- Hamilton01698 829711
- Leeds0113 235 1356
- Belfast02890 830302
Fluke 1732 Three-Phase Electrical Energy Logger
Includes: Fluke 1732 Energy Logger, EU and US version (includes current probes), Power supply, Voltage test leads, Alligator clips (4x), 12 in 1,500A flexible current probe (3x), Soft case, Energy Analyze Plus software, Line cords, Colour coding set, Documentation on USB flash drive.
Designed to measure the most critical three-phase power parameters, the Fluke 1732 can simultaneously log rms voltage, rms current, voltage, voltage and current THD, active power, reactive power, power factor, active energy, reactive energy, and more. With enough memory for more than a year of data logging, the 1732 can discover which loads can be optimised to enable you to reduce your energy bill.
By discovering where and when energy is being used allows energy usage to be compared with activity in the facility. The Fluke 1732 consist of measurement hardware and application software so that data can be collect and reports created with the minimum of effort. The 1732 instrument incredibly easy to use, it even makes automatic checks to ensure the user has connected up correctly. Downloading data is quick and simple – data be written directly to a USB stick without having to use a computer for downloading. The application software creates reports in minutes and allows users to compare data from location to location with ease.
FEATURES
Key measurements: Automatically capture and log voltage, current, power, power factor, energy and associated values
Fluke Connect® compatible: With upgrade package*.
Convenient instrument powering: Power instrument directly from the measured circuit
Highest safety rating in the industry: 600 V CAT IV/1000 V CAT III rated for use at the service entrance and downstream
Measure all three phases: With included 3 flexible current probes
Comprehensive logging: More than 20 separate logging sessions can be stored on the instruments
Optimised user interface: Quick, guided, graphical setup ensures you’re capturing the right data every time.
Bright, colour touch screen: Perform convenient in-the-field analysis and data checks with full graphical display
Complete “in-the-field" setup through the front panel or Fluke Connect.
Energy Analyze Plus application software: Download and analyse every detail of energy consumption with our automated reporting.
*Upgrade packages are available to upgrade existing 1732 Energy Loggers with the same features of the 1734 Energy logger.
Question: Is the Fluke 1732 and 1734 a power quality analyser?
Answer: No, the Fluke 1732 and 1732 are designed to allow facilities professional discover their energy savings potential. The only power quality measurement made by the Fluke 1732 and 1734 is total harmonics distortion, if this number is high then it’s time to consider a product like the Fluke 430-II Series or the Fluke 1736 and 1738.
Three-phase Energy Loggers | Three-phase Power Loggers | |||
---|---|---|---|---|
Features | 1732 Energy Logger | 1734 Energy Logger | 1736 Power Logger | 1738 Advanced Power Logger |
Load studies | • | • | • | • |
Energy assessments | • | • | • | • |
Neutral Current Measurement (four current channels) | • | • | ||
Harmonics measurements | • | • | ||
Voltage event capture | • | • | ||
Advanced analysis: Waveform and Inrush event capture PQ Health (EN51060) |
Upgrade package* | • | ||
IEEE519 total harmonic distortion measurements | Optional | Optional | ||
Fully integrated logging with Fluke Connect® | Upgrade package* | • | Upgrade package* | • |
WiFi | Optional | • | • | • |
Wi-Fi / Bluetooth | Optional | • | Optional | • |
Magnetic probe set | Optional | • | Optional | • |
Magnetic hanger | Optional | • | Optional | • |
Connection via WiFi router | Requires FREE software license available upon product registration. | Requires FREE software license available upon product registration. | ||
*Upgrade packages are available to upgrade existing 1732 Energy Loggers with the same features of the 1734 Energy logger, and to upgrade existing 1736 Power Loggers with the same features and capabilities of the 1738 Advanced Power Logger. Please note that 1732 and 1734 Energy Loggers cannot be upgraded with the functionality of 1736 and 1738 Power Loggers. |
Electrical Specifications | |
Power Supply | |
Voltage range | 100 V to 500 V using safety plug input when powering from the measurement circuit. |
100 V to 240 V using standard power cord (IEC 60320 C7). | |
Power consumption | Maximum 50 VA (max. 15 VA when powered using IEC 60320 input). |
Efficiency | ≥ 68.2% (in accordance with energy efficiency regulations). |
Maximum no-load consumption | < 0.3 W only when powered using IEC 60320 input. |
Mains power frequency | 50/60 Hz ±15%. |
Battery | Li-ion 3.7 V, 9.25 Wh, customer-replaceable. |
On-battery runtime | Four hours in standard operating mode, up to 5.5 hours in power saving mode. |
Charging time | < 6 hours. |
Data Acquisition | |
Resolution | 16-bit synchronous sampling. |
Sampling frequency | 10.24 kHz at 50/60 Hz, synchronized to mains frequency. |
Input signal frequency | 50/60 Hz (42.5 to 69 Hz). |
Circuit types | 1-φ, 1-φ IT, Split phase, 3-φ delta, 3-φ wye, 3-φ wye IT, 3-φ wye balanced, 3-φ Aron/Blondel (2-element delta), 3-φ delta open leg, Currents only (load studies). |
Data storage | Internal flash memory (not user replaceable). |
Memory size | Typical 10 logging sessions of 8 weeks with 1-minute intervals and 500 events¹. |
¹The number of possible logging sessions and logging period depends on user requirements. | |
Basic Interval | |
Measured parameters | Voltage, current, aux, frequency, THD V, THD A, power, power factor, fundamental power, DPF, energy. |
Averaging interval | User selectable: 1 sec, 5 sec, 10 sec, 30 sec, 1 min, 5 min, 10 min, 15 min, 30 min. |
Averaging time min/max values | Voltage, Current: Full cycle RMS updated every half cycle Aux, Power: 200ms. |
Demand Interval (Energy Meter Mode) | |
Measured parameters | Energy (Wh, varh, VAh), PF, maximum demand, cost of energy. |
Interval | User selectable: 5 min, 10 min, 15 min, 20 min, 30 min, off. |
Standards Compliance | |
Power | IEEE 1459. |
Interfaces | |
USB-A | File transfer via USB flash drive, firmware updates Max. current: 120 mA. |
WiFi | File transfer and remote control via direct connection or WiFi infrastructure. |
Bluetooth | Read auxiliary measurement data from Fluke Connect® 3000 series modules (requires 1734, or 1732 upgrade option). |
USB-mini | Data download device to PC. |
Voltage Inputs | |
Number of inputs | 4 (3 phases and neutral). |
Maximum input voltage | 1000 Vrms, CF 1.7. |
Input impedance | 10 MΩ. |
Bandwidth (-3 dB) | 42.5 Hz - 3.5 kHz. |
Scaling | 1:1 and variable. |
Measurement category | 1000 V CAT III/600 V CAT IV. |
Current Inputs | |
Number of inputs | 3, mode selected automatically for attached sensor. |
Input voltage | Clamp input: 500 mVrms/50 mVrms; CF 2.8. |
Rogowski coil input | 150 mVrms/15 mVrms at 50 Hz, 180 mVrms/18 mVrms at 60 Hz; CF 4; all at nominal probe range. |
Range | 1 A to 150 A/10 A to 1500 A with thin flexible current probe i17XX-flex1500 12". |
3 A to 300 A/30 A to 3000 A with thin flexible current probe i17XX-flex3000 24". | |
6 A to 600 A/60 A to 6000 A with thin flexible current probe i17XX-flex6000 36". | |
40 mA to 4 A/0.4 A to 40 A with 40 A clamp i40s-EL. | |
Bandwidth (-3 dB) | 42.5 Hz - 3.5 kHz. |
Scaling | 1:1 and variable. |
Auxiliary Inputs | |
Number of inputs | 2. |
Input range | 0 to ±10 V dc, 1reading/s. |
Scale factor | Format: mx + b (gain and offset) user configurable. |
Displayed units | User configurable (7 characters, for example, °C, psi, or m/s). |
Wireless Connection | |
Number of inputs | 2. |
Supported modules | Fluke Connect® 3000 series. |
Acquisition | 1 reading/s. |
Environmental Specifications | |
Operating temperature | -10 °C to +50 °C (14 °F to 122 °F). |
Storage temperature | -20 °C to +60 °C (-4 °F to 140 °F), with battery: -20 °C to +50 °C (-4 °F to 122 °F). |
Operating humidity | 10 °C to 30 °C (50 °F to 86 °F) max. 95% RH. |
30 °C to 40 °C (86 °F to 104 °F) max. 75% RH. | |
40 °C to 50 °C (104 °F to 122 °F) max. 45% RH. | |
Operating altitude | 2000 m (up to 4000 m derate to 1000 V CAT II/600 V CAT III/300 V CAT IV). |
Storage altitude | 12,000m. |
Enclosure | IP50 in accordance with EN60529. |
Vibration | MIL-T-28800E, Type 3, Class III, Style B. |
Safety | IEC 61010-1. |
IEC Mains Input: Overvoltage Category II, Pollution Degree 2. | |
Voltage Terminals: Overvoltage Category IV, Pollution Degree 2. | |
IEC 61010-2-031: CAT IV 600 V / CAT III 1000 V. | |
Electromagnetic compatibility | EN 61326-1: Industrial CISPR 11: Group 1, Class A. |
Korea (KCC): Class A Equipment (industrial broadcasting and communication equipment). | |
USA (FCC): 47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103. | |
Temperature coefficient | 0.1 x accuracy specification/°C. |
General Specifications | |
Colour LCD display | 4.3-inch active matrix TFT, 480 pixels x 272 pixels, resistive touch panel. |
Warranty | Instrument and power supply: Two-years (battery not included). |
Accessories: one-year. | |
Calibration cycle: two-years. | |
Dimensions | Instrument: 19.8 x 16.7 x 5.5 cm (7.8 x 6.6 x 2.2 in). |
Power supply: 13.0 x 13.0 x 4.5 cm (5.1 x 5.1 x 1.8 in). | |
Instrument with power supply attached: 19.8 x 16.7 x 9 cm (7.8 x 6.6 x 3.5 in). | |
Weight | Instrument: 1.1 kg (2.5 lb). |
Power supply: 400 g (0.9 lb). | |
Tamper protection | Kensington lock slot. |
i17xx-flex 1500 12" Flexible Current Probe Specifications | |
Measuring range | 1 to 150 A ac/10 to 1500 A ac. |
Nondestructive current | 100 kA (50/60 Hz). |
Intrinsic error at reference condition* | ±0.7% of reading. |
Accuracy 173x + iFlex | ±(1% of reading + 0.02% of range). |
Temperature coefficient over operating temperature range | 0.05% of reading/°C 0.09% of reading/°F. |
Working voltage | 1000 V CAT III, 600 V CAT IV. |
Probe cable length | 305 mm (12 in). |
Probe cable diameter | 7.5 mm (0.3 in). |
Minimum bending radius | 38 mm (1.5 in). |
Output cable length | 2 m (6.6 ft). |
Weight | 115 g. |
Probe cable material | TPR. |
Coupling material | POM + ABS/PC. |
Output cable | TPR/PVC. |
Operating temperature | -20 °C to +70 °C (-4 °F to 158 °F) temperature of conductor under test shall not exceed 80 °C (176 °F). |
Temperature, non-operating | -40 °C to +80 °C (-40 °F to 176 °F). |
Relative humidity, operating | 15% to 85% non-condensing. |
IP rating | IEC 60529:IP50. |
Warranty | Two-year. |
Reference condition: Environmental: 23 °C ±5 °C, no external electrical/magnetic field, RH 65%. Primary conductor in center position. |
No customer reviews for the moment.
COMPONENT PARTS | DESCRIPTION | PART No. | |
MP1-MAGNET PROBE 1 | Magnet Probes for 4mm banana, Set of 4. | 4589220 | |
C17XX | C17XX Soft Case. | 4637381 | |
i17XX-flex1500 | 1500A 12 inch iFlex® Current Clamp. | 4637328 | |
i17XX-flex1500/3pk | 1500A 12 inch, 3 pack iFlex® Current Clamps. | 4637337 | |
i17XX-flex1500/4pk | 1500A 12 inch, 4 pack iFlex® Current Clamps. | 4637411 | |
i17XX-flex3000 | 3000A 24 inch iFlex® Current Clamp. | 4637343 | |
i17XX-flex3000/3pk | 3000A 24 inch, 3 pack iFlex® Current Clamps. | 4637355 | |
i17XX-flex3000/4pk | 3000A 24 inch, 4 pack iFlex® Current Clamps. | 4637427 | |
i17XX-flex6000 | 6000A 36 inch iFlex® Current Clamp. | 4637362 | |
i17XX-flex6000/3pk | 6000A 36 inch, 3 pack iFlex® Current Clamps. | 4637370 | |
i17XX-flex6000/4pk | 6000A 36 inch, 4 pack iFlex® Current Clamps. | 4637430 | |
FLUKE-17xx-TL 0.1M | Test Lead Set, 1000V CAT III, Non-stackable connectors; 0.1M; Red/Blk. | 4715389 | |
FLUKE-17XX-TL 1.5M | Test Lead Set, 1000V CAT III, Non-stackable connectors; 1.5M; Red/Blk. | 4715392 | |
3PHVL-1730 | Cable Assembly, Voltage Test Lead 3-Phase+N. | 4344712 |