- Hamilton01698 829711
- Leeds0113 235 1356
- Belfast02890 830302
Megger MIT400/2 Insulation and Continuity Tester
Includes: Megger MIT400/2, Red/Black Silicone test leads with Probes + Clips, Owners information CD, Batteries 6 x AA Alkaline, Hard carry case.
The MIT400/2 is a competitively priced entry-level instrument with the capability to test insulation at 250 V, 500 V and 1000 V. It offers an enhanced fast continuity test feature, with auto-ranging for measurements from 0.01 Ω to 1.0 MΩ. Continuity tests can be performed at either 200 mA or 20 mA, to suit the requirements of the application. The instruments also offer voltage measurement up to 600 V AC and DC, with AC measurements being true RMS (TRMS).
The MIT400/2 has a tough shock-absorbing rubber over moulding that provides excellent grip, and it also features weatherproof IP54 protection. In addition, the instrument has a bar at the top to allow the addition of future accessories, such as magnetic hanging straps and belt loops.
ELECTRICAL INSTALLATION TESTING
The MIT400/2 includes all the features required for electricians and engineers working in a range of industries. Features are selected to make testing easy and fast in a range of situations.
Typical industries include: Electrical supply companies, Large and small scale electrical installation, Periodic inspection and testing, Cable testing.
FEATURES
Stabilised insulation testing.
Variable 10V to 1000V test voltage.
Auto hold on continuity tests.
Analogue arc with pointer.
200Gohm test range.
Continuous continuity range.
Rechargeable options.
Contoured ergonomic design.
Increased battery life.
IP54 ingress protection.
CAT IV safety design.
600V measurement.
MIT400/2 | MIT410/2 | MIT420/2 | MIT430/2 | |
Insulation | ||||
50/100 V | - | |||
250/500/1000 V | ||||
Variable | - | - | ||
PI-/DAR/Timed | - | |||
Lock Button on MΩ | ||||
Continuity | ||||
Continuity 0.01 Ω to 1 MΩ | 100 Ω | |||
Auto Reverse Polarity (setup ON-OFF) | - | |||
Lead Null (<10 Ω) | ||||
Voltage | ||||
AC/DC Volts 600 V | ||||
mV AC/DC Range | ||||
Frequency Measurements 15 to 400 Hz | - | |||
Input Impedance | 0.25 MΩ | 0.25 MΩ | 0.25 MΩ | 0.25 MΩ |
Capacitance | ||||
Capacitance 0.1 nF to 10 μF | - | - | ||
Other Features | ||||
PASS/FAIL on Limit Alarms | - | |||
Auto Power Down (setup) | ||||
On-Board Memory | - | - | ||
Bluetooth Download + Software | - | - | - | |
AA Alkaline or NIMH | Both | Both | Both | Both |
Recharger Ready | - | - | - | |
CAT IV 600V / CAT III 1000V |
Test Voltage | ||
MIT 400/2 | 250, 500 and 1000 V. | |
MIT 410/2, 420/2 and 430/2 | 50, 100, 250, 500 and 1000 V. | |
Insulation Accuracy | ||
---|---|---|
Test Voltage | Range | Accuracy |
50 V | 10 GΩ | ±2% ± 2 digits ± 4.0% per GΩ. |
100 V | 20 GΩ | ±2% ± 2 digits ± 2.0% per GΩ. |
250 V | 50 GΩ | ±2% ± 2 digits ± 0.8% per GΩ. |
500 V | 100 GΩ | ±2% ± 2 digits ± 0.4% per GΩ. |
1000 V | 200 GΩ | ±2% ± 2 digits ± 0.2% per GΩ. |
Display Range | Analogue 1 GΩ full scale. |
|
Resolution | 0.1 kΩ. | |
Short Circuit/Charge Current | 2 mA +0% to -50% to EN 61557-2 (2007). | |
Open Circuit Voltage Insulation | -0 +2% ±2 V. | |
Test Current | 1 mA at min pass value of insulation to a max of 2 mA max. | |
Leakage | 10% ± 3 digits. | |
Voltage | 3% ±3 digits ±0.5% of rated voltage. | |
Timer Control | 60 second countdown timer. | |
Note: Above specifications only apply when high quality silicone leads are being used. | ||
Continuity | ||
Continuity Measurement | 0.01 Ω to 999 kΩ (0 to 1000 kΩ on analogue scale). | |
Continuity Accuracy | ± 3% ± 2 digits (0 to 100 Ω ) ±5% ±2 digits (100 to 500 kΩ) (500 kΩ to 1 MΩ unspecified) Service Error: BS EN 61557-4 (2007) - ± 2.0%, 0.1 Ω - 2 Ω ± 6.8%. |
|
Open Circuit Voltage | 5V ±1 V. | |
Test Current | 200 mA (-0 mA to +20 mA) (0.01 Ω to 4 Ω). |
|
Polarity | Single polarity (default) / Dual polarity (configurable on setup). | |
Lead Resistance | Null up to 9.00 Ω. | |
Voltage | ||
Voltage Range | AC: 10mV to 600V RMS sinusoidal (15Hz to 400Hz) DC: 0 to 600V. |
|
Volt Range Accuracy | AC: ±2% ±1 digit DC: ±2% ±2 digit Service Error: BS EN 61557-1 (2007) - ± 2.0% ± 2d, 0 V - 300 V AC/DC ± 5.1%. |
|
Waveform | Unspecified range: 0 – 10 mV (15 to 400 Hz) For non-sinusoidal waveforms additional specifications apply. Non-sinusoidal waveforms: ±3% ± 2 digits >100 mV to 600 V TRMS ±8% ± 2 digits 10 mV to 100 mV TRMS. |
|
Frequency | ||
Frequency Measurement Range | 15 Hz to 400 Hz. | |
Frequency Measurement Accuracy | ±0.5% ±1 digit (100 Hz to 400 Hz unspecified). | |
Capacitance Measurement (MIT420/2 and MIT430/2) | ||
Capacitance Measurement | 1 nF to 10 μF. | |
Capacitance Measurement Accuracy | ±5.0% ± 2 digits (0.1 nF to 1 nF unspecified). | |
Storage (MIT420/2 and MIT430/2) | ||
Storage Capacity | >1000 test results. | |
Data Download | Bluetooth wireless Bluetooth Class II. |
|
Range | Up to 10m. | |
General Specifications | ||
Battery Life | 3000 insulation tests with duty cycle of 5 seconds ON/55 sec off @ 1000 V into 1 MΩ. | |
Dimensions | Instrument: 228 x 108 x 63 mm (9.00 x 4.25 x 2.32 inches). | |
Weight | 600g (MIT400/2) (1.32lbs). |
No customer reviews for the moment.
COMPONENT |
DESCRIPTION | PART No. | ||
Test Leads | Red/Black Silicone test leads with Probes + Clips. | 1007-781 | ||
SP5 Probe | Remote switch probe (not MIT400/2). | 1007-157B | ||
Test Leads | Unfused lead set, Red/Black.Long & short prods and croc clips. Boxed. | 1002-001B | ||
Strