Includes: Soft case, Timing cables, 5 m (16 ft)Control cables, 5 m (16 ft), Protective earth (ground) cable, Mains cable, Bag for cables, USB memory stick, Ethernet cable, CABA Win, User’s manual.

BL-49090
Megger
Call For Price

The Megger TM1700 series circuit breaker analysers utilises some of the ground breaking technology from the top of the line version TM1800. There are four models starting from PC-remote controlled to fully stand-alone. All models can be controlled from a computer using the well proven data management and analysing software CABA Win.

In line with the Megger product line tradition, the instrument is portable and rugged. The concept is a flexible, modular system that can be easily configured for any type of circuit breaker. Distribution circuit breakers with one contact per phase and one operating mechanism can easily be tested.

The robust design offers powerful technology that assists the user to achieve efficient and reliable circuit breaker testing. All inputs and outputs on the instrument are designed to withstand the challenging environment in high-voltage substations and industrial environments. Galvanically isolated inputs and outputs makes it possible to perform all relevant measurements in one test, eliminating the need for new setup and re-connections.

FEATURES

Provides reliable and accurate test results in noisy high voltage substations.
Five standard models.
Modular design for customized configuration.
Full stand-alone functionality or data acquisition models without user interface.
Faster and safer testing with DualGround™, both sides of breaker are grounded.
On-screen assistance with connection diagrams and test template wizard.
All models can be controlled via computer.

OPTIONS

TM1710 - a ‘black box‘ version with 1 x Control section, 1 x Timing M/r section, 1 x Digital section.
TM1720 - a ‘black box‘ version with 2 x Control sections, 1 x Timing Aux, 1 x Timing M/r section, 1 x Digital section.
TM1750 - 2 x Control sections, 1 x Timing Aux, 1 x Timing M/r section, 1 x Digital section.
TM1760 - Equipped as TM1750 plus 3 x Analog channels (total 6 x Analog channels).

Megger TM1700 Series Product Video

Megger TM1700-Series Specifications
Environment
Application field For use in high-voltage substations and industrial environments.
Operating temperature -20°C to +50°C (-4°F to +122°F).
Storage temperature -40°C to +70°C (-40°F to +158°F).
CE Marking
EMC 2004/108/EC.
LVD 2006/95/EC.
External input
TRIG IN - Voltage mode
Input range 0 – 250 V AC / DC
0 – 350 V DC.
Threshold level User configurable in software in steps of 1 V.
Contact mode
Open circuit voltage 30 V DC ±15%.
Short circuit current 10 – 40 mA.
Threshold level 1 – 2 kΩ.
Communication Interfaces
USB Universal Serial Bus ver. 2.0.
Ethernet 100 base-Tx Fast Ethernet.
HMI, Human-Machine interface
CABA Local Circuit breaker analysing software.
Available languages English, French, German, Russian, Span-ish, Swedish. Translation kit available.
Display High brightness SVGA 800x600, touch screen.
Diagonal size 21 cm (8”).
Keyboard On screen.
Control section (1 or 2)
General
No. of channels 3.
Time base inaccuracy ±0.01% of reading ±1 sample interval.
Max. sample rate 40 kHz.
Measurement time 200 s at 10 kHz sample rate.
Non-bouncing switch
Max current 60 A AC / DC, pulse ≤ 100 ms.
Duration User configurable in steps of 1 ms.
Delay User configurable in steps of 1 ms.
Current measurement
Measurement range 0 to ±80 A AC / DC.
Resolution 16 bits.
Inaccuracy ±2% of reading ±0.1% of range.
External current measurement
Max input CT ±1 V.
Scaling 100 A / 1 V.
Range ±80 A V / ±0.8 V.
Voltage measurement
Measurement range 0 – 250 V AC, 0 – 350 V DC.
Resolution 12 mV.
Inaccuracy ±1% of reading ±0.1% of range.
Timing M/R section (1)
General
No. of channels 6.
Time base inaccuracy ±0.01% of reading ±1 sample interval.
Min. resolution 0.05 ms.
Max. sample rate 40 kHz.
Measurement time 200 s at 20 kHz sample rate.
Timing of main and resistive contacts
Open circuit voltage 6 V or 26 V ±10% (Toggling at every second sample).
Short cicuit current 9.7 mA or 42 mA ±10%.
Status threshold
Main Closed < 10 Ω < Open.
Main and Resistor Main < 10 Ω
PIR resistance measurement
Supported PIR types Linear PIR.
Measurement range 30 Ω – 10 kΩ.
Inaccuracy ±10% of reading ±0.1% of range.
Voltage measurement
Measurement ranges ±50 Vpeak, ±15 Vpeak, ±0.5 Vpeak.
Resolution 16 bits.
Inaccuracy ±1% of reading ±0.1% of range.
Analog section (none, 1 or 2)
General
No. of channels 3 isolated channels.
Time base inaccuracy ±0.01% of reading ±1 sample interval.
Max. sample rate 40 kHz.
Measurement time 200 s at 10 kHz sample rate.
Transducer resistance 500 Ω – 10 kΩ at 10 V output.
Output
Voltage output 10 V DC ±5%, 24 V DC ±5%.
Max. output current 30 mA.
Current measurement
Measurement range ±22 mA.
Resolution 16 bits.
Inaccuracy ±1% of reading ±0.1% of range.
Voltage measurement
Input voltage range 0 – 250 V AC, 0 – 350 V DC.
Measurement ranges ±10 V, ±400 V.
Resolution 16 bits.
Inaccuracy 250 V range±1% of reading ±0.1% of range
10 V range±0.1% of reading ±0.01% of range.
Digital Section
General
No. of channels 6.
Supported types Incremental transducers, RS422.
Time base inaccuracy ±0.01% of reading ±1 sample interval.
Max. sample rate 40 kHz.
Measurement time 200 s at 10 kHz sample rate.
Output
Voltage 5 V DC ±5% or 12 V DC ±5%.
Max. output current 700 mA.
Digital input
Range ±32000 pulses.
Resolution 1 pulse.
Inaccuracy ±1 pulse.
Timing Aux Section
General
No. of channels 6 isolated channels.
Time base inaccuracy ±0.01% of reading ±1 sample interval.
Max. sample rate 40 kHz.
Measurement time 200 s at 10 kHz sample rate.
Voltage mode
Input voltage range 0 – 250 V AC, 0 – 350 V DC.
Status threshold ±10 V.
Inaccuracy ±0.5 V.
Contact mode
Open circuit voltage 25 – 35 V DC.
Short circuit current 10 – 30 mA DC.
Status threshold Closed < 100 Ω, Open > 2 kΩ.
General
Mains input (nominal) 100 – 240 V AC, 50 / 60 Hz
125 – 340 V DC.
Power consumption 200 VA (max).
Dimensions 500 x 185 x 410 mm (19.7” x 7.3” x 16.1”).
Weight 12 kg (26.5 lbs).

Download

Megger TM1700 Datasheet

PDF Specifications of the Megger TM1700 Circuit Breaker Analyser System.

Download (1.49M)

No customer reviews for the moment.

Write your review

Megger TM1700 Circuit Breaker Analyser System
COMPONENT
DESCRIPTION PART No.
DCM1700 3 ch Kit for 3-channels DualGround™ Timing. BL-59190
DCM1700 6 ch Kit for 6-channels DualGround™ Timing. BL-59192
Keyboard Keyboard for TM1700 series. HC-01090
TP1 300 Digital Linear Transducer. XB-39140
TP1 500 Digital Linear Transduce. XB-39150
AHMA 4/8 (ABB) Circuit breaker transducer kit. XB-61030
HMB 4/8 (ABB) Circuit breaker transducer kit. XB-61040
LTC135 Load Tap Changer power supply. CG-92100

12 other products in the same category: