMARTPAT
  • Kewtech SMARTPAT

Kewtech SMARTPAT Manual PAT Tester

kewtech authorised distributor

Includes: Extension lead adapter (EZYLEAD), Earth continuity test lead with probe and croc clip (EZYEARTH), Mains Lead (EZYMAIN), Carry bag with strap.

SMARTPAT
£645.00
£774 Inc. VAT
In Stock

The Kewtech SMARTPAT is a hand-held portable appliance tester and can test the electrical safety of Class I and Class II appliances. The SMARTPAT performs tests and indicates PASS/FAIL results complying with the criteria of judgement defined in The IEE Code of Practice for In-service Inspection and Testing of Electrical Equipment: 2003.

FEATURES

Easy to use.
Converts into a full downloading PAT Tester with the KEWPAT APP.
Automatic test sequences - standard or make your own.
Large easy to read display.
250 V and 500 V insulation.
Battery operated - approx. 1400 tests.
IT safe with 200mA earth test and 250V insulation option.
PASS / FAIL – Green / Red screens.
Run / leakage at supply voltage (110V or 230V).
Portable RCD tests 10mA & 30mA.

KEWPAT APP

The SMARTPAT is a manual tester. The KEWPAT APP is designed to work with it enabling fast documentation. This facilitates record documentation, appliance risk assessment and in conjunction with your SimplyPats Manual+ software, covers your obligations for holding a product register to control your PAT testing.

Fast entry of the essential product information; what, where & ID number. Dropdown menus for:

Customer.
Site.
Location.
Description.
Auto-number increment.
New description or repeat.
Appliance description.
Scan feature for barcodes and QR code.

Kewtech SMARTPAT Out Of The Box

Kewtech SMARTPAT Specifications
Protective Conductor Resistance Test
Measuring range 0.00 - 20.00 Ω (NULL value inc)*
Over-range indication > 20.00 Ω.
Resolution 0.01 Ω.
Open-circuit voltage 5 V ±0.4 V DC.
Measuring current 200 mA DC (nominal value).
Accuracy ±3%rdg ±5dgt.
* Resistances exceeding 3 Ω cannot be cancelled by NULL function.
Mains Voltage 
Display range 30 - 270 V.
Hi/Lo indication < 30 V: No voltage indication > 270 V: 270 V.
Resolution & Accuracy 1 V ±3%rdg ±5dgt.
Insulation
Rated Voltage 250 V 500 V
Measuring range 0.00 - 20.00 MΩ.
Over-range indication > 20.00 MΩ.
Resolution 0.01 MΩ.
No-load voltage 250 V DC +20%, -0% 500 V DC +20%, -0%
Short-circuit current 1.5 mA DC or less.
Rated current 1 -1.2 mA with a load of 0.25 MΩ 1 to 1.2 mA with a load of 0.5 MΩ
Accuracy ±2%rdg±3dgt.
Substitute Leakage
Measuring range 0.10 - 12.00 mA rms.
Over-range indication > 12.00 mA.
Resolution 0.01mA.
Open-circuit voltage/Freq. 30 V ±5 V rms / 50 Hz ±5%.
Measuring current 1.2 mA AC ±0.5 mA (when measuring 12.00 mA).
Accuracy ±3%rdg±5dgt.
Insulation Test Between L-N
Open-circuit voltage 4.5 V ±0.5 V DC.
Criteria of judgement 100 kΩ ±20 kΩ or less: LCD shows “<0.10 MΩ” and the measurement is halted.
Run Leakage
Item Load Current Leakage Current
Mains voltage range 100 - 253 V / 50 Hz.
Measuring range 0.10 - 13.00 A rms. 0.10 - 20.00 mA rms.
Display range 0.00 - 13.00 A. 0.00 - 20.00 mA.
Over-range indication > 13.00 A. > 20.00 mA.
Resolution 0.01 A. 0.01 mA.
Accuracy ±10%rdg ±5dgt. ±3%rdg ±5dvgt.
Max. rating 3 kVA max. / 15 sec. cont.
RCD Test
Rated voltage 230 V - 15% to +10% / 50Hz.
Rated current 10 mA / 30 mA.
Test duration ×1: 0.0 ms - 500.0 ms. ×5: 0.0 ms - 40.0 ms.
Test current accuracy 2% - 8%.
Operating time accuracy ±2 ms ( 40 ms) ±8 ms (>40 ms).
General Specifications
Power Six size AA alkaline batteries (LR6).
Operating temperature 0ºC to +40ºC.
Storage temperature -20ºC to +60ºC.
Safety IEC/EN61010-1 CAT II 300V-instrument
IEC/EN61010-2-030
IEC/EN61010-031 CAT III 600V.
EMC EN61326-1, 2-2.
Dimensions 290(L) x 140(W) x 130(D)mm (boxed).
Weight 1.84kg (boxed).
Kewtech SMARTPAT warranty 24-months subject to registration.

Download

Kewtech SMARTPAT Datasheet

PDF Specifications of the Kewtech SMARTPAT hand-held portable appliance tester.

Download (125.18k)

No customer reviews for the moment.