loading spinner
  • Reduced price
Fluke 3000 FC Industrial System
  • Fluke 3000 FC Industrial System
  • Fluke 3000 FC Industrial System
  • Fluke 3000 FC Industrial System
  • Fluke 3000 FC Industrial System

Fluke 3000 FC Industrial System

Fluke authorised distributor and calibration house.

Includes: Fluke 3000 FC, Fluke a3001 FC Wireless iFlex AC Current Module (3), Fluke v3000 Voltage Module, TL224 Test Leads, TL175 Test Leads, AC285 Alligator Clips, AC175 Alligator Clips, iFlex i2500-10 Flexible Current Probe (3), Magnetic hanging strap.

4465599
£835.00
£709.75 Save 15%
Tax excluded
Quantity
  • done HTTPS SECURE: Our pages are encrypted and protected from cyber-attack.
  • done COMPLIANT: Payment Card Industry Data Security Standard (PCI DSS) Compliant.
  • done PROTECTED: by TLS (SSL) - all data/information is secure from interception.

Connect the three FC Wireless iFlex AC Current Module to your test points, and view the results from all three phases in 1/3 the time and cost of current test methods or connect the FC Wireless AC Voltage Module and view both voltage and current measurements simultaneously. You’ll get better answers, faster, and spend less time in full PPE.

From short distances, you can even view readings from modules through closed electrical panels. Plus the Fluke Connect® remote modules capture up to 65,000 sets of time stamped min/max/avg readings, using the optional PC adapter. Fluke Connect wireless test tools also offer increased safety by letting you view readings in a separate location from the test point.

FEATURES

Fluke 3000 FC Series Wireless Multimeter:

AC and DC voltage measurements to 1000V.
AC and DC current with 0.01 mA resolution.
Continuity, resistance, diode test, capacitance and frequency measurements.
MIN/MAX recording.
CAT III 1000 V, Cat IV 600 V; IP54.

Fluke v3000 FC Wireless AC Voltage Module:

Measurements up to 1000 V true-RMS AC.
Use as a standalone meter or as part of the system.
A logging function for recording and saving up to 65,000 readings.

Fluke a3001 FC Wireless iFlex AC Current Module:

Measure up to 2500 A AC.
Use as a standalone meter or as part of the system.
Logging function for recording and saving up to 65,000 readings.
Inrush function.

