The Chauvin F407 harmonics clamp can be clamped around a conductor with just one hand. With a measurement range up to 1500A, their ability to measure AC or DC currents and their exceptional jaw opening capacity, these clamps are ideal for use on switchboards in small or large industrial installations.

Equipped with a fast 12-bit TRMS digital acquisition system, F407 clamps offer particularly accurate measurements. Due to their large bandwidth and high crest factor, these clamps guarantee accurate measurements whatever the type of signal.

They are particularly comfortable to read because of their backlit LCD display, offering contrasts and a viewing angle which are unprecedented for this type of instrument.

Quick, Safe Implementation

Users select the required measurement with the rotary switch and then clamp the conductor or hook up their measurement leads. To obtain further details on the measurement in progress, all you have to do is press the corresponding function on the front panel: HOLD, Min/Max, etc.

Harmonics

By monitoring voltage and current harmonics, it is usually possible to determine which loads are polluting the electrical network. With the F407 clamp, the harmonics mode enables you to: determine the harmonic currents produced by non-linear loads, analyse the problems caused by these harmonics, depending on their order (heating of neutral, motors, etc.). THD measurement (THD-f and THD-r) can be  used to quantify the harmonics present on the network.

Recording to detect even intermittent faults

This is an important advantage for technicians in the field. In the event of random faults, they no longer have to wait for them to occur: the paperless recorder function enables them to record  the relevant parameters over time at a rate which they can define. The instrument automatically stores the average, minimum and maximum values in all the modes (voltage, current, power, etc.). All the parameters will be stored in the instrument’s memory. The programmable acquisition rate allows users to define the recording duration possible on the instrument. All the recordings will then be available as trend curves for analysis.

FUNCTIONS

Current measurement (AC/DC).
Measurement of inrush current / overcurrent (True-Inrush).
Voltage measurement (AC/DC).
Frequency measurement.
Measurement of harmonic distortion, total (THD) and order by order.
Continuity test with buzzer.
Resistance measurement.
Power (W, VA, var and PF) and Energy measurements.
Measurement of the Crest Factor (CF), the Displacement Power Factor (DPF), and RIPPLE.
Recording of data in memory, Wireless data transfer to a PC (by Bluetooth).

Chauvin Arnoux F407 Specifications
Clamping Diameter 48 mm.
Display Backlit LCD.
Resolution 10,000 counts.
Number of Values Displayed 3.
Type of Acquisition TRMS (AC, AC+DC]/DC).
Autorange Yes.
Automatic AC / DC detection Yes.
AC Current
AC Current Range 0.25 to 1,000 A (1,500 A peak).
DC Current Range 0.25 to 1500 A.
A AC+DC 0.25 to 1500 A
(1,500 A peak).
Best Accuracy 1% reading + 3 cts.
AC/DC Voltage
Range 0.15 to 1,000 V.
Frequency
Range Current: 5.0 to 2000 Hz
Voltage: 5.0 to 20.00 kHz.
Resistance
Range 0.1 to 99.99 kΩ.
Open Circuit Voltage ≤8 V.
Measurement Current ≤680 μA.
Audible Continuity
Continuity Threshold 40 Ω.
Diode Test No.
Single-phase and total three-phase power values
Active power 1 W to 1,000 kW.
Reactive power 1 var to 1,000 kvar.
Apparent power 1 VA to 1,00 kVA.
FP / DPF Yes/Yes.
Harmonic analysis Yes.
THDf / THDr Yes / Yes.
Frequency analysis 25th order.
Phase rotation (2-wire method) -
General
Dimensions 92 x 272 x 41 mm.
Weight 600 g.
Chauvin F407 warranty 3 years.

Download

Chauvin F200+400+600 Datasheet

PDF Specifications of the Chauvin Arnoux F200, F400 & F600 Clamp Meters.

Download (1.84M)

No customer reviews for the moment.

Write your review

Chauvin F407 Power Clamp
COMPONENT PARTS DESCRIPTION PART No.
Test leads PVC moulded lead 1.5m DM4 -CM4 Cat4 1kV RD/BK. P01295451Z
Test Leads Silicone moulded lead 1.5m DM4-CM4 Cat4 1kV. P01295453Z
Probes Moulded test probe Cat4 1 kV RD/BK. P01295454Z
Probes 2 PVC leads/test probes 1 5A 1.5m 1000V cat 4. P01295455Z
Croc Clips Crocodile clip Cat4 1kV R D/BK. P01295457Z