- Hamilton01698 829711
- Leeds0113 235 1356
- Belfast02890 830302
Beha-Amprobe UAT-620-EUR
Includes: UAT-600-R Receiver, UAT-600-T Transmitter, CC-UAT-600 Carrying Case, TL-UAT-600 Test Leads Kit (black test lead with detachable black alligator clip, red test lead with permanently attached red alligator clip, ground stake), SC-600 Signal Clamp, 2 x FP-UAT-600 Replacement Fuses, 6 x AA Batteries, 8 x D Batteries..
Avoid disruption with the rugged and durable Beha-Amprobe UAT-620-EUR, designed to accurately pinpoint underground utilities and buried services up to 100 feet deep with accurate depth measurement to 20 feet. Accidentally hitting an utility line during a project can lead to costly repairs and create hazardous public safety situations. Digging in the wrong place can also lead to unnecessary delays and costs for your project
The locating kit comes complete and ready for use with a Transmitter, Receiver, test lead kit, batteries and additional fuses, all in a mobile, protective duffle bag. The UAT-620 kit also includes a Signal Clamp for transmitting a signal when it is not possible to make electrical contact with the cable to be traced. For applications where ground fault locating is required, use the UAT-600 Transmitter in combination with the optional A-Frame accessory.
FEATURES
Multiple tracing modes allow you to locate and trace energised and de-energised utilities in a variety of applications.
The intuitive Transmitter automatically chooses the correct locating function based on the connected accessory and includes selectable 8/33 kHz frequencies.
The Receiver’s high-contrast display allows for clear viewing in full sunlight and features an automatic backlight for shaded and dark areas.
Semi-automatic gain control quickly detects tracing signal and allows precise adjustment of the receiver sensitivity.
Measure voltage, resistance and output current.
Depth measurement up to 20 ft.
Rated CAT IV 600 V, ensuring safety when working with energised cables.
High-contrast display allows for clear viewing in full sunlight and features an automatic backlight for dark areas.
Rugged, durable construction: water and dust resistant to IP54 and drop proof to 3.28 ft (1 m).
Use the Signal Clamp to induce a signal without making electrical contact (included with the UAT-620).
Ground fault locating with the optional A-Frame accessory.
UAT-610 Kit | UAT-620 Kit | |
UAT-600-R Receiver | ||
UAT-600-T Transmitter | ||
CC-UAT-600 Carrying Case | ||
TL-UAT-600 Test Leads Kit | ||
FP-UAT-600 Replacement Fuse | ||
User Manual | ||
Quick Reference Guide | ||
6 x 1.5 V AA (IEC LR6) Batteries (Receiver, not installed) | ||
8 x D-Cell Batteries (Transmitter, not installed) | ||
SC-600 Signal Clamp |
Features | UAT-600-R Receiver | UAT-600-T Transmitter | SC-600 Signal Clamp (included with UAT-620, optional for UAT-610) |
Measurement category | CAT IV 600 V. | ||
Operating voltage/current | 0 to 600 V. | 0 to 600 V, 100 A max. | |
Operating frequency/tracing modes | Active tracing: 33 kHz and 8 kHz Passive tracing: 50/60 Hz and Radio. |
Energised circuit Induction mode: 33 kHz Direct connection modes: 8 kHz and 33 kHz Clamp mode: 8 kHz and 33 kHz De-Energised circuit Induction mode: 33 kHz Direct connection modes: 8 kHz, 33 kHz, A-Lo/A-Hi A-Frame: 8 kHz Clamp mode: 8 kHz and 33 kHz. |
33 kHz and 8 kHz. |
Locating modes | Peak and Null | – | – |
Depth measurement and accuracy | Up to 20 ft 4 in to 10 ft: pm; 3 % 10 ft to 20 ft: pm; 5 % |
– | – |
Display backlight | Automatic | Yes | – |
Audio indication | Increasing closer to the signal | Fast beeps showing the better signal is applied. | – |
Transmitting mode power output | – | Max. 3 watts. | – |
Output voltage | – | Max. 50 V rms. | – |
Output current | – | Max. 250 mA rms, constant current in 5 steps. | – |
Signal voltage output (nominal) | – | – | 23 V rms at 8 kHz 30 V rms at 33 kHz. |
Mains voltage measurement | – | 0 V to 600 V, 50 Hz to 60 Hz Resolution: 1 V Accuracy: pm; 10% |
– |
Resistance measurement (De-energised circuit) |
– | 0 ohm; to 999 k ohm; Range: 0 ohm; to 999 ohm; (resolution: 5 ohm;) Range: 1 k ohm; to 999 k ohm; (resolution: 1 k ohm;) Accuracy: pm; 10% |
– |
Output hazardous voltage warning | – | ≥ 30 V rms | – |
Mains hazardous voltage warning | – | ≥ 30 V rms | – |
Sensitivity adjustment (gain control) | Yes | – | – |
Sensitivity at 1 m (typical) | Power: 2 mA Radio: 20 μA 8 kHz: 5 μA 33 kHz: 5 μA |
– | – |
Display | 4.3 in, 320 x 240 BW outdoor LCD display with auto backlight | LCD display (LED backlight) 2.4 in x 1.3 in |
– |
Update rate | Instantaneous | Current (mA): 10 ms Voltage (V): 15 ms Resistance ( ohm;): 330 ms. |
– |
Operating temperature and humidity | -4 °F to 122 °F (-20 °C to 50 °C), ≤90% RH. | ||
Storage temperature and humidity | -40 °F to 140 °F (-40 °C to 60 °C), ≤90% RH | ||
Operating altitude | < 6561 ft (< 2000 m) | ||
Pollution degree | 2 | ||
Water and dust resistance | IP54 | ||
Drop proof | 3.28 ft (1 m) | ||
Power supply | (6) 1.5 V AA alkaline batteries | (8) 1.5 V D cell alkaline batteries. | – |
Auto power off | 15 minutes idle | – | – |
Battery life | Approx. 35 hours at 70 °F (21 °C) (Typical) | Approx. 16 hours at 70 °F (21 °C) (Typical) | – |
Overload protection | – | 600 V rms Fuse FF 500 mA, 1000 V, IR 30 kA, Φ6.3×32 mm |
– |
Safety compliance | IEC 61010-1, IEC 61010-2-033 CSA/UL 61010-1, CSA/UL 61010-2-033 |
IEC 61010-1, IEC 61010-2-033 CSA/UL 61010-1, CSA/UL 61010-2-033 IEC 61010-031, CSA/UL 61010-031 (test leads) |
IEC 61010-1, IEC 61010-2-033 CSA/UL 61010-1, CSA/UL 61010-2-033. |
Size (H x W x L) | Approx. 11.9 x 4.7 x 30.7 in (302 x 120 x 779 mm) | Approx. 14 x 9 x 4.7 in (355 x 230 x 120 mm) | Approx. 11.6 x 7.1 x 1.4 in (295 x 180 x 37 mm). |
Weight | Approx. 4.2 lb (1.9 kg) (batteries installed) | Approx. 7.0 lb (3.2 kg) (batteries installed) | Approx. 1.9 lb (0.85 kg). |
No customer reviews for the moment.
COMPONENT | DESCRIPTION | PART No. | ||
SC-600-Euro | Signal clamp for UAT-600 series. | 4994647 | ||
AF-600 | A-Frame cable ground fault locator. | 4994583 | ||
TL-UAT-600 | Test lead set for UAT-600 Series. | 4994446 | ||
CC-UAT-600EUR | Carrying case for UAT-600 Series. | 9027 | ||
FP-UAT-600 | Fuse, 2 pack for UAT-600 Series. | 4994468 |