loading spinner
Metrel MI 3360 OmegaPAT XA
  • Metrel MI 3360 OmegaPAT XA
  • Metrel MI 3360 OmegaPAT XA
  • Metrel MI 3360 OmegaPAT XA

Metrel MI 3360 OmegaPAT XA

metrel authorised distributor

Includes:MI 3360 OmegaGT XA, Bag for accessories, Smartball pen with touch screen function, Crocodile clip, black, Test lead, black, Test tip, black, IEC test cable, 2 m, Mains cable, USB cable, Calibration Certificate, Short form instruction manual, CD with instruction manual (full version) and PC SW Metrel ES Manager.

MI3360
Metrel UK
Choose Your Model
The Metrel OmegaPAT XA brings 4 models of the instrument, intended for professional use in the most demanding applications. All of them support user accounts, which means that one device can be used by several electricians.

Model versions cover the following fields of testing: portable appliances, welding equipment, medical devices and professional testing of PRCD devices. All instruments have an advanced built-in user interface that enables the execution of pre-defined and user-created AUTOSEQUENCE®s. Large memory capacity (8 GB microSD card) enables the user long term saving and archiving of data.

All the instruments are specially designed for long-term testing, since their memory structure enables simple searching through the archive of devices and quick re-execution of (periodic) tests. Great emphasis was put on support for peripheral devices such as printers and barcode or QR code scanners and RFID readers (in Bluetooth and wired versions).

Medical equipment testing is another sub-field of PAT testing, but one that requires special care since the tested devices are in direct contact with medical staff and patients, which translates to a heightened probability of electric shock. There are numerous types of medical equipment that needs to be regularly inspected and tested to maintain its reliability. Metrel has developed a special version of MI 3360 OmegaPAT XA (model M), which covers the international standard IEC/EN 62353 for medical electrical equipment testing.

TEST FUNCTIONS

Visual inspections.
Fuse test.
Continuity / Protective earth resistance 200mA.
Continuity / Protective earth resistance 10A, 25A (25A, M, F, models only).
Insulation Resistance (Riso, Riso-S).
Sub-Leakage Current, Substitute Leakage Current - S.
Differential Leakage current.
PE leakage current.
Touch leakage current.
Insulation resistance, IEC/EN 62353.
Touch leakage current, IEC/EN 62353.
Equipment leakage (direct, differential, alternative) IEC/EN 62353.
Applied part leakage (direct, alternative), IEC/EN 62353.
Insulation resistance, (optional A 1422) IEC/EN 60974-4.
Welding circuit leakage, (optional A 1422) IEC/EN 60974-4.
Primary leakage, (optional A 1422) IEC/EN 60974-4.
No-load voltage, (optional A 1422) IEC/EN 60974-4.
Power (P, S, Q, PF, THDu, THDi, CosØ, I, U,).
PRCD test, (2 pole, 3 pole, K/ Di (varistor), S (3-pole)).
PRCD PE probe test, PRCD open conductor test, PE conductor (PRCD) test.
RCD test, (type A, AC, B, B+, F).
Flash test, (1500V, 3000V).
Polarity / Active polarity test.
Clamp current (with optional A 1283).