Fluke Connect Product Video

Fluke 3000 FC Industrial System Specifications

Fluke 3000 FC Series Wireless Multimeter

AC Voltage
Range ¹ / Resolution 600.0 mV / 0.1 mV
6.000 V / 0.001 V
60.00 V / 0.01 V
600.0 V / 0.1 V
1000 V / 1 V
Accuracy 234 45 Hz to 500 Hz 1.0% + 3
500 Hz to 1 kHz 2.0% + 3
1. All AC voltage ranges are specified from 1% of range to 100% of range.
2. Crest factor of ≤ 3 at full scale up to 500 V, decreasing linearly to crest factor < 1.5 at 1000 V.
3. For non-sinusoidial waveforms, add ±(2% of reading + 2% full scale) typical, for crest factor up to 3.
4. Do not exceed 107 V-Hz.
DC Voltage, Continuity, Resistance, Diode Test and Capacitance
Function
mV Range / Resolution 600.0 mV / 0.1 mV.
Accuracy 0.09% + 2.
V Range / Resolution 6.000 V / 0.001 V
60.00 V / 0.01 V
600.0 V / 0.1 V
1000 V / 1 V.
Accuracy 0.09% + 2
0.15% + 2.
))) Range / Resolution 600 Ω / 1 Ω.
Accuracy Meter beeps at < 25 Ω, beeper detects opens or shorts of 250 μs or longer.
Ω Range / Resolution 600.0 Ω / 0.1 Ω
6.000 kΩ / 0.001 kΩ
60.00 kΩ / 0.01 kΩ
60.00 kΩ / 0.1 kΩ
600.0 kΩ / 0.001 MΩ
50.00 MΩ / 0.01 MΩ.
Accuracy 0.5% + 2
0.5% + 1
1.5% + 3.
Diode test Range / Resolution 2.000 V / 0.001 V.
Accuracy 1% + 2.
µF Range / Resolution 1000 nF / 1 nF
10.00 μF / 0.01 μF
100.0 μF / 0.1 μF
9999 μF1 / 1 μF.
Accuracy 1.2% + 2
10% typical.
1. In the 9999 μF range for measurements to 1000 μF, the measurement accuracy is 1.2% + 2.
AC and DC Current
Function
mA AC
(45 Hz to 1 kHz)
Range 1 / Resolution 60.00 mA / 0.01 mA
400.0 mA 3/ 0.1 mA.
Accuracy 1.5% + 3.
mA DC 2 Range 1 / Resolution 60.00 mA / 0.01 mA
400.0 mA 3/ 0.1 mA.
Accuracy 0.5% + 3.
1. All AC current ranges are specified from 5% of range to 100% of range.
2. Input burden voltage (typical): 400 mA input 2 mV/mA.
3. 400.0 mA accuracy specified up to 600 mA overload.
Frequency
Range / Resolution 99.99 Hz / 0.01 Hz
999.9 Hz / 0.1 Hz
9.999 kHz / 0.001 kHz
99.99 kHz / 0.01 kHz.
Accuracy 1 0.1% + 1.
1 Frequency is specified up to 99.99 kHz in volts and up to 10 kHz in amps.
Input Characteristics
Function Overload
protection
Input impedance
(nominal)
Common mode rejection ratio (1 kΩ unbalance) Normal mode rejection
V DC 1100 Vrms > 10 MΩ < 100 pF > 120 dB at DC, 50 Hz or 60 Hz > 60 dB at 50 Hz or 60 Hz
V AC 1100 Vrms > 10 MΩ < 100 pF > 60 dB, DC to 60 Hz > 60 dB at 50 Hz or 60 Hz
mV AC/DC 1100 Vrms > 10 MΩ < 100 pF > 120 dB at DC, 50 Hz or 60 Hz > 60 dB at 50 Hz or 60 Hz
Open circuit test voltage Full scale voltage Typical short circuit current.
To 6 MΩ 50 MΩ Typical short circuit current.
Ω 1100 Vrms < 2.7 VDC < 0.7 VDC < 0.9 VDC < 350 mA
))) 1100 Vrms < 2.7 VDC 2.000 VDC   < 1.1 mA
mA Function
Overload protection Fused, 44/100 A, 1000 V FAST Fuse.
Overload 600 mA overload for 2 minutes maximum, 10 minutes rest minimum.
MIN/MAX Recording Accuracy
DC functions The specified accuracy of the measurement function ±12 counts for changes > 350 mS in duration.
AC functions The specified accuracy of the measurement function ±40 counts for changes > 900 mS in duration.
General Specifications
Maximum voltage between any terminal and earth ground 1000 VDC or AC rms.
Ω fuse protection from A inputs 0.44 A (44/100 A, 440 mA), 1000 V FAST Fuse, Fluke specified part only.
Display (LCD) Update rate 4/sec.
Volts, amps, ohms 6000 counts.
Frequency 10,000 counts.
Capacitance 1,000 counts.
Battery type Three AA Alkaline batteries, NEDA 15A IEC LR6.
Battery life 250 hours minimum.
RF communications 2.4 GHZ ISM Band.
RF communication range Open air, unobstructed. Up to 20 m
Obstructed, sheetrock wall. Up to 6.5 m
Obstructed, concrete wall, or steel electrical enclosure. Up to 3.5 m
Temperature Operating -10°C to 50°C
Storage -40°C to 60°C
Temperature coefficient 0.1 x (specified accuracy) / °C (< 18°C or > 28°C).
Relative humidity 0% to 90% (0°C to 35°C)
0% to 75% (35°C to 40°C)
0% to 45% (40°C to 50°C).
Altitude Operating 2,000 m.
Storage 12,000 m.
Electromagnetic compatibility
EMI, RFI, EMC, RF
EN 61326-1:2006, EN 61326-2-2:2006
ETSI EN 300 328 V1.7.1:2006, ETSI EN 300 489
V1.8.1:2008,
FCC Part 15 Subpart C Sections 15.207, 15.209, 15.249
FCCID : FCC: T68-FDMMBLE IC: 6627A-FDMMBLE.
Safety compliance ANSI/ISA 61010-1 / (82.02.01): 3rd edition
CAN/CSA-C22.2 No 61010-1-12: 3rd edition
UL 61010-1: 3rd edition
IEC/EN 61010-1:2010.
Certifications CSA, FCC, CE.
Ingress Protection (IP) rating IP54.
Pollution Degree 2.
Size (H x W x L) 4.75 x 9.3 x 20.7 cm (1.87 x 3.68 x 8.14 in)..
Weight 340 g (12 oz).
Warranty Three years.
Not compatible with Fluke CNX test tools.

