- Hamilton01698 829711
- Leeds0113 235 1356
- Belfast02890 830302
Developed in response to user demand for an affordable mid-range circuit breaker analyser that is fast and easy to use, the Megger EGIL 200 delivers dependable results with a minimum of user intervention. Ideally suited for testing high- and medium-voltage circuit breakers in substation and industrial applications, this versatile instrument offers a wide range of functions, including all of the standard measurements specified in the IEEE C37 and IEC 62271 standards.
The EGIL 200 is based on technology used in Megger’s market-leading EGIL and TM-series circuit breaker analysers. It combines the ease of use offered by these instruments with many of the other features that have made them so popular. These include DualGroundTM timing using the patented dynamic capacitance measurement (DCM) system; and accurate PIR contact timing and PIR resistance measurement, even in difficult environments, thanks to patented Active Interference Suppression technology.
Other key features of the EGIL 200 are one-click report generation to a pdf file or direct to an optional integrated printer, and robust construction that makes it suitable for use in even the most demanding of on-site conditions. In fact, the EGIL 200 is so robust that it can even be shipped as goods without the need for protective transport case.
Measurements - Only a single hook-up required for:
Timing of main and PIR contacts.
Coil current: close, open 1 and 2 coils.
Station voltage measurements .
Motion measurements.
Motor current measurement.
FEATURES
Versions for 2 or 4 breaks per phase.
1 analogue channel.
3 control channels (close, open and open2), 3 digital motion channels, 3 auxiliary contact timing channels, and Internal coil current measurement.
Easy-to-use and intuitive interface.
Printer option.
Fitted in rugged, IP67 rated, case.
INCLUDED ACCESSORIES
Timing M/R cable, Timing M/R extension cable, Timing AUX cable, Control cable kit, Timing M/R clamp, Analogue cable, Lead and accessory bag, Thermal printing paper (if ordered with printer option), Ground lead 2.5/5 m, Ethernet cable 5 m, USB cable 3 m, USB memory stick, Lead ties, Power cable, User's manual.
EGIL221 | |
---|---|
2 brk/ph, 1 analogue ch, no accessories | CM-22100. |
2 brk/ph, 1 analogue ch, printer, no accessories | CM-22101. |
2 brk/ph, 1 analogue ch, standard lead kit | CM-22190. |
2 brk/ph, 1 analogue ch, printer, standard lead kit | CM-22191. |
EGIL241 | |
4 brk/ph, 1 analogue ch, no accessories | CM-24100. |
4 brk/ph, 1 analogue ch, printer, no accessories | CM-24101. |
4 brk/ph, 1 analogue ch, standard lead kit | CM-24190. |
4 brk/ph, 1 analogue ch, printer, standard lead kit | CM-24191. |
External Outputs | |
---|---|
Trig output for SDRM20X | |
Output voltage | 12 V DC ±10 %. |
Short circuit protection | PTC 250 mA. |
Switching current | < 250 mA, resistive load. |
Control Section | |
General | |
Control pulse outputs | Close, open 1 and open 2 (Galvanically insulated from earth and each other). |
Time base inaccuracy | ±0.01 % of reading ±1 sample interval. |
Max. sample rate | 40kHz. |
Measurement time | 36 s at 10 kHz sample rate. |
Non-bouncing switch | |
Max. current | 60 A AC / DC, pulse ≤ 20 ms. |
Max. continuous current | 5 A. |
Duration | User configurable in steps of 1 ms. |
Delay | User configurable in steps of 1 ms. |
Current measurement | |
Measurement range | ±20 A. |
Resolution | 16 bits. |
Inaccuracy | ±2 % of reading ±0.1 % of range. |
Voltage measurement | |
Max. voltage | 250 V AC, ±300 V DC. |
Measurement range | ± 400V. |
Resolution | 16 bits. |
Inaccuracy | ±1 % of reading ±0.1 % of range. |
Timing M/R Section | |
General | |
No. of channels | 6 or 12 selectable at ordering. |
Time base inaccuracy | ±0.01 % of reading ±1 sample interva. |
Min. resolution | 0.05 ms. |