Metrel MI 3360 OmegaPAT XA Promotional Video

Metrel MI 3360 OmegaPAT XA Comparison Chart
FEATURE Standard (S) High Current (25A) Medical (M) Flash (F)
Visual Inspection
Fuse Test
Cont/EB Resistance 200mA
Cont/EB Resistance 10A & 25A -
Insulation Resistance (Riso, Riso-S)
Substitute Leakage Current
Differential Leakage Current
PE Leakage Current
Touch Leakage Current
Polarity / Active Polarity
Power (P, S, Q, PF, THDu, THDi, Cosø, I, U)
P-RCD, (2 pole, 3 pole, K/ Di (varistor), S (3-pole))
PRCD PE probe test, open conductor test, PE conductor test
RCD test, (type A, AC, B, B+, F)
Flash test (1500V, 3000V) - - -
Insulation Resistance, IEC/EN 62353 - - -
Touch Leakage Current, IEC/EN 62353 - - -
Equipment Leakage (Direct, Differential, Alternative), IEC/EN 62353
Applied Part Leakage (Direct, Alternative), IEC/EN 62353
Insulation resistance, (optional A 1422) IEC/EN 60974-4
Welding circuit leakage, (optional A 1422) IEC/EN 60974-4
Primary leakage, (optional A 1422) IEC/EN 60974-4
No-load voltage, (optional A 1422) IEC/EN 60974-4
Metrel MI 3360 OmegaPAT Specifications
Continuity / Protective Earth Resistance
Continuity
Ranges 0.00 Ω … 19.99 Ω / 20.0 Ω … 99.9 Ω / 100.0 Ω … 199.9 Ω / 200 Ω … 999 Ω.
Resolution 0.01 Ω / 0.1 Ω / 0.1 Ω / 1 Ω.
Accuracy ±(2 % of reading + 2 D) / ± 3 % of reading / ± 5 % of reading / indicative.
Operating range (acc. to EN 61557-4) 0.08 Ω … 199.9 Ω.
Test currents 0.2 A,10 A, 25 A.
Current source (at nominal mains voltage, use of standard accessories) > 0.2 A at R < 2 Ω.
> 10 A at R < 0.1 Ω at 230 V.
> 25 A into short circuit at 230 V.
Open circuit voltage < 9 V a.c.
Test Terminals
Continuity
R (200 mA) P/S – PE, Socket PE; Socket PE – IEC PE.
R (10 A, 25 A) P/S – Socket PE; Socket PE – IEC PE.
Protective Earth Resistance
R (200 mA) P/AP – PE, Socket PE.
R (10 A, 25 A) P/AP – Socket PE.
Insulation Resistance (Riso, Riso-S)
Insulation resistance, Insulation resistance –S (250 V, 500 V).
Range 0.00 MΩ … 19.99 MΩ / 20.0 MΩ … 99.9 MΩ / 100.0 MΩ … 199.9 MΩ.
Resolution 0.01 MΩ / 0.1 MΩ / 0.1 MΩ.
Accuracy ±(3 % of reading + 2 D) / ± 5 % of reading /± 10 % of reading.
Output voltage (Um)
Range 0 V … 600 V.
Resolution 1V.
Accuracy ±(3 % of reading + 2 D).
Operating range (acc. to EN 61557-2) 0.08 MΩ … 199.9 (999) MΩ.
Nominal voltages Un 250 V, 500 V (- 0 %, + 10 %).
Short circuit current max. 2.0 mA.
Test terminals Riso LN, Socket LN – PE, Socket PE, P/S.
Riso-S LN, Socket LN – P/S.
Sub-Leakage Current, Substitute Leakage Current - S (Isub, Isub-S)
Range 0.00 mA … 1.99 mA / 2.00 mA … 19.99 mA.
Resolution 0.01mA / 0.01mA.
Accuracy ±(3 % of reading + 3 D) / ±(5 % of reading).
Operating range (acc. to EN 61557-16) 0.02 mA … 19.99 mA.
Open circuit voltage 230 V a.c., 110 V a.c.
Current calculated to mains supply voltage (110 V or 230 V) is displayed.
Test Terminals Isub LN, Socket LN – PE, Socket PE, P/S.
Isub-S LN, Socket LN – P/S.
Differential leakage current (Idiff)
Differential leakage current
Range 0.000 mA … 1.999 mA / 2.00 mA … 19.99 mA.
Resolution 1 µA / 0.01 mA.
Accuracy ±(3 % of reading + 3 D) / ±(5 % of reading).
Power (active) (P)
Range 0 W … 999 W / 1.00 kW … 3.70 kW.
Resolution 1W / 10W.
Accuracy ±(5 % of reading + 5 D) / ±5 % of reading.
