- Hamilton01698 829711
- Leeds0113 235 1356
- Belfast02890 830302
Megger EasyTest 20 kV Cable Tester
Includes: Connection cable for HV, mains supply and earth, Accessory bag, Carrying belt, Operating manual.
The Easytest represents a simplified version of the standard VLF test. It has been designed to verify operational integrity versus operational reliability, which is the objective of a standard VLF test in accordance with the respective standards.
Typically, a simplified test is performed in accordance with company specifications after repairs or after a new cable or circuit has been installed. The purpose of such a test is to verify the integrity of the cable and there accessories before switching the circuit back into operation. The Easytest allows such a test at voltages well above operating voltage in order to provide a safe indication regarding operational integrity.
With an output voltage of 20 kV and 0.1 Hz AC at 0.5 μF (and up to 2.5 μF at 0.02 Hz), the Easytest provides sufficient power to test 20 kV cables that are up to 2 km in length at 0.1 Hz with a test voltage of 1.7 Uo.
An optional logging function allows the measured data to be saved on a USB memory stick. In combination with the Winkis/chip card version, all test parameters can be set directly from the PC. After inserting the chip card, the test parameters saved on it are loaded directly to the Easytest, and once the test has taken place, the readings are stored on the chip card.
FEATURES
Easy to operate.
Configurable test sequences.
Compact, rugged and lightweight design.
AC, DC and sheath testing in one single system.
Reporting via USB or Winkis.
AC testing | 0-20 kV 0.5 μF @ 0.1 Hz 1 μF @ 0.05 Hz 2.5 μF @ 0.02 Hz 5 μF @ 0.01 Hz. |
DC testing | 0-20 kV with leakage current measurement. |
Leakage current measurement | Automatic change-over between two measuring ranges: 0-1 mA 1-50 mA. |
Breakdown detection | Visual signalisation. |
Timer | 0-60 minutes, 5 min. interval. |
Sheath testing | 0-5 kV, 0-10 kV. |
Sheath fault location | 0-5 kV, 0-10 kVDC, duty cycling 1:3. |
Safety | F-Ohm monitoring/emergency stop, HV key interloc. |
Supply | 110 V or 230 V, 750 W. |
Operating temperature | -20°C - +50°C. |
Storage temperature | -20°C - +60°C. |
Protection class | IP 54 with closed lid. |
Dimensions (W x H x D) | 480 x 290 x 495 mm. |
Weight | 17 kg. |
Megger Easytest 20 kV warranty | One-year. |
No customer reviews for the moment.
COMPONENT |
DESCRIPTION | PART No. | ||
Trolley | Trolley for Easytest. | 890009658 |