loading spinner
Fluke 1760TR Power Quality Recorder Topas
  • Fluke 1760TR Power Quality Recorder Topas
  • Fluke 1760TR Power Quality Recorder Topas
  • Fluke 1760TR Power Quality Recorder Topas

Fluke 1760TR Power Quality Recorder Topas

fluke Approved distributor

lead time   Lead Time Approx. 7-14 Days.


Includes: Fluke 1760TR, 4 x TPS Flex 24 flexible current probe, 4 x TPS VoltProbe 6000V, 2 GB internal flash memory, ST1760 standard Ethernet cable, RS232 interface cable and RS232-USB adapter, CS1760 crossover Ethernet cable, 1 mains cable, PC software on CD-ROM, WC17xx colour localisation set, CS 1750/1760 carrying bag, hardware and software manual..

2637634
£23329.00
£27994.8 Inc. VAT

The Fluke 1760 TR includes all of the items in the Fluke 1760 unit, plus Fast transient analysis up to 10 MHz.

The Fluke 1760TR Three-Phase Power Quality Recorder is fully compliant to IEC 61000-4-30 Class-A, for advanced power quality analysis and consistent compliance testing. Designed for analysis of utility and industrial power distribution systems, in medium and low-voltage networks. With the GPS time synchronization accessory, data recorded with multiple instruments can be correlated with Class-A precision.

The Fluke 1760TR Topas provides exceptional flexibility with the ability to customize thresholds, algorithms, and measurement selections. The 1760TR power recorder captures the most comprehensive details on user-selected parameters; the supplied PQAnalyze application software enables users uses the in depth measurement and produce sophisticated analysis and reports. Data can be viewed in trend diagrams for root cause analysis or in statistical summaries in a variety of formats. You can also generate professional reports with the Report Writer function.

FEATURES:

Fully Class-A compliant: Conduct tests according to the stringent international IEC 61000-4-30 Class-A standard.
GPS time synchronization: Correlate data with events or datasets from other instruments with precision.
Flexible and fully configurable thresholds and scale factors.
Uninterrupted power supply (40 minutes): Never miss important events.
2 GB data memory: Enables detailed, simultaneous recording of numerous power parameters for long periods of time.
Comprehensive software: Provides trend diagrams for root cause analysis, statistical summaries, report writing and real-time data monitoring.
Plug and play: Allows quick setup with automatic sensor detection; sensors are instrument powered, eliminating the need for batteries.
Rugged field design: Insulated housing and a solid state design with no rotating components.
Power quality statistics according to EN50160.
Voltage event list (dips, swells and interruptions).
Continuous recording of: Voltage, Current, Power P, Q, S, Power factor, kWh, Flicker, Unbalance, Frequency, Voltage and current harmonics to the 50th / Interharmonics, THD, Mains signaling.

The Fluke 1760 Three-Phase Power Quality Recorder is fully compliant to IEC 61000-4-30 Class-A, for advanced power quality analysis and consistent compliance testing. Designed for analysis of utility and industrial power distribution systems, in medium and low-voltage networks. With the GPS time synchronization accessory, data recorded with multiple instruments can be correlated with Class-A precision.

The Fluke 1760 Topas provides exceptional flexibility with the ability to customize thresholds, algorithms, and measurement selections. The 1760 power recorder captures the most comprehensive details on user-selected parameters; the supplied PQAnalyze application software enables users uses the in depth measurement and produce sophisticated analysis and reports. Data can be viewed in trend diagrams for root cause analysis or in statistical summaries in a variety of formats. You can also generate professional reports with the Report Writer function.

FEATURES:

Fully Class-A compliant: Conduct tests according to the stringent international IEC 61000-4-30 Class-A standard.
GPS time synchronization: Correlate data with events or datasets from other instruments with precision.
Flexible and fully configurable thresholds and scale factors.
Uninterrupted power supply (40 minutes): Never miss important events.
2 GB data memory: Enables detailed, simultaneous recording of numerous power parameters for long periods of time.
Comprehensive software: Provides trend diagrams for root cause analysis, statistical summaries, report writing and real-time data monitoring.
Plug and play: Allows quick setup with automatic sensor detection; sensors are instrument powered, eliminating the need for batteries.
Rugged field design: Insulated housing and a solid state design with no rotating components.
Power quality statistics according to EN50160.
Voltage event list (dips, swells and interruptions).
Continuous recording of: Voltage, Current, Power P, Q, S, Power factor, kWh, Flicker, Unbalance, Frequency, Voltage and current harmonics to the 50th / Interharmonics, THD, Mains signaling.

Fluke 1760TR Specifications
Overview of Measurement Functions
Statistical evaluation Power quality statistics according to EN50160 and DISDIP tables like ITIC, CEBEMA, ANSI.
Event list Dips, swells and interruptions are detected and stored in the event list. Also any trigger which fires generates an event added to this list.
The Event list shows the exact time when the event occurred as well as the duration and magnitude. Sorting by several attributes of these events is possible to select one for further root cause analysis.
RMS values, transients and fast transients can be stored if a trigger fires.
Continuous recording Fluke 1760 records rms values together with corresponding minimum and maximum values for:
• Voltage
• Current
• Power P, Q, S
• Power Factor
• kWh
• Flicker
• Unbalance
• Frequency
• Harmonics/Interharmonics continuously with the following time aggregations: Day, 10 min, Free Interval, e.g.: 15 min, 2 h
Triggered recordings rms Aggregation time is adjustable between 10 ms (1/2 cycle), 20 ms (1 cycle), 200 ms (10/12 cycles) or 3 sec (150/180 cycles).
Calculating rms values, Harmonics and Interharmonics is performed synchronous to the power frequency.
Basic aggregation for harmonics and interharmonics is 200 ms.
Sample rate is 10.24 kHz for all 8 channels.
Mains signalling Phases and N-conductor, Voltage and current.
Online mode Variable refresh rate. This feature allows verification of instrument set up and delivers a quick overview of oscilloscope, transients and events.
General Data
Intrinsic uncertainty refers to reference conditions and is guaranteed for two years.
Quality system developed, manufactured as per ISO 9001: 2000.
Environment conditions Operating temp. range 0°C to +50°C; 32°F to +122°F.
Working temp. range -20°C to +50°C; -4°F to +122°F.
Storage temp. range 20°C to +60°C; -4°F to 140°F.
Reference temperature 23°C ±2 K; 74°F ±2 K.
Climatic class B2 (IEC 654-1), -20°C to +50°C; -4°F to +122°F.
Max. operating altitude 2000 m: max. 600 V CAT IV1
power supply: 300 V CAT III 5000 m: max 600 V CAT III1
power supply: 300 V CAT II.
1. Depending on sensor.
Reference conditions Environment temperature 23°C ±2 K ; 74°F ±2 K.
Power supply 230 V ±10%.
Power frequency 50 Hz / 60 Hz.
Signal declared input voltage Udin.
Averaging 10 minute intervals.
Housing Insulated, robust plastics housing.
EMC Emission Class-A as per IEC/EN 61326-1.
Immunity IEC/EN 61326-1.
Power supply Range AC: 83 V to 264 V, 45 to 65 Hz.
DC: 100 V to 375 V.
Safety IEC/EN 61010-1 2nd edition.
300 V CAT III.
Power consumption NIMH, 7.2 V, 2.7 Ah.
Battery pack In case of a power supply failure an internal battery maintains the supply for up to 40 minutes. Afterwards, or in case of discharged accumulators the Fluke 1760 is turned off and continues the measurements with the latest settings as soon as the supply voltage returns. The battery can be replaced by the user.
Display Fluke 1760 features LED indicators for the status of the 8 channels, phase sequence, power supply (mains or accumulator), memory usage, time synchronization, and data transfer.
Power LED Permanent light: normal power supply from mains.
OFF: supply via internal accumulator in case of a power failure.
Channel LEDs 3-colour LEDs per channel for Overload condition
Under load condition.
Data memory 2 GB Flash memory.
Memory model Linear.
Interfaces Ethernet (100 MB/s), compatible to Windows® XP, 7 and 8, RS 232, external modem via RS 232.
Baud rate for RS 232 9600 Baud to 115 kBaud.
Dimensions (H x W x D) 325 x 300 x 65 mm; 2.8 x 11.8 x 2.6 in.
Weight appr. 4.9 kg; 10.8 lbs (without accessories).
Fluke 1760 Warranty 2 years.
Calibration interval 1 year recommended for Class-A, otherwise 2 years.
Signal Conditioning
Range for 50 Hz systems 50 Hz ±15% (42.5 Hz to 57.5 Hz).
Range for 60 Hz systems 60 Hz ±15% (51 Hz to 69 Hz).
Resolution 16 ppm.
Sampling frequency for 50 Hz power frequency 10.24 kHz, The sampling rate is synchronized to mains frequency.
Uncertainty for frequency measurements < 20 ppm.
Uncertainty of internal clock < 1 s / day.
Measurement intervals Aggregation of the interval values as per IEC 61000-4-30 Class-A.
Min-, Max-values Half cycle, e.g.: 10 ms rms values at 50Hz.
Transients Sample rate 100 kHz to 10 MHz per channel.
Harmonics as per IEC 61000-4-7:2002: 200 ms.
Flicker as per EN 61000-4-15:2003: 10 min (Pst), 2 h (Plt).
Measurement Inputs
Number of inputs 8 galvanically isolated inputs for voltage and current measurements.
Sensor safety up to 600 V CAT IV depending on sensor.
Basic safety 300 V CAT III.
Nominal voltage (rms) 100 mV.
Range (peak value) 280 mV.
Overload capacity (rms) 1000 V, continuously.
Voltage rise rate max. 15 kV / µs.
Input resistance 1 MΩ.
Input capacitance 5 pF.
Input filter Each channel is equipped with a passive low-pass filter, an anti-aliasing filter and a 16-bit A/D converter. All channels are sampled synchronously with a common quartz-controlled clock pulse.
The filters protect against voltage transients and limit the signal rise rate, reduce high frequency components and especially the noise voltage above half the sampling rate of the A/D converter by 80 dB, thus achieving very small measuring errors in an exceptionally large amplitude range. This is also valid under extreme operating conditions like transient voltages at the output of converters.
Uncertainties
Uncertainty at reference conditions Uncertainty including the voltage sensors is in compliance with IEC 61000-4-30 Class-A. All voltage sensors are suitable for DC up to 5 kHz.
With Sensor 1000 V 0,1% at Udin = 480 V and 600 V P-N.
Sensor 600 V 0,1% at Udin = 230 V P-N.
Intrinsic uncertainty for harmonics Class I as per EN 61000-4-7:2002.
Reference conditions 23°C ±2 K < 60% rH; 74°F ±2 K < 60% rH.
Warmed up instrument > 3h.
Power supply: 100 V to 250 V AC.
Temperature drift 100 ppm / K.
Aging < 0.05% / year.
Common mode rejection > 100 dB at 50 Hz.
Temperature drift Change of amplification through temperature: < 0.005%/K.
Aging Change of amplification due to ageing: < 0.04%/year.
Noise Noise voltage, input short-circuited: < 40 µV.
DC ±(0.2% rdg + 0.1% sensor).