Operating range (acc. to EN 61557-16) 0.010 mA … 19.99 mA.
Influence of load current < 0.02 mA/A.
Test terminals Idiff Socket L,N – Socket PE, P/S.
P Socket L – Socket N.
PE leakage current (Ipe)
PE leakage current
Range 0.000 mA … 1.999 mA / 2.00 mA … 19.99 mA.
Resolution 1µA / 0.01mA.
Accuracy ±(3 % of reading + 3 D) / ±(5 % of reading).
Power (active) (P)
Range 0 W … 999 W / 1.00 kW … 3.70 kW.
Resolution 1W / 10W.
Accuracy ±(5 % of reading + 5 D) / ±5 % of reading.
Operating range (acc. to EN 61557-16) 0.010 mA … 19.99 mA.
Test terminals Ipe Socket L,N – Socket PE.
P Socket L – Socket N.
Touch leakage current (Ipe)
Range 0.000 mA … 1.999 mA / 2.00 mA … 19.99 mA.
Resolution 1 µA / 0.01mA.
Accuracy ±(3 % of reading + 3 D) / ±(5 % of reading).
Power (active) (P)
Range 0 W … 999 W / 1.00 kW … 3.70 kW.
Resolution 1W / 10W.
Accuracy ±(5 % of reading + 5 D) / ±5 % of reading.
Operating range (acc. to EN 61557-16) 0.010 mA … 19.99 mA.
Test terminals Itou: Socket L,N – P/S.
P: Socket L – Socket N.
Power
Power (active) (P)
Range 0 W … 999 W / 1.00 kW … 3.70 kW.
Resolution 1W / 10W.
Accuracy ±(5 % of reading + 5 D) / ±5 % of reading.
Power (apparent) (S)
Range 0 VA … 999 VA / 1.00 kVA … 3.70 kVA.
Resolution 1 VA / 10VA.
Accuracy ±(5 % of reading + 5 D) / ±5 % of reading.
Power (reactive) (Q)
Range ±(0 VAr … 999) VAr / ±(1.00 kVAr … 3.70) kVAr.
Resolution 1 VAr / 10 VAr.
Accuracy ±(5 % of reading + 5 D) / ±5 % of reading.
Power factor (PF)
Range 0.00i … 1.00i / 0.00c … 1.00c.
Resolution 0.01.
Accuracy ±(5 % of reading + 5 D).
Total Harmonic Distortion (voltage) (THDU)
Range 0.0 % … 99.9 %.
Resolution 0.1 %.
Accuracy ±(5 % of reading + 5 D).
Total Harmonic Distortion (current) (THDI)
Range 0.00 A … 16.00 A.
Resolution 0.01 A.
Accuracy ±(3 % of reading + 5 D).
Cosinus Φ (Cos Φ)
Range 0.00i … 1.00i / 0.00c … 1.00c.
Resolution 0.01.
Accuracy ±(5 % of reading + 5 D).
Current (I)
Range 0.00 A … 16.00 A.
Resolution 0.01 A.
Accuracy ±(3 % of reading + 5 D).
Voltage (U)
Range 0.0 V … 199.9 V / 200 V … 264 V.
Resolution 0.1V / 1V.
Accuracy ±(3 % of reading + 10 D) / ±3 % of reading.
Test terminals
P,S,Q,PF,THDU,THDI, Cos Φ, I, U Socket L – Socket N.
Leaks & Power
Power (active) (P)
Range 0 W … 999 W / 1.00 kW … 3.70 kW.
Resolution 1W / 10W.
Accuracy ±(5 % of reading + 5 D) / ±5 % of reading.
Touch leakage current: (Itou)
Range 0.000 mA … 1.999 mA / 2.00 mA … 19.99 mA.
Resolution 1 µA / 0.01 mA.
Accuracy ±(3 % of reading + 3 D) / ±(5 % of reading).
Operating range (acc. to EN 61557-16) 0.010 mA … 19.99 mA.
Differential leakage current (Idiff)
Range 0.000 mA … 1.999 mA / 2.00 mA … 19.99 mA.
Resolution 1 µA / 0.01 mA.
Accuracy ±(3 % of reading + 3 D) / ±(5 % of reading).
Operating range (acc. to EN 61557-16) 0.010 mA … 19.99 mA.
Influence of load current < 0.02 mA/A.
Power (apparent) (S)
Range 0 VA … 999 VA / 1.00 kVA … 3.70 kVA.
Resolution 1 VA / 10VA.
Accuracy ±(5 % of reading + 5 D) / ±5 % of reading.
Power (reactive) (Q)
Range ±(0 VAr … 999) VAr / ±(1.00 kVAr … 3.70) kVAr.
Resolution 1 VAr / 10 VAr.
Accuracy ±(5 % of reading + 5 D) / ±5 % of reading.
Power factor (PF)
Range 0.00i … 1.00i / 0.00c … 1.00c.
Resolution 0.01.
Accuracy ±(5 % of reading + 5 D).
Total Harmonic Distortion (voltage) (THDU)
Range 0.0 % … 99.9 %.
Resolution 0.1 %.
Accuracy ±(5 % of reading + 5 D).
Total Harmonic Distortion (current) (THDI)
Range 0.00 A … 16.00 A.
Resolution 0.01 A.
Accuracy ±(3 % of reading + 5 D).
Cosinus Φ (Cos Φ)
Range 0.00i … 1.00i / 0.00c … 1.00c.
Resolution 0.01.
Accuracy ±(5 % of reading + 5 D).
Current (I)
Range 0.00 A … 16.00 A.
Resolution 0.01 A.
Accuracy ±(3 % of reading + 5 D).
Voltage (U)
Range 0.0 V … 199.9 V / 200 V … 264 V.
Resolution 0.1V / 1V.
Accuracy ±(3 % of reading + 10 D) / ±3 % of reading.
Test terminals
P,S,Q,PF,THDU,THDI, Cos Φ, I, U Socket L – Socket N.
Idiff Socket L,N – Socket PE, P/S.
Itou Socket L,N – P/S.
PRCD test
Trip-out time (tΔN)
Range 0 ms … 300 ms (999 ms*) (½xI∆N) / 0 ms … 300 ms (I∆N) / 0 ms … 40 ms (5xI∆N).
Resolution 1ms / 1ms / 1ms.
Accuracy ±3ms / ±3ms / ±3ms.
*According to standard AS/NZS 3017.
Trip out-current (IΔ)
Range 0.2xI∆N … 2.2xI∆N.
Resolution 0.05xI∆N.
Accuracy ±0.1xI∆N.
Test current type sine-wave (AC), pulsed (A,F), smooth DC (B,B+).
Test currents (IΔN) 10 mA, 15 mA, 30 mA;.................100 mA and 300 mA with A1322, A1422.
Test current size (PRCD standard is AS/NZS 3017) ±5%.
Test current size (general) -0/+10%.
Test terminals tΔN, IΔ Socket – IEC.
RCD Test
Trip-out time (tΔN)
Range 0 ms … 300 ms (999 ms*) (½xI∆N) / 0 ms … 300 ms (I∆N) / 0 ms … 40 ms (5xI∆N).
Resolution 1ms / 1ms / 1ms.
Accuracy ±3ms / ±3ms / ±3ms.
*According to standard AS/NZS 3017.
Trip out-current (IΔ)
Range 0.2xI∆N … 2.2xI∆N.
Resolution 0.05xI∆N.
Accuracy ±0.1xI∆N.
Contact voltage (Uc)
Range 0.0 V … 19.9 V / 20.0 V … 99.9 V.
Resolution 0.1V / 0.1V.
Accuracy (-0 % / +15 %) of reading ± 10 D / 0.1 V (-0 % / +15 %) of reading.
Test current type sine-wave (AC), pulsed (A,F), smooth DC (B,B+).
Test currents (IΔN) 10 mA, 15 mA, 30 mA.
Test current size (RCD standard is AS/NZS AS/NZS) 5%.
Test current size (EN 61008/EN 61009) -0/+10%.
Test terminals tΔN, IΔ Mains Socket.
PE conductor (PRCD)
PE conductor (Type = 2 pole, 3 pole, S(3 pole)) (R)
Range 0.00 Ω … 19.99 Ω / 20.0 Ω … 99.9 Ω / 100.0 Ω … 199.9 Ω / 200 Ω … 999 Ω.
Resolution 0.01 Ω / 0.1 Ω / 0.1 Ω / 1 Ω.
Accuracy ±(2 % of reading + 2 D) / ± 3 % of reading / ± 5 % of reading / indicative.
Operating range (acc. to EN 61557-4) 0.08 Ω … 199.9 Ω.
Current source (at nominal mains voltage, use of standard accessories) > 0.2 A at R < 2 Ω.
Open circuit voltage < 9 V a.c.
Test terminals R Socket PE – IEC PE.
PE conductor (Type = K/ Di (varistor))
Test principle: A voltage is applied between PE connections of the PRCD-K. There is a ‘PASS’ if PRCD trips.
Open circuit voltage 24 V.
Output resistance 220 Ω ± 10 % (IΔN = 30 mA), 620 Ω ± 10 % ((IΔN = 10 mA).
Test terminals Result: Socket – IEC.
Open conductor (PRCD)
Test principle: Mains voltage is applied to the mains test socket. Disconnection of the L, N and PE connections is performed inside the instrument. There is a ‘PASS’ if the PRCD trips.
Test terminals L open, N open, PE open Socket – IEC.
PRCD PE probe test
Test principle: Mains voltage is applied to the mains test socket. A safe voltage sufficiently high to activate the protection circuit in the PRCD is applied to the P/S terminal.
Test terminals Result (manual): Socket, P/S.
