- Hamilton01698 829711
- Leeds0113 235 1356
- Belfast02890 830302
Martindale MicroPat+ Dual Voltage PAT Tester
Includes: Martindale Micro PAT+, Earth bond lead with crocodile clip, Flash Test pistol probe with trigger, 110 volt power adaptor, Carry bag for accessories, Spare Internal Fuses, Instruction manual.
The Martindale MicroPAT Plus is a dual voltage PAT tester with memory storage and download capability. It features a one-button, one test operation and can be connected to a barcode scanner for easy entering of appliance numbers.
This portable appliance tester carries out both the legal minimum tests, as well as earth leakage, run current and flash tests. Suitable for testing of both standard appliances and IT equipment, the MicroPAT Plus is an excellent value-for-money tester. For downloading the test results we would recommend using the Martindale MPATSUITE software, however you can also download results to Shire Safety First Express & Simply PATs.
FEATURES
Downloads to computer/printer.
Simple one button, one test operation.
Tests both 240V and 110V appliances based on supply voltage.
Fast and easy Class I, Class II appliance testing.
Extension lead tests with optional LTDV accessory.
Performs 5 PAT tests (earth bond, insulation, run current, run leakage, flash).
High and low current earth bond tests at 25A, 8A and 200mA for sensitive IT equipment.
Suitable for onsite PAT testing, tool hire and workshop applications.
Mains powered 110V/240V with instant on.
Hard case with storage and removable top.
Earth Continuity Test | |
Test Voltage | 6 V AC nominal with no load. |
Test Current | 25 A AC nominal with 0.1 Ω load. (at 240 V AC) 10 A AC nominal with 0.5 Ω load. 100 mA (soft test) for ITequipment. |
Display Range | 0 to 1.99 Ω. |
Accuracy | ±10% ± 1 digit. |
Insulation Test | |
Test Voltage | 500 V DC - 0% + 20%. |
Short Circuit Current | 1 mA DC nominal. |
Display Range | 0 to 19.9 MΩ. |
Accuracy | ±5% ±1 digit. |
Run Test | |
Display Range | 0 to 3.1 kVA. |
Accuracy | ±10% ±1 digit at nominal 240 V. |
Earth Leakage Test | |
Display Range | 0 to 6 mA AC. |
Accuracy | ±10% ±1 digit. |
Flash Test | |
Test Voltage | 1.5 kV AC - Class I (at nom 240V AC) 3 kV AC - Class II. |
Display Range | 0 to 3.0 mA AC. |
Accuracy | ±5% ±1 digit. |
Socket Test | |
Mains/AC | 240V 13A to BS1363, 110V 16A to BS4343. |
Serial Interface | Printer/computer output using a 9 pin ‘D’ type connector RS232. |
Flash | 4mm high voltage safety type. |
Lamps | |
Flash | Neon lamp illuminates when flash test is selected. |
Display | |
LCD | 2 lines x 20 characters. supertwist liquid crystal high contrast display. |
General | |
---|---|
Material | ABS/Polycarbonate. |
Dimensions | 330 X 263 X 144 mm. |
Weight | 4.75 kg complete. |
Martindale MicroPAT Plus warranty | Two-years. |
No customer reviews for the moment.
COMPONENT |
DESCRIPTION | PART No. | ||
EB Lead | Earth bond lead suitable for the Martindale EPAT1600, EPAT2100 & MicroPAT Plus. | MARTL66 | ||
Extension Lead Tester | The LTDV enables IEC power lead testing for the Martindale MicroPAT Plus and includes the EX332 adaptor. | MARLTDV | ||
3 Phase Adaptor | 4 pin, 16A 3 phase socket to UK mains plug, allows testing of earth bond and insulation from PAT testers. | MARTL151 | ||
3 Phase Adaptor | 4 pin, 32A 3 phase socket to UK mains plug, allows testing of earth bond and insulation from PAT testers. | MARTL153 | ||
PASS Labels | A pack of 500 folded "Pass" Electrical Safety PAT Test Labels. | PASS500 | ||
FAIL Labels | Roll of 250 "Fail" Electrical safety test labels for PAT Testing. | FAIL250 |