In Stock

The T&R 750ADM mk3 is a flexible current injection system capable of supplying currents of up to 750A ac into a variety of loads. The unit is designed for testing devices used for power system protection, but can be used wherever a high current AC source is required. The 750ADMH mk3 has a maximum no load output voltage of 5V. The unit is ideally suited to all low power primary injection tasks requiring up to 750A for short periods.

The unit has two outputs, allowing injection of currents as low as a few hundred milliamps and up to 750A. Voltages up to 16V are available on the 40A output, allowing higher impedance trips to be tested. Four true RMS metering ranges are provided, allowing the full scale of the meter and trip level to be set independently of the selected output.

FEATURES

Primary injection up to 750A.
4V output*
16V 40A output for secondary injection.
True RMS memory ammeter with singlecycle capture.
Multi-function timing system.
Large back-lit liquid crystal display.
Thermal and over-current protection.
Automatic switch-off at end of test.
Compact and portable.
Automatic mains voltage selection*.
* See specifications.

T&R 750ADM-H mk3 Specifications
Main Output
    115 V 230 V
750 A Output Open Circuit Voltage 3.5 V 5.0 V
Voltage at 500A 2.8 V 4 V
Continuous Current 125 A 125 A
5 Min On 250 A 250 A
1 Min On 440 A 500 A
Max Current 500 A 750 A
Max Current On Time 10 s 20 s
40 A Output Open Circuit Voltage 10 V 16 V
Full Load Voltage 7.5 V 10 V
Continuous Current 10 A 10 A
1 Min On 40 A 40 A
Metering
Range Resolution Trip Current Accuracy
20.00 A 0.01 A 21 A ±0.5%rdg+5d.
50.00 A 0.01 A 53 A ±0.5%rdg+5d.
200.0 A 0.1 A 210 A ±0.5%rdg+5d.
750 A 1 A 788 A ±0.5%rdg+2d.
Timing System
Range 0-999.999s/9999.99s/99999.9s auto-ranging.
Resolution 1ms/10ms/100ms.
Accuracy ±0.01%rdg+2d (all modes except current operated)
±0.01%rdg+4d (current operated mode).
General Specifications
Supply Requirements (self selecting) 115V±10% 50/60Hz 1ph, 1900 VA max
230V±10%, 50/60 Hz 1ph, 3900 VA max.
Storage Temperature -20°C to 60°C.
Operating Temperature 0°C to 45°C.
Dimensions 560 x 456 x 265 mm.
Weight 27.4 kg.
T&R 750ADM-H mk3 warranty One-year.

Download

T&R 750ADM-H mk2 Datasheet

PDF Specifications of the T&R 750ADM-H mk2 Current Injection System.

Download (2.1M)

No customer reviews for the moment.

Write your review

T&R 750ADM-H mk3 PCITS
COMPONENT
DESCRIPTION PART No.
3m Leads 3m output leads. A200-0001
1.5m Leads 1.5m output leads. A200-0002
3m Leads 3m output leads with grey case. A200-1001
1.5m Leads 1.5m output leads with grey case. A200-1002
Printer Kit Suitable for DVS3, PCU1-LT/SP, DSM/DMO and ADM range of test sets. 210