loading spinner
Chauvin C.A 6550 10KV Insulation Tester
  • Chauvin C.A 6550 10KV Insulation Tester
  • Chauvin C.A 6550 10KV Insulation Tester

Chauvin C.A 6550 10KV Insulation Tester

chauvin arnoux authorised distributor.

Includes: Bag with 2 safety leads 3 m long equipped with an HV plug at each end (red / blue), 1 guard test lead 3 m long equipped with an HV plug at one end and an HV plug with rear connection at the other end (black), 3 crocodiles clips (red, blue, black), 2 CAT IV 1,000 V test probes (red/black) for voltage measurements, 1 blue lead with rear connection, 1 mains power cable 2 m long, DataView software, 1 optical / USB communication lead, 1 Chauvin C.A6550 operating manual in 5 languages on CD-ROM and 5 specification labels (1 per language).

P01139705
£3099.00
£3718.8 Inc. VAT

The Chauvin Arnoux C.A 6550 megohmmeter is a high-end portable measuring instruments intended for the measurement of very high electrical insulation and resistance values, mounted in a rugged site housing with a cover; it has a graphic screen and can operate on battery or mains power.

With its site-proof casing, the Chauvin C.A 6550 insulation tester is used to check equipment insulation during manufacturing, on-site installation work, periodic inspections and recommissioning of installations.

Specially adapted for checking insulation on rotating machinery with a 12 kV power supply or higher, the Chauvin C.A6550 complies with the IEEE43 standard which recommends insulation testing at 5-10kV.

FEATURES

Wide measurement range from 10 kΩ to 30 TΩ.
Fixed or programmable test voltage from 40 V to 10/15 kV.
5 mA charging current.
Large backlit LCD screen with digital display, bargraph and R(t)+u(t), i(t) and i(u) graphs.
Automatic  calculation of DAR / PI / DD /∆R (ppm/V) ratios.
Multiple test modes: voltage ramp and step with “burning”, “early break” and “I-limit” modes.
3 filters to optimise measurement stability.
Calculation of R at a reference temperature.
Storage of 80,000 measurements and Real-time Clock.
Optically-isolated USB communication for transfer onto PC and report generation with the DataView® software.

Chauvin CA6550 & CA6555 Specifications
    CA6550 CA6555
Test Voltages   10kV 15kV
Test Voltages Ranges 500 V: 10 kΩ to 2 TΩ
1000 V: 10 kΩ to 4 TΩ
2500 V: 10 kΩ to 10 TΩ
5000 V: 10 kΩ to 15 TΩ
500 V: 10 kΩ to 25 TΩ
      15000 V: 10 kΩ to 30 TΩ.
  Fixed Test Voltages 500 / 1,000 / 2,500 / 5,000 / 10,000 V 500 / 1,000 / 2,500 / 5,000 / 10,000 / 15,000 V
  Variable Test Voltages 40 V - 10,000 V
3 Settable Voltage Values
40 V - 15,000 V
3 Settable Voltage Values.
  Adjustment Increment
for Variable Voltages
Variable: 40-10 kV step : 40 V-1 kV: 10 V
1 kV-10 kV: 100 V
Variable: 40-15 kV step: 40 V-1 kV: 10 V
1 kV-15 kV: 100 V.
  Ramp Mode 3 presettable ramps: start voltage / end voltage / duration.
  Ramp Configuration Mode 40-1,100 V / 500-10,000 V 40-1,100 V / 500-15,000 V
  Step Mode Up to 10 steps (value and duration con gurable for each step).
Voltage Measurement After Test   AC: 0 – 2,500 V / DC: 0 – 4,000 V.
Capacitance Measurement   0.001-9.999 μF / 10.00-49.99 μF.
Leakage Current Measurement   0 - 8 mA.
Discharge After Test   Yes/Automatic.
Additional Test Stop Modes I-limit Programmable: 0.2-5 mA.
Early Break di/dt.
Timer Up to 99 minutes 59 seconds.
Burning Mode Burning Constant Testing.
Ratio Calculation PI, DAR, DD.
Calulcation of R at ref. T° Yes.
Measurement Display Filter 3 Filters with 3 Possible Time Constant.
Graphs on Display R(t)+u(t); i(t); i(u);
Storage 256 recordings, 80,000 points : R, U, I and date.
Communication Optically-isolated port for USB and RS232 links.
PC Software DataView
Power Supply NiMH rechargeable batteries, 8x 1.2 V / 4,000 mAh
charging by external voltage: 90-260 V 50/60 Hz.
Battery Charging Battery charging possible while performing insulation measurements.
Electrical Safety 1,000 V CAT IV - IEC 61010-1 and IEC 61557.
EMC, Mechanical Protection, Altitude EN 61326-1 , IP54 , 3,000 m.
Dimensions LxWxH: 340 x 300 x 200 mm.
Weight 6.2 kg approx. (excluding accessories).
Chauvin CA6550 warranty One year.

Download

Chauvin CA6550-CA6555 Datasheet

PDF Specifications of the Chauvin Arnoux CA6550 & CA6555 10kV/15kV Insulation Testers.

Download (862.25k)

No customer reviews for the moment.

Write your review

Chauvin C.A 6550 10KV Insulation Tester
COMPONENT
DESCRIPTION PART No.
HV Leads Set of 3 Cables - 3m HV Croc 10/15KV RD+BU+BK. P01295466
Large Croc Lead Blue 8M HV Croco 10/15KV Cable. P01295468
Large Croc Lead Red 8M HV Croco 10/15KV Cable. P01295469
Large Croc Lead Blue 15M HV Croco 10/15KV Cable. P01295471
Large Croc Lead Red 15M HV Croco 10/15KV Cable. P01295472
Large Croc Lead Black 15M HV Croco 10/15KV Cable. P01295473
Croc Clips Set of 3 crocodile clips: red/blue/black. P01103062
HV Lead 50 cm HV lead with rear connection. P01295467
>

5 other products in the same category:

arrow_upward