Max. sample rate | 40 kHz. |
Measurement time | 36s at 10 kHz sample rate. |
Timing of main and resistor contacts | |
Open circuit voltage | Toggling ±12 V ±10 %. |
Short circuit current | 30 mA ±10 %. |
PIR resistance measurement | |
Supported PIR types | Linear PIR. |
Measurement range | 10 Ω – 10 kΩ. |
Inaccuracy | ±10 % of reading ±0.1 % of range. |
Voltage measurement (Only TIMING M/R, DRM/VDS inputs) | |
Measurement ranges | ±50 V and ±2.5 V. |
Resolution | 16 bits. |
Inaccuracy | ±1 % of reading ±0.1 % of range. |
Analogue Section | |
General | |
No. of channels | 1 or 3 isolated channels. |
Time base inaccuracy | ±0.01 % of reading ±1 sample interval. |
Max. sample rate | 40 kHz. |
Measurement time | 36 s at 10 kHz sample rate. |
Transducer resistance | 500 Ω – 5 kΩ. |
Output | |
Max. output current | 30 mA. |
Voltage measurement | |
Max. voltage | ±10 V peak. |
Measurement ranges | ±1 V and ±10 V. |
Resolution | 16 bits. |
Inaccuracy | |
1 V range | ±0.1 % of reading ±0.1 % of range. |
10 V range | ±1 % of reading ±0.1 % of range. |
External current measurement | |
Max. input | ±1 V peak. |
Scaling | Selectable in software. |
Digital Section | |
General | |
No. of channels | 3. |
Supported types | Incremental transducers, RS422. |
Time base inaccuracy | ±0.01 % of reading ±1 sample interval. |
Max. sample rate | 40 kHz. |
Measurement time | 36s at 10 kHz sample rate. |
Output | |
Voltage | 12 V DC ±5 %. |
Max. output current | 300 mA. |
Digital Input | |
Range | ±32000 pulses. |
Resolution | 1 pulse. |
Inaccuracy | ±1 pulse. |
Timing Aux Section | |
General | |
No. of channels | 3 isolated channels. |
Time base inaccuracy | ±0.01 % of reading ±1 sample interval. |
Max. sample rate | 40 kHz. |
Measurement time | 36s at 10 kHz sample rate. |
Max. voltage | 250 V AC, ±300 V DC. |
Contact mode | |
Open circuit voltage | 30 V DC. |
Short circuit current | 30 mA DC. |
User configurable status threshold | Open < -10 V < Closed < 10 V< Open (Factory default). |
Printer (optional) | |
Type | Thermal printer. |
Paper width | 112 mm x 114 mm (4.41", 4.48"). |
Operating temperature | 0 °C to +60 °C (32 °F to +140 °F). |
Storage & transport | -20 °C to +70 °C (-4 °F to +158 °F). |
Environmental | |
Operating temperature | -20 °C to +55 °C (-4 °F to +131 °F). |
Storage & transport | -40 °C to +70 °C (-40 °F to +158 °F). |
Humidity | 5 % – 95 % RH, non-condensing. |
CE-marking | |
LVD | 2014/35/EU. |
EMC | 2014/30/EU. |
RoHS | 2011/65/EU. |
General Specifications | |
Mains input (nominal) | 100 – 240 V AC, 50 / 60 Hz 110 – 250 V DC. |
Power consumption | 200 VA (max). |
IP rating (IEC 60528) | Closed case: IP67 Open case: IP20. |
Display | 7" (17.8 cm) LCD, Capacitive touch screen. |
Communication interfaces | 3 USB A, 1 USB B RJ45 connector for connection to external PC On-screen and optional USB keyboard. |
Languages | English, French, German & Swedish. |
Dimensions | 474 x 415 x 214 mm (18.7” 16.3” 8.4). |
Weight | 12 kg (26.5 lbs). |
No customer reviews for the moment.
COMPONENT |
DESCRIPTION | PART No. | ||
Transducer Mounting Kit | For linear and rotary travel transducers. Universal. | XB-51020 | ||
Rotary Digital Transducer Kit | With 10 m (33 ft) cable and flexible coupling. Fits with transducer mounting kit XB-51020. | XB-39131 | ||
Linear Analogue Transducer TLH-225 | 225 mm (8.8”) travel. Fits with transducer mounting kit XB-51020. | XB-30017 | ||
Digital Extension Cable | neutriCON female to neutriCON male, 10 m (33 ft). | GA-00891 | ||
Current Clamp | With BNC connector. Ranges: 30/300 A DC/AC, 10/1 mV / A. Cable length 2 m (6.6 ft). | XA-11620 | ||
Soft Carrying Case | Fits EGIL200 and one lead bag. Dimensions: 66 x 46 x 46 cm (26" x 18" x 18"). | GD-31070 | ||
Soft Cable Case | With 11 compartments, shoulder strap and two handles. Made from sturdy nylon fabric. Dimensions: 74 x 27 x 42 cm. | GD-31055 |