Download

Fluke 1760 Datasheet

PDF Specifications of the Fluke 1760 Three-Phase Energy Logger.

Download (432.27k)

No customer reviews for the moment.

Write your review

Fluke 1760TR Power Quality Recorder Topas
COMPONENT
DESCRIPTION PART No.
TPS Clamp 10/1 TPS Clamp 10A/1A Clip-on Current Transformer. 2540445
TPS Clamp 50/5 TPS Clamp 50A/5A Clip-on Current Transformer. 2540461
TPS Clamp 200/20 TPS Clamp 200A/20A Clip-on Current Transformer. 2540450
TPS Flex 18-TF-ll 100/500A Fluke 1760 Thin Flexi 45cm (18in). 4531837
TPS Flex 24-TF-ll 200/1000A Fluke 1760 Thin Flexi 61cm (24in). 4531843
TPS Flex 36-TF-ll 3000/6000A Fluke 1760 Thin Flexi 91cm (36in). 3971234
TPS Shunt 20MA TPS Shunt 20MA AC/DC. 2540553
TPS Voltprobe 10V TPS Voltprobe 10V. 2540636
TPS Voltprobe 100V TPS Voltprobe 100V. 2540624
TPS Voltprobe 400V TPS Voltprobe 400V. 2540660
TPS Voltprobe 600V TPS Voltprobe 600V. 2540697
TPS Voltprobe 1KV TPS Voltprobe 1000V. 2540659
TPS/MBX Dolph Red EP0326Z, Dolphin clip, red. 2540744

14 other products in the same category: