- Hamilton01698 829711
- Leeds0113 235 1356
- Belfast02890 830302
T&R 750ADM-H mk3 PCITS
Includes: T&R 750ADM-H mk2 Operating manual, mains lead, spare fuse set and carrying strap.
The T&R 750ADM mk3 is a flexible current injection system capable of supplying currents of up to 750A ac into a variety of loads. The unit is designed for testing devices used for power system protection, but can be used wherever a high current AC source is required. The 750ADMH mk3 has a maximum no load output voltage of 5V. The unit is ideally suited to all low power primary injection tasks requiring up to 750A for short periods.
The unit has two outputs, allowing injection of currents as low as a few hundred milliamps and up to 750A. Voltages up to 16V are available on the 40A output, allowing higher impedance trips to be tested. Four true RMS metering ranges are provided, allowing the full scale of the meter and trip level to be set independently of the selected output.
FEATURES
Primary injection up to 750A.
4V output*
16V 40A output for secondary injection.
True RMS memory ammeter with singlecycle capture.
Multi-function timing system.
Large back-lit liquid crystal display.
Thermal and over-current protection.
Automatic switch-off at end of test.
Compact and portable.
Automatic mains voltage selection*.
* See specifications.
Main Output | ||||
---|---|---|---|---|
115 V | 230 V | |||
750 A Output | Open Circuit Voltage | 3.5 V | 5.0 V | |
Voltage at 500A | 2.8 V | 4 V | ||
Continuous Current | 125 A | 125 A | ||
5 Min On | 250 A | 250 A | ||
1 Min On | 440 A | 500 A | ||
Max Current | 500 A | 750 A | ||
Max Current On Time | 10 s | 20 s | ||
40 A Output | Open Circuit Voltage | 10 V | 16 V | |
Full Load Voltage | 7.5 V | 10 V | ||
Continuous Current | 10 A | 10 A | ||
1 Min On | 40 A | 40 A | ||
Metering | ||||
Range | Resolution | Trip Current | Accuracy | |
20.00 A | 0.01 A | 21 A | ±0.5%rdg+5d. | |
50.00 A | 0.01 A | 53 A | ±0.5%rdg+5d. | |
200.0 A | 0.1 A | 210 A | ±0.5%rdg+5d. | |
750 A | 1 A | 788 A | ±0.5%rdg+2d. | |
Timing System | ||||
Range | 0-999.999s/9999.99s/99999.9s auto-ranging. | |||
Resolution | 1ms/10ms/100ms. | |||
Accuracy | ±0.01%rdg+2d (all modes except current operated) ±0.01%rdg+4d (current operated mode). |
|||
General Specifications | ||||
Supply Requirements (self selecting) | 115V±10% 50/60Hz 1ph, 1900 VA max 230V±10%, 50/60 Hz 1ph, 3900 VA max. |
|||
Storage Temperature | -20°C to 60°C. | |||
Operating Temperature | 0°C to 45°C. | |||
Dimensions | 560 x 456 x 265 mm. | |||
Weight | 27.4 kg. | |||
T&R 750ADM-H mk3 warranty | One-year. |
No customer reviews for the moment.
COMPONENT |
DESCRIPTION | PART No. | ||
3m Leads | 3m output leads. | A200-0001 | ||
1.5m Leads | 1.5m output leads. | A200-0002 | ||
3m Leads | 3m output leads with grey case. | A200-1001 | ||
1.5m Leads | 1.5m output leads with grey case. | A200-1002 | ||
Printer Kit | Suitable for DVS3, PCU1-LT/SP, DSM/DMO and ADM range of test sets. | 210 |