- Hamilton01698 829711
- Leeds0113 235 1356
- Belfast02890 830302
Clare STM/L SafeTest Manufacturing/Luminaire
Includes: Clare STM/L, HT Probe, Earth Bond Lead, Guard with Plug and Instruction Manual.
The Clare STM/L performs 500V insulation tests using a DC test voltage, which can be used instead of a flash test when required, as well as completing earth bond, polarity and continuity and load and operation testing.
Manufacturers and importers of luminaire products must be able to demonstrate that their products meet relevant EU directives including the LVD (Low Voltage Directive), which is addressed by IEC/EN 60598-1. The STML is able to conduct the electrical safety tests as published in EN60598.
FEATURES
AC / Flash / Hipot Test.
DC Insulation Resistance.
Leakage Test.
Load Test.
Power / Run Test.
Storage of up to 6,000 test results.
Manual and semi-automatic test sequencing.
Link to a printer and scanner for fast and traceable testing.
Clare STM/L Specifications
Test Voltage Class I | 1.5kV AC. | |
Display Range | 0.1 – 10.00mA. | |
Resolution | 0.01mA. | |
Accuracy | +/- 5% +/- 2 digits. | |
Pass Levels | Selectable up to 10mA. | |
Flash/Hipot Test (Class II) | ||
Test Voltage Class II | 3.0kV AC. | |
Range | 0.1 – 10.00mA. | |
Resolution | 0.01mA. | |
Accuracy | +/- 5% +/- 2 digits. | |
Pass Levels | Selectable up to 10mA. | |
Earth/Ground Bond Test | ||
Test Voltage | 6VAC (open circuit). | |
Test Currents | 25A, 10A, 4A, 100mA AC into short circuit. | |
Range | 0.04 - 20Ω. | |
Resolution | 1mΩ. | |
Accuracy | +/- 5% +/- 2 digits. | |
Pass Levels | User selectable. | |
DC Insulation Test | ||
Test Voltages | 250V, 500VDC. | |
Range | 100k - 50M. | |
Accuracy | +/- 5% +/- 2 digits. | |
Earth Leakage (Load Leakage) | ||
Voltage | Mains Supply. | |
Range | 0.1 – 20mA. | |
Resolution | 0.01 mA. | |
Accuracy | +/- 10% +/- 2 digits (1.00 – 20mA). | |
Pass Levels | Selectable up to 10 mA. | |
Substitute Leakage (Short to case test) | ||
Voltage | 40VAC nominal at 230V/110V supply. | |
Range | 0.1 – 20mA. | |
Resolution | 0.01 mA. | |
Accuracy | +/- 10% +/- 2 digits (1.00 – 20 mA). | |
Pass Levels | Selectable up to 15 mA. | |
Power/Run/Load Test | ||
Measured Load | 0 – 4.2kVA. | |
Resolution | 0.01 kVA. | |
Accuracy | +/- 10% of reading, +/- 2 digits. | |
Polarity | ||
Test performed | Live & Neutral continuity & polarity. | |
General Specifications | ||
Dimensions | 0 – 4.2kVA. | |
Weight | 0.01 kVA. | |
Accuracy | +/- 10% of reading, +/- 2 digits. |
No customer reviews for the moment.
COMPONENT |
DESCRIPTION | PART No. | ||
CCD Barcode Scanner | A non contact barcode label scanner for rapid, error free entry of appliance number, test code and asset details. | 194A922 | ||
Desk Test n Tag Printer | A desktop thermal transfer printer for long-lasting labels. Supplied with 100 x 50mm labels. | 312A916 | ||
Desk Test n Tag Labels (White) | Replacement white labels (1000) for the Desk Test n Tag Printer. | 312A951 | ||
Desk Test n Tag Labels (Yellow) | Replacement yellow labels (1000) for the Desk Test n Tag Printer. | 312A956 | ||
Guard Switch | Handheld guard switch. | DCS317 | ||
Hipot Test Probe - Red | HV test probe with trademark Clare retractable tip. | 03918/2 |
9 other products in the same category:
arrow_upward