Result (auto): Socket – IEC, P/S.
Polarity
Test voltage (normal) < 50 V.
Test voltage (active) mains voltage.
Power consumption of tested device during the active test < 25 VA.
Test terminals Result (normal, active) Socket – IEC.
Clamp current (I, Idiff, Ipe)
True RMS current using 1000:1 current clamp
Range 0.10 mA … 9.99 mA / 10.0 mA … 99.9 mA / 100 mA … 999 mA / 1.00 A … 9.99 A / 10.0 A … 24.9 A.
Resolution 0.01 mA / 0.1 mA / 1 mA / 0.01 A / 0.1 A.
Accuracy ±(5 % of reading + 10 digits) / ±(5 % of reading + 5 digits) / ±(5 % of reading + 5 digits) / ±(5 % of reading + 5 digits) / ±(5 % of reading + 5 digits).
Notes Accuracy of current transformer is not considered.
Frequency range of current clamp is not considered.
Test terminals I, Idiff, Ipe: CLAMPS terminals.
Insulation resistance Riso (welding equipment)
Riso
Range 0.00 MΩ … 19.99 MΩ / 20.0 MΩ … 99.9 MΩ / 100.0 MΩ … 199.9 MΩ.
Resolution 0.01 MΩ / 0.1 MΩ / 0.1 MΩ.
Accuracy ±(3 % of reading + 2 D) / ±5 % of reading / ±10 % of reading.
Output voltage (Um)
Range 0 V … 600 V.
Resolution 1 V.
Accuracy ±(3 % of reading + 2 D).
Operating range (acc. to EN 61557-2) 0.08 MΩ … 199.9 (999) MΩ.
Nominal voltages Un 500 V (- 0 %, + 10 %).
Short circuit current max. 2.0 mA.
Test terminals
Riso LN-W: A 1422 Socket L1 L2 L3 N (16A-5p, 32A-5p or 16A-3p) – W1 W2.
Riso W-PE A 1422: Socket PE (16A-5p, 32A-5p or 16A-3p) – W1 W2.
Riso LN-PE A 1422: Socket L1 L2 L3 N (16A-5p, 32A-5p or 16A-3p) – Socket PE (16A-5p, 32A-5p or 16A-3p).
Riso LN (Class II) - P A 1422: Socket L1 L2 L3 N (16A-5p, 32A-5p or 16A-3p) – MI 3360: P/S.
General Specifications
Mains supply
Supply voltage, frequency 110 V / 230 V AC, 50 Hz / 60 Hz.
Supply voltage tolerance 10 %.
Max. power consumption 300 VA (without load on test socket).
Max. load 10 A continuous, 16 A short duration, 1.5 kW motor.
Mains supply overvoltage category CAT II / 300V.
Altitude ≤ 2000 m.
Measuring categories
Instrument Cat II / 300 V.
Test socket Cat II / 300 V.
Plug test cable Cat II / 300 V.
Altitude ≤ 2000 m.
Protection classifications
Power supply Mains supply.
Pollution degree 2.
Degree of protection IP40.
IP20 (mains test socket).
Case Shock proof plastic / portable.
Display Colour TFT display, 4.3 inch, 480 x 272 pixels.
Touch screen Capacitive.
Communication
Memory depends on microSD card size.
RS232 interfaces 2.
USB 2.0 Standard USB Type B.
Bluetooth Class 2.
Dimensions (w×h×d) 31 cm × 13 cm × 25 cm.
Weight 6.1 kg.
Reference conditions
Reference temperature range 15 ˚C … 35 ˚C.
Reference humidity range 35 % … 65 % RH.
Operation Conditions
Working temperature range 0 ˚C … +40 ˚C.
Maximum relative humidity 85 % RH (0 ˚C … 40 ˚C), non-condensing.
Storage Conditions
Temperature range -10 ˚C … +60 ˚C.
Maximum relative humidity 90 % RH (-10 ˚C … +40 ˚C).
80 % RH (40 ˚C … 60 ˚C).
Notes Accuracies apply for 1 year in reference conditions. Temperature coefficient outside these limits is 0.2 % of measured value per ˚C plus 1 digit, otherwise noted.
Fuses 2 x T 16 A / 250 V, 32 mm - 6.3 mm / 1500 A.

Download

Metrel MI 3360 Datasheet

PDF Specifications of the Metrel MI 3360 OmegaPAT XA Portable Appliance Tester.

Download (3.49M)

No customer reviews for the moment.