Megger TXL850 Telecom Load Unit
  • Megger TXL850 Telecom Load Unit
  • Megger TXL850 Telecom Load Unit
  • Megger TXL850 Telecom Load Unit

Megger TXL850 Telecom Load Unit

Megger approved distributor and service centre.

Optional Accessories (not supplied): Cable set GA-09550, 2x3 m 70 m2* (* Control leads 2 x 2 m (6.5 ft),Transport case, Mains cable).

BS-59005
Megger
£6440.00
£7728 Inc. VAT

NB: The Megger TXL850 (BS-59005) is supplied without accessories.

The Megger TXL850 load unit is designed for use together with TORKEL battery testers. Their purpose is to provide higher load currents for use in constant current or constant power tests. Together, TORKEL and the TXL extra loads form a system that can discharge batteries with currents of up to several kA. TXL extra loads are connected directly to the battery, and TORKEL measures the total current using a clamp-on ammeter.

The Torkel TXL850 extra load unit is shut down automatically when TORKEL is stopped.

Megger TXL830, 850, 870, 890 Specifications
AC/DC Voltage
Voltage DC Max Current Max Power Max
TXL830 28 V 300 A 8.3 kW
TXL850 56 V 300 A 16.4 kW
TXL870 280 V 112 A 15.8 kW
TXL890 480 V 62 A 15.4 kW
Internal Resistance, 3-Position Selector
Position 1 Position 2 Position 3
TXL830 0.275 Ω 0.318 Ω 0.092 Ω
TXL850 0.55 Ω 0.275 Ω 0.184 Ω
TXL870 4.95 Ω 2.48 Ω 1.24 Ω
TXL890 14.10 Ω 7.05 Ω 3.52 Ω
Maximal Currents, 3 Position Selector
Position 1 Current Voltage Cells Cell Voltage
TXL830 100 A 27.6 V 12 2.3 V
78.5 A 21.6 V 12 1.8 V
TXL850 100 A 55.2 V 24 2.3 V
78.5 A 43.2 V 24 1.8 V
TXL870 50.1 A 248.4 V 108 2.3 V
39.2 A 194.4 V 108 1.8 V
TXL890 32.3 A 469.2 V 204 2.3 V
26.0 A 367.2 V 204 1.8 V
Position 2 Current Voltage Cells Cell Voltage
TXL830 200 A 27.6 V 12 2.3 V
156 A 21.6 V 12 1.8 V
TXL850 200 A 55.2 V 24 2.3 V
156 A 43.2 V 24 1.8 V
TXL870 50.1 A 124.2 V 54 2.3 V
39.2 A 97.2 V 54 1.8 V
TXL890 35.2 A 248.4 V 108 2.3 V
27.8 A 194.4 V 108 1.8 V
Position 3 Current Voltage Cells Cell Voltage
TXL830 300 A 27.6 V 12 2.3 V
235 A 21.6 V 12 1.8 V
TXL850 300 A 55.2 V 24 2.3 V
235 A 43.2 V 24 1.8 V
TXL870 100 A 124.2 V 54 2.3 V
74.8 A 97.2 V 54 1.8 V
TXL890 70.5 A 248.4 V 108 2.3 V
55.2 A 194.4 V 108 1.8 V
Environment The instrument is intended for use in high voltage substations and industrial environments.
Operating temperature 0°C to +40°C (32°F to +104°F).
Storage temperature -40°C to +70°C (-40°F to +158°F).
CE Marking LVD: IEC61010-1:2010
EMC: IEC61326 -1.
Main Voltage 100 – 240 V AC, 50 / 60 Hz.
Power consumption 75 W (max).
Protection Thermal cut-outs, automatic overload protection.
Dimensions Instrument: 210 x 353 x 600 mm (8.3” x 13.9” x 23.6”)
Transport case: 265 x 460 x 750 mm (10.4” x 18.1” x 29.5”).
Weight 13 kg (29 lbs) 21.4 kg (47 lbs) with transport case.
Storage temperature -40°C to +70°C (-40°F to +158°F).

Download

Megger Torkel900 Datasheet

PDF Specifications of the Megger Torkel 910, 930 & 950 Battery Load Units.

Download (686.55k)