Fluke a3001 FC Wireless iFlex® AC Current Module

Range 0.5 A to 2500 A AC.
Resolution 0.1 A.
Accuracy 3% ±5 digits (5 Hz to 500 Hz).
Crest factor (50 Hz/60 Hz) 3.0 at 1100 A
2.5 at 1400 A
1.42 at 2500 A
add 2% for C.F. > 2.
LCD w/ backlight 3½ digits.
Log rate/interval 1 sec minimum/adjustable by PC or front panel.
Battery type 2 AA, NEDA 15 A, IEC LR6.
Battery life 400 hours.
Memory Record up to 65,000 readings.
RF communications 2.4 GHZ ISM Band.
RF communication range. Open air, unobstructed Up to 20 m
Obstructed, sheetrock wall Up to 6.5 m
Obstructed, concrete wall or steel electrical enclosure Up to 3.5 m.
Operating temperature -10°C to +50°C.
Storage temperature -40°C to +60°C.
Temperature coefficient Add 0.1 x (specified accuracy) / °C (< 18°C or > 28°C).
Operating humidity 90% at 35°C
75% at 40°C
45% at 50°C.
Altitude Operating 2,000 m.
Storage 12,000 m.
EMC EN 61326-1:2006.
Safety compliance IEC 61010-1, 600 V CAT IV/1000 V CAT III, 3rd edition.
Safety rating CAT IV 600 V, CAT III 1000 V.
Certifications CSA, CE, FCC: T68-FBLE IC: 6627A-FBLE.
Ingress Protection (IP) rating IP42.
Pollution Degree 2.
Jaw opening 25.4 cm (10 in) coil.
Size (H x W x D) 16.5 x 6.35 x 1.4 cm (6.5 x 2.5 x 1.4 in).
Weight .22 kg (8 oz).
Warranty Three years.
Not compatible with Fluke CNX test tools.

Fluke v3000 FC Wireless AC Voltage Module

Accuracy is specified as ±([% of reading] + [number of least significant digits]). All ranges are autoranging. Accuracy is specified from 5% to 100% of the range obtained by autoranging, from 18°C to 28°C.
Range ¹ / Resolution 6.000 V / 0.001 V
60.00 V / 0.01 V
600.0 V / 0.1 V
1000 V / 1 V.
Accuracy 234 45 Hz to 500 Hz 1.0% + 3.
500 Hz to 1 kHz 2.0% + 3.
1. All AC voltage ranges are specified from 1% of range to 100% of range.
2. Crest factor of ≤ 3 at full scale up to 500 V, decreasing linearly to crest factor < 1.5 at 1000 V.
3. For non-sinusoidial waveforms, add ±(2% of reading + 2% full scale) typical, for crest factor up to 3.
4. Do not exceed 107 V-Hz.
General Specifications
LCD w/ backlight 3½ digits, 6000 counts, updates 4/sec.
Battery type 2 AA, NEDA 15 A, IEC LR6.
Battery life 400 Hours.
Memory Record up to 65000 readings.
RF communications 2.4 GHZ ISM Band.
RF communication range Open air, unobstructed Up to 20 m.
Obstructed, sheetrock wall. Up to 6.5 m.
Obstructed, concrete wall or steel electrical enclosure. Up to 3.5 m.
Operating temperature -10°C to +50°C.
Storage temperature -40°C to +60°C.
Temperature coefficient 0.1 x (specified accuracy)/ °C (< 18°C or > 28°C).
Operating humidity 90% at 35°C, 45% at 40°C, 45% at 50°C.
Altitude Operating 2,000 m.
Storage 12,000 m.
EMC EN 61326-1:2006.
Safety compliance ANSI/ISA 61010-1 / (82.02.01) 3rd edition.
CAN/CSA-C22.2 No 61010-1-12 3rd edition.
UL 61010-1 3rd edition.
IEC/EN 61010-1 2010
Safety rating CAT IV 600 V, CAT III 1000 V.
Certifications CSA, CE, FCC: T68-FBLE IC: 6627A-FBLE.
Ingress Protection (IP) rating IP42.
Pollution Degree 2.
Size (H x W x D) 16.5 x 6.35 x 1.4 cm (6.5 x 2.5 x 1.4 in).
Weight .22 kg (8 oz).
Warranty Three years.
Not compatible with Fluke CNX test tools.

Download

Fluke 3000 FC Datasheet

PDF Specifications of the Fluke 3000 FC General maintenance System.

Download (1.5M)

No customer reviews for the moment.

Write your review

Fluke 3000 FC Industrial System
COMPONENT
DESCRIPTION PART No.
PC3000 FC FC Wireless PC Adapter. 4401602
TL175 TwistGuard™ Test Leads offer adjustable length test tips for use in different measurement environments. 3521976

2 other products in the same category: