- Hamilton01698 829711
- Leeds0113 235 1356
- Belfast02890 830302
Megger MIT430/2 Insulation and Continuity Tester
Includes: Megger MIT430/2, Red/Black Silicone test leads with Probes + Clips, Owners information CD, Batteries 6 x AA Alkaline, Hard carry case.
The MIT400 mk2 series insulation and continuity testers are designed not just for Electrical and Industrial, but with an exceptionally wide range of applications from electrical installations, cable testing, motor testing, automotive, ESD, panel building, avionics, maintenance etc.
All primary results are displayed in the larger digital display and repeated on the analogue arc. Auxiliary test information such as frequency, leakage current, insulation or circuit voltage is displayed in the smaller secondary digital display.
The MIT430/2 has a tough shock-absorbing rubber over moulding that provides excellent grip, and it also features weatherproof IP54 protection. In addition, the instrument has a bar at the top to allow the addition of future accessories, such as magnetic hanging straps and belt loops.
ELECTROSTATIC DISCHARGE TESTING
The ability to swap displays from kΩ, MΩ, GΩ to 10^5, 10^6, 10^7 and to vary the test voltage make the MIT430/2 ideal for ESD testing, including servicing of equipment and routine maintenance of ESD conductive flooring, bench mats and grounding systems etc. Typical industries include: electronic manufacturing, electronic servicing and repair calibration houses.
FEATURES
Stabilised insulation testing.
Variable 50V to 1000V test voltage.
Auto hold on continuity tests.
Analogue arc with pointer.
200Gohm test range.
Continuous continuity range.
Rechargeable options.
Contoured ergonomic design.
Increased battery life.
IP54 ingress protection.
CAT IV safety design.
600V measurement.
MIT400/2 | MIT410/2 | MIT420/2 | MIT430/2 | |
Insulation | ||||
50/100 V | - | |||
250/500/1000 V | ||||
Variable | - | - | ||
PI-/DAR/Timed | - | |||
Lock Button on MΩ | ||||
Continuity | ||||
Continuity 0.01 Ω to 1 MΩ | 100 Ω | |||
Auto Reverse Polarity (setup ON-OFF) | - | |||
Lead Null (<10 Ω) | ||||
Voltage | ||||
AC/DC Volts 600 V | ||||
mV AC/DC Range | ||||
Frequency Measurements 15 to 400 Hz | - | |||
Input Impedance | 0.25 MΩ | 0.25 MΩ | 0.25 MΩ | 0.25 MΩ |
Capacitance | ||||
Capacitance 0.1 nF to 10 μF | - | - | ||
Other Features | ||||
PASS/FAIL on Limit Alarms | - | |||
Auto Power Down (setup) | ||||
On-Board Memory | - | - | ||
Bluetooth Download + Software | - | - | - | |
AA Alkaline or NIMH | Both | Both | Both | Both |
Recharger Ready | - | - | - | |
CAT IV 600V / CAT III 1000V |
Test Voltage | ||
MIT 400/2 | 250, 500 and 1000 V. | |
MIT 410/2, 420/2 and 430/2 | 50, 100, 250, 500 and 1000 V. | |
Insulation Accuracy | ||
---|---|---|
Test Voltage | Range | Accuracy |
50 V | 10 GΩ | ±2% ± 2 digits ± 4.0% per GΩ. |
100 V | 20 GΩ | ±2% ± 2 digits ± 2.0% per GΩ. |
250 V | 50 GΩ | ±2% ± 2 digits ± 0.8% per GΩ. |
500 V | 100 GΩ | ±2% ± 2 digits ± 0.4% per GΩ. |
1000 V | 200 GΩ | ±2% ± 2 digits ± 0.2% per GΩ. |
Display Range | Analogue 1 GΩ full scale. |
|
Resolution | 0.1 kΩ. | |
Short Circuit/Charge Current | 2 mA +0% to -50% to EN 61557-2 (2007). | |
Open Circuit Voltage Insulation | -0 +2% ±2 V. | |
Test Current | 1 mA at min pass value of insulation to a max of 2 mA max. | |
Leakage | 10% ± 3 digits. | |
Voltage | 3% ±3 digits ±0.5% of rated voltage. | |
Timer Control | 60 second countdown timer. | |
Note: Above specifications only apply when high quality silicone leads are being used. | ||
Continuity | ||
Continuity Measurement | 0.01 Ω to 999 kΩ (0 to 1000 kΩ on analogue scale). | |
Continuity Accuracy | ± 3% ± 2 digits (0 to 100 Ω ) ±5% ±2 digits (100 to 500 kΩ) (500 kΩ to 1 MΩ unspecified) Service Error: BS EN 61557-4 (2007) - ± 2.0%, 0.1 Ω - 2 Ω ± 6.8%. |
|
Open Circuit Voltage | 5V ±1 V. | |
Test Current | 200 mA (-0 mA to +20 mA) (0.01 Ω to 4 Ω). |
|
Polarity | Single polarity (default) / Dual polarity (configurable on setup). | |
Lead Resistance | Null up to 9.00 Ω. | |
Voltage | ||
Voltage Range | AC: 10mV to 600V RMS sinusoidal (15Hz to 400Hz) DC: 0 to 600V. |
|
Volt Range Accuracy | AC: ±2% ±1 digit DC: ±2% ±2 digit Service Error: BS EN 61557-1 (2007) - ± 2.0% ± 2d, 0 V - 300 V AC/DC ± 5.1%. |
|
Waveform | Unspecified range: 0 – 10 mV (15 to 400 Hz) For non-sinusoidal waveforms additional specifications apply. Non-sinusoidal waveforms: ±3% ± 2 digits >100 mV to 600 V TRMS ±8% ± 2 digits 10 mV to 100 mV TRMS. |
|
Frequency | ||
Frequency Measurement Range | 15 Hz to 400 Hz. | |
Frequency Measurement Accuracy | ±0.5% ±1 digit (100 Hz to 400 Hz unspecified). | |
Capacitance Measurement (MIT420/2 and MIT430/2) | ||
Capacitance Measurement | 1 nF to 10 μF. | |
Capacitance Measurement Accuracy | ±5.0% ± 2 digits (0.1 nF to 1 nF unspecified). | |
Storage (MIT420/2 and MIT430/2) | ||
Storage Capacity | >1000 test results. | |
Data Download | Bluetooth wireless Bluetooth Class II. |
|
Range | Up to 10m. | |
General Specifications | ||
Battery Life | 3000 insulation tests with duty cycle of 5 seconds ON/55 sec off @ 1000 V into 1 MΩ. | |
Dimensions | Instrument: 228 x 108 x 63 mm (9.00 x 4.25 x 2.32 inches). | |
Weight | 600g (MIT400/2) (1.32lbs). |
No customer reviews for the moment.
COMPONENT |
DESCRIPTION | PART No. | ||
Test Leads | Red/Black Silicone test leads with Probes + Clips. | 1007-781 | ||
SP5 Probe | Remote switch probe (not MIT400/2). | 1007-157B | ||
Test Leads | Unfused lead set, Red/Black.Long & short prods and croc clips. Boxed. | 1002-001B | ||
Strap | Magnetic hanging strap. | 1010-013 | ||
Case | Blow moulded case. | 1007-169 | ||
Pouch | Test and carry pouch (MIT400 Mk2 Series). | 1007-887 |