- Hamilton01698 829711
- Leeds0113 235 1356
- Belfast02890 830302
Megger PAM420 Phase Angle Meter
Includes: Test lead set, mains adapter (battery charger) PAM 420 and transport case.
The Megger PAM420, provides phase angle measuring functionality identical to that of the PAM410, but adds facilities for two-channel voltage, current and frequency measurement.
It also has a high-accuracy timing function that can be triggered by voltage signals or volt-free contacts, and can measure times up to 999.999 s with a resolution of 1 ms. The PAM420 has a built-in rechargeable battery, allowing it to be used in almost any location.
The PAM420 is suited for checking polyphase metering installations, testing protective relays, make comparative test in electrical substations, and verifying the phase angle deviation on power transformers.
FEATURES
Phase Angle Meter.
2 channels: voltage, current and frequency meter.
Timer.
Compact and lightweight.
Local calibration.
Rechargeable batteries.
Easy to use.
Measurement Section | |||
Current - Inputs I1 and I2 | |||
Measurement category | CAT III 500 V CAT IV 300 V. |
||
Input range | 0 - 25 A AC. | ||
Inaccuracy | 0.5% of reading. | ||
Resolution | 0.1 A. | ||
Protection | Built-in 25 A fuse. | ||
Voltage - Inputs U1 and U2 | |||
Measurement category | CAT III 500 V CAT IV 300 V. |
||
Input range | 0 - 500 V AC true RMS. | ||
Inaccuracy | 0.15 % of reading + 0.03% of range (± 0.15 V). | ||
Resolution | 0.1 V. | ||
Phase Angle |
|||
Phase angle range | 0 - 359.9° (2–500 V and 0.15–25 A. | ||
Type of phase angle measurement | Current-current, voltage-voltage and current-voltage. | ||
Waveform | Sinusoidal. | ||
Resolution | 0.1 V. | ||
Inaccuracy | ±0.5° at >10% of voltage/current range ±1° at 2–10% of voltage/current range ±2° at 1–2% of voltage/current range. |
||
Frequency | |||
Note: Frequency component in voltage component only. | |||
Range | 15 - 75 Hz. | ||
Inaccuracy | 0.1%. | ||
Resolution | 0.01 Hz. | ||
Timer | |||
Measurement category | CAT II 250 V. | ||
Range | 0-999.999 s. | ||
Resolution | 1 ms. | ||
Inaccuracy | ±0.02% + 2 digits of displayed value. | ||
Max input voltage | 250 V AC / DC. | ||
Input debouncing filter | 1 ms. | ||
Temperature | |||
Operating | -10°C to +50°C (14°F to +122°F). | ||
Storage & transport | -20°C to +70°C (-4°F to +158°F). | ||
Humidity | 5% - 95% RH, non-condensing. | ||
CE-Marking | |||
LVD | 2006/95/EC. | ||
EMC | 2004/108/EC. | ||
General | |||
Display | Alpha numerical LC display with backlighter. | ||
Measurement category | CAT III 500 V CAT IV 300 V. |
||
Enclosure class | IP21. | ||
Power supply | Rechargeable batteries. | ||
Mains adapter | 100 – 240 V AC, 50 / 60 Hz Adapter output voltage: 9 V DC Power consumption: 10 W (max). |
||
Dimensions | Instrument: 260 x 140 x 55 mm (except handle), (10.2” x 5.5” x 2.2”) Transport case: 390 x 300 x 140 mm, (15.4” x 11.8” x 5.5”). |
||
Weight (with accessories and transport case) | 1.2 kg (2.6 lbs) 3.5 kg (7.7 lbs). |
||
Megger PAM420 warranty | 1 year. |
No customer reviews for the moment.