Megger DCM300E Earth Leakage Clampmeter
Includes: Megger DCM300E Earth Leakage Clampmeter, 2 Batteries (2 x LR44), Carrying Case and Instruction Manual.
The Megger DCM300E Earth Leakage Clamp designed primarily to check earth leakage currents with a dedicated 30 mA range providing resolution down to 10 µA. The capabilities of the DCM300E extend to measuring currents of up to 300 A ac, making it a highly versatile instrument capable of taking current measurements in a wide variety of situations and applications.
The Megger DCM300E has 4 ranges: 30 mA, 300 mA, 30 A and 300 A with a best resolution of 0.01 mA. The analog-style bargraph of the DCM300E is very useful when monitoring changes, allowing the operator to easily interpret the rapidly changing bargraph rather than the digital display. Other key functions include the “Data Hold” feature which aids in measurements where there is a problem with accessibility or poor lighting, and the automatic power off feature that extends the battery life.
FEATURES
0,01 mA resolution for measuring earth leakage currents.
300 A range for standard current measurements.
Analogue Bargraph Display for trending.
Handguard designed for operator safety.
Pocket sized and lightweight.
Measuring Method | Dual integration mode. |
Measuring Function | Leakage current and load. |
Display | 3.5 digit LCD; max reading of 3200. |
Range | 0-30 mA, 300 mA, 30 A, 300 A (50/60 Hz). |
Ranging | 2 manual ranges. |
Accuracy Specified at Operating Temperature | 23°C ±5°C: 80% RH max. |
Range, Min Resolution and Accuracy | 30/300 mA - 0.01/0.01 ma - ±1.2% rdg ±5dgt 30/300 A - 0.01/0.1 A - 200-250 A: ±3.0% rdg ±5 dgt. 250-300 A: ±5.0% rdg ± 5 dgt. |
Jaw Opening Capability | 40 mm. |
Over Range Indication | "OL" mark on LCD screen. |
Maximum Indication | 3200. |
Low Battery Indication | 2.5 V - 2.7 V; ("+-") mark on LCD. |
Data Hold Indication | "DH" mark on LCD screen. |
Sampling Time | Approx 2 times/sec (digital display) Approx 12 times/sec (bargraph display). |
Auto Power Off | The meter will power down after approx 10 minutes of switching on. |
Limitation of Circuit Voltage | Less than 600 V AC. |
Withstanding Voltage | AC 3700 V/1 minute max. (between the core of CT and the unit housing). |
Operating Temperature | 0 to 40°C <80% RH (non-condensing). |
Storage Temperature | -10 to 60°C <70% RH (non-condensing). |
Power Supply | 2 x 1.5V button cells (LR44 or SR44). |
Power Consumption | Approx 5mW. |
Battery Life | Approx 50 hours (LR44). |
Dimensions | 64 x 176 x 23 mm (2.5 x 7 x 9 inches) (width x height x depth). |
Weight | Approx 125g (1/4 lb approx). |
Safety | EN61010-1 and EN61010-2-032 300V phase to earth 500V phase to phase CAT III or 600V CAT II double insulated. |
EMC | In accordance with IEC61326 including amendment number 1. |
No customer reviews for the moment.