- Hamilton01698 829711
- Leeds0113 235 1356
- Belfast02890 830302
Fluke CV300 ClirVu 75 mm (3 in) Infrared Window
Includes: 3 in (75 mm) IR Window, Hand turn door latch, Warranty statement. Fluke IR Windows are complete, assembled and ready for installation.
Increase the safety and speed of electrical thermal imaging inspections with the Fluke ClirVu® IR Windows. Reduce the risk of arc-flash and electrocution, increase the safety of your personnel and reduce the time and cost of preventive maintenance.
The ClirVu® coating - exclusive to Fluke infrared windows - seals the optic prior to assembly to protect against moisture degradation making it perfect for very hot and very cold environments. Each Fluke infrared window is delivered with an identification plate attached for unique, on-site numbering for rapid location confirmation and faster repairs.
KEY FEATURES
One hole with standard Greenlee® punch.
Panel door does not need to be removed.
Grounds instantly to metal enclosure with patent-pending AutoGround™ process.
Maintains panel arc test ratings up to 63kA when properly installed.
General Specifications | |
Size | 75 mm (3 in). |
Voltage range | Any. |
NEMA environment type | Type 4/12 (indoor/outdoor). |
AutoGround™ | Yes. |
ClirVu® optic | Yes. |
Operating temperature | -40°C to +232°C (-40° F to +450°F) and +260°C (500°F) intermittent. |
Compatible with all Fluke cameras | Yes. |
Jam nut locking system | Yes. |
Cover and fastener permanently attached | Yes. |
Single-hole install | Yes. |
Hand turn and security key door latch options | Yes. |
Visual inspection and fusion capable | Yes. |
Short/Mid/Long-wave IR and UV capable | Yes. |
Ratings and Testing | |
Arc-tested (IEEE C37.20.7) | 63 kA for 30 cycles @ 60 Hz at KEMA. |
UL 50 V component recognition | Yes. |
UL 50 /NEMA environmental rating | NEMA Type 4/12. |
UL1558 | Yes. |
CSA C22.2 No. | Yes. |
CSA type rating | Type 4. |
IP rating | IP67 at TUV. |
Lloyds register | Up to 11 kV marine switchgear, indoor or outdoor (offshore only). |
Vibration rating | IEC60068-2-6 at TUV. |
Humidity rating | IEC60068-2-3 at TUV. |
Install | |
Actual mounting hole diameter required | 89.89 mm (3.539 in). |
Greenlee® punch kit = punch/die | 739BB = 1431AV/1432AV. |
Recommended max panel thickness | 10 gage. |
Overall window height | 141.5 mm (5.57 in). |
Overall window width | 111.5 mm (4.39 in). |
Overall window thickness | 16.2 mm (0.64 in). |
Door latch | Hand Turn. |
Optics | |
Optic insert diameter | 75 mm (2.96 in). |
Viewing aperture diameter | 67.95 mm (2.675 in). |
Viewing aperture area | 3626 mm2 (5.62 in2). |
Thickness | 2 mm (0.08 in). |
Other | |
Fluke CV200 warranty | Lifetime replacement against manufacturing defects. |
No customer reviews for the moment.