- Hamilton01698 829711
- Leeds0113 235 1356
- Belfast02890 830302
Megger MOM600A Micro-ohmmeter
Includes: Cable set GA-05053, Ground cable GA-00200, Transport case GD-00010 and MOM 600A user manual.
Micro-ohmmeters are used to measure contact resistances in high-voltage breakers, disconnecting switches (isolators), knife-contact fuses, bus joints, line joints etc. The Megger MOM600A can provide an output current of up to 600 A, and it can be set to six different measuring ranges. Full-wave rectified current is used for measuring.
The instrument is equipped with a device that guards against induction. A relay short-circuits the sensing input when the instrument’s ON/OFF switch is off and also when the instrument is in the mΩ mode. To protect against external overvoltages, both the current output and the sensing input are decoupled to ground.
The MOM600A includes a set of highly flexible cables (including separate measurement cables) and a sturdy transport case.
FEATURES
Easy to operate.
Designed for rugged field use.
Highly flexible cable connections.
Environment | ||||
---|---|---|---|---|
Application Field | The instrument is intended for use in HV substations and industrial environments. | |||
Temperature | Operating: 0 to +40°C Storage/Transport: -40 to +70°C. |
|||
Humidity | 5 to 95% RH, non-condensing. | |||
Resistance Measurements | ||||
Range | 0 to 1999 μΩ. | |||
Resolution | 1 μΩ. | |||
Inaccuracy | ±1% of reading + 1 digit (at 100 to 600A test current). | |||
Output | ||||
Current | 0 to 600 A DC. | |||
Open Circuit Voltage | 9 V DC. | |||
Current Shunt Output | 10 mV/100 A ±0.5%, max 60 mV out, max 10 V to protective earth (ground). | |||
Max Load Capacity | ||||
Output Current | Minimum Output Voltage | Max Load Time | Rest Time | Input Current |
100 A DC | 8.3 V | - | - | 6 A |
300 A DC | 7.2 V | 2.5 min. | 15 min. | 16 A |
600 A DC | 5.6 V | 15s | 5 min. | 32 A |
CE-Marking | ||||
EMC | 2004/108/EC. | |||
LVD | 2006/95/EC. | |||
General Specifications |
||||
Mains Voltage | 230 V AC, 50/60 Hz. | |||
Power Consumption (Max) | 7360 VA. | |||
Protection | Miniature circuit breakers, thermal cutouts. | |||
Current Cables | 2 x 5 m (16 ft), 50 mm². | |||
Sensing Cables | 2 x 5 m (16 ft), 2.5 mm². | |||
Dimensions | Instrument: 356 x 203 x 241 mm Transport Case: 610 x 290 x 360 mm. |
|||
Weight | 24.7 kg (54.5 lbs), 42.8 kg (94.4 lbs) with accessories and transport case. | |||
MOM600A warranty | 1 year. |
No customer reviews for the moment.
COMPONENT PARTS | DESCRIPTION | PART No. | |
Cable set 10m | 2 x 10 m (33 ft), 70 mm² (current cables). 2 x 10 m (33 ft), 2.5 mm² (sensing cables) Weight: 16.8 kg (37 lbs). |
GA- 07103 | |
Cable set 15m | 2 x 15 m (49 ft), 95 mm² (current cables). 2 x 15 m (49 ft), 2.5 mm² (sensing cables) Weight: 29.4 kg (65 lbs). |
GA-05057 | |
Calibration Shunt | 600 A / 60 mV. | BB-90020 | |
Ground cable | Earth/ground cable. | GA-00200 | |
Cable set | Cable set (2 current cables and 2 sensing cables). | GA-05053 |