- Hamilton01698 829711
- Leeds0113 235 1356
- Belfast02890 830302
Martindale EZ165 Socket & Non-Trip Earth Loop Tester
Includes: Martindale EZ165 and user manual.
The Martindale EZ165 is a socket tester that additionally checks the earth loop impedance of the wiring under test and indicates the range that the measured earth loop impedance falls within. If the wiring is faulty or the mains voltage is not within limits the earth loop impedance test is not performed. The EZ165 also indicates if the mains voltage is below 195V or above 270V or if the neutral to earth voltage is greater than 30V.
The EZ165 uses two rows of LED’s to indicate wiring condition, mains voltage level and earth loop impedance. The top row of three tricolour LED’s marked LOOP TEST indicates the range within which the measured earth loop impedance falls.
The bottom row of three tricolour LED’s indicates the condition of the wiring or if the mains supply is <195V or >270V or if the neutral to earth voltage is >30V. The EZ165 must only be used on CAT II installations up to 300V to earth.
FEATURES
Detects 28 socket wiring fault conditions.
Red/Green LEDs show fault conditions.
Non-trip earth loop impedance test.
Auto self-test routine on plug-in.
Voltage low indication.
Voltage high indication.
Earth neutral voltage high indication.
Open earth indication.
EZ165 | EZ365 | EZ2500 | |
---|---|---|---|
Indicate functional socket | ✔ | ✔ | ✔ |
Detect line/neutral reversal | ✔ | ✔ | ✔ |
Detect presence of earth | ✔ | ✔ | ✔ |
Audible indication | ✔ | ||
Mains voltage check | ✔ | ✔ | ✔ |
Earth loop impedance range | ✔ | ✔ | |
Earth loop impedance value | ✔ | ||
Polarity swap touch test | ✔ | ||
30mA RCD trip check | ✔ | ||
Digital display | ✔ |
Function | EZ165 | EZ365 |
Electrical | ||
Nominal operating voltage | 230V AC rms. | |
Operating frequency | 50Hz. | |
Power consumption | <2.5W. | |
Power | from mains socket under test. | |
Standby | after approx. 10 minutes. | |
Non-trip earth loop impedance ranges | 0 - 1.7 - 5 - 10 - 100 - 200 - 500Ω. | |
Earth loop threshold accuracy | ± (10% + 0.3Ω)* | |
Voltage low indication | <195V ± 5%. | |
Voltage high indication | >270V ± 5%. | |
Earth neutral voltage high indication | >30V nominal. | |
Open earth indication | >500Ω ± 10%. | |
RCD test current at 195V | 30mA. | |
Duration of RCD test current | 300ms. | |
Polarity | reversal test (L-NE swap at incoming supply). | |
General Specifications | ||
Dimensions | 65 x 80 x 59mm. | |
Weight | 93g. | |
Environmental | ||
Temperature (Operating & Storage) | -10°C to 40°C, at max. 60% RH. | |
Altitude | up to 2000m. | |
Pollution degree | 2. | |
Safety | ||
Conforms to | BS EN 61010-1, CAT II 300V, Class II, Double insulation. | |
EMC | ||
Conforms to | BS EN 31326-1. | |
NB | * Measurement accuracy can be affected by highly inductive or capacitive loads distributed on the supply. |
No customer reviews for the moment.