loading spinner
Martindale MicroPat Plus Dual Voltage PAT Tester
  • Martindale MicroPat Plus Dual Voltage PAT Tester
  • Martindale MicroPat+ Dual Voltage PAT Tester
  • Martindale MicroPat+ Dual Voltage PAT Tester

Martindale MicroPat+ Dual Voltage PAT Tester

Martindale approved distributor and service centre.

Includes: Martindale Micro PAT+, Earth bond lead with crocodile clip, Flash Test pistol probe with trigger, 110 volt power adaptor, Carry bag for accessories, Spare Internal Fuses, Instruction manual.

MARMPATPLUS
£799.00
£958.8 Inc. VAT

The Martindale MicroPAT Plus is a dual voltage PAT tester with memory storage and download capability. It features a one-button, one test operation and can be connected to a barcode scanner for easy entering of appliance numbers.

This portable appliance tester carries out both the legal minimum tests, as well as earth leakage, run current and flash tests. Suitable for testing of both standard appliances and IT equipment, the MicroPAT Plus is an excellent value-for-money tester. For downloading the test results we would recommend using the Martindale MPATSUITE software, however you can also download results to Shire Safety First Express & Simply PATs.

FEATURES

Downloads to computer/printer.
Simple one button, one test operation.
Tests both 240V and 110V appliances based on supply voltage.
Fast and easy Class I, Class II appliance testing.
Extension lead tests with optional LTDV accessory.
Performs 5 PAT tests (earth bond, insulation, run current, run leakage, flash).
High and low current earth bond tests at 25A, 8A and 200mA for sensitive IT equipment.
Suitable for onsite PAT testing, tool hire and workshop applications.
Mains powered 110V/240V with instant on.
Hard case with storage and removable top.

Martindale MicroPat+ Specifications
Earth Continuity Test
Test Voltage 6 V AC nominal with no load.
Test Current 25 A AC nominal with 0.1 Ω load.
(at 240 V AC) 10 A AC nominal with 0.5 Ω load.
100 mA (soft test) for ITequipment.
Display Range 0 to 1.99 Ω.
Accuracy ±10% ± 1 digit.
Insulation Test
Test Voltage 500 V DC - 0% + 20%.
Short Circuit Current 1 mA DC nominal.
Display Range 0 to 19.9 MΩ.
Accuracy ±5% ±1 digit.
Run Test
Display Range 0 to 3.1 kVA.
Accuracy ±10% ±1 digit at nominal 240 V.
Earth Leakage Test
Display Range 0 to 6 mA AC.
Accuracy ±10% ±1 digit.
Flash Test
Test Voltage 1.5 kV AC - Class I
(at nom 240V AC) 3 kV AC - Class II.
Display Range 0 to 3.0 mA AC.
Accuracy ±5% ±1 digit.
Socket Test
Mains/AC 240V 13A to BS1363, 110V 16A to BS4343.
Serial Interface Printer/computer output using a 9 pin ‘D’ type
connector RS232.
Flash 4mm high voltage safety type.
Lamps
Flash Neon lamp illuminates when flash test is selected.
Display
LCD 2 lines x 20 characters. supertwist liquid crystal high
contrast display.
General
Material ABS/Polycarbonate.
Dimensions 330 X 263 X 144 mm.
Weight 4.75 kg complete.
Martindale MicroPAT Plus warranty Two-years.

Download

Martindale MicroPAT+ Datasheet

PDF Specifications of the Martindale MicroPat+ Dual Voltage PAT Tester.

Download (258.55k)

No customer reviews for the moment.

Write your review

Martindale MicroPat+ Dual Voltage PAT Tester
COMPONENT
DESCRIPTION PART No.
EB Lead Earth bond lead suitable for the Martindale EPAT1600, EPAT2100 & MicroPAT Plus. MARTL66
Extension Lead Tester The LTDV enables IEC power lead testing for the Martindale MicroPAT Plus and includes the EX332 adaptor. MARLTDV
3 Phase Adaptor 4 pin, 16A 3 phase socket to UK mains plug, allows testing of earth bond and insulation from PAT testers. MARTL151
3 Phase Adaptor 4 pin, 32A 3 phase socket to UK mains plug, allows testing of earth bond and insulation from PAT testers. MARTL153
PASS Labels A pack of 500 folded "Pass" Electrical Safety PAT Test Labels. PASS500
FAIL Labels Roll of 250 "Fail" Electrical safety test labels for PAT Testing. FAIL250

5 other products in the same category:

arrow_upward