Kewtech KT300 Digital Insulation Tester
Includes: ACC020 two wire test lead set, Carry Case, KT300 Manual, Batteries, Calibration certificate.
The Kewtech KT300 Digital Insulation/Continuity Tester is a handheld, single-function tester for determining insulation and continuity. Includes all of the functionality you need for measurements of insulation resistance in any electrical application in accordance with 18th Edition regulations. The KT300 is compact, accurate and easy to use with a ‘hands free’ facility.
FEATURES
Insulation test at 50V, 100V 250V, 500V & 1000V.
Continuity test with audible tone.
Test lead null facility.
Buzzer mode.
Hands free function.
Breakdown voltage.
Voltage present LED.
Auto power off.
KT300 On Site Testing Video
Kewtech KT300 Specifications
Continuity Test Range Accuracy | |||
Range | Tolerance (@20ºc). | ||
0.00 to 9.99 Ω | + (3% + 2 digits). | ||
10.0 to 99.9 Ω | + (3% + 2 digits). | ||
100 to 19.99 kΩ | + (3% + 2 digits). | ||
Open circuit Voltage | >4V, <10V. | ||
Zero offset adjust (test lead null) | 5 Ω. | ||
Typical test time (2 Ω) | >2 seconds. | ||
Hazard Warning LED | >25V. | ||
Run Leakage | |||
Test Voltage | Ranges (Auto Range) | Tolerance (@ 20°C) | |
50 V | 0.01 to 9.99 MΩ | ± (6% + 2 digits) | |
10.0 to 49.9 MΩ | ± (6% + 2 digits) | ||
100 V | 0.01 to 999 MΩ | ± (6% + 2 digits) | |
10.0 to 99.9 MΩ | ± (6% + 2 digits) | ||
250 V | 0.01 to 9.99 MΩ | ± (3% + 1 digits) | |
10.0 to 99.9 MΩ | ± (3% + 1 digits) | ||
100 to 199 MΩ | ± (6% + 1 digits) | ||
500 V | 0.01 to 9.99 MΩ | ± (3% + 1 digits) | |
10.0 to 99.9 MΩ | ± (3% + 1 digits) | ||
100 to 199 MΩ | ± (3% + 1 digits) | ||
200 to 499 MΩ | ± (6% + 1 digits) | ||
1000 V | 0.01 to 9.99 MΩ | ± (3% + 1 digits) | |
10.0 to 99.9 MΩ | ± (3% + 1 digits) | ||
100 to 399 MΩ | ± (3% + 1 digits) | ||
400 to 999 MΩ | ± (6% + 1 digits) | ||
Insulation Output Voltage | |||
Voltage | Load | Output Current | Tolerance |
50 V | 50 kΩ | 1 mA | -0% +20% |
100 V | 100 kΩ | 1 mA | -0% +20% |
250 V | 250 kΩ | 1 mA | -10% +20% |
500 V | 500 kΩ | 1 mA | -10% +20% |
1000 V | 1 MΩ | 1 mA | -10% +20% |
Short circuit current (into 2k Ω) | < 2 mA | ||
Typical Test Time (10 MΩ) | < 2 seconds | ||
General Specifications | |||
Power supply | 4 x AA LR6 Batteries. | ||
Battery life | 50 hours. | ||
Overvoltage category | CAT III 500V CAT IV 300V. |
||
Operating temperature | 0 - 40ºC. | ||
Storage temperature | -10 to 60ºC. | ||
Operating humidity | 80% @ 31ºC to 50% @ 40ºC. | ||
Safety compliance | BSEN 61010-2-030:2010. | ||
EMC compliance | BSEN 61326-2-2:2013. | ||
Performance standard | BSEN 61557-1:2007 BSEN 61557-2:2007 BSEN 61557-4:2007 |
||
Probes | GS38 compliant. | ||
Dimension | 180 x 85 x 50mm. | ||
Weight | Approximately 450g. | ||
KT300 warranty | Two-years. |
No customer reviews for the moment.
COMPONENT | DESCRIPTION | PART No. | ||
Non-fused Test leads | 2 Wire right angle connector Test Leads. Includes 1 pair 4mm leads, 1 pair base prods and 1 pair crocodile clips. | ACC020 | ||
Fused Upgrade kit | Converts non fused test leads to fused for extra safety. Includes 1 pair fused black & red prods, 1 pair fused black & red crocodile clips. Fits ACC020. | ACC040 |
16 other products in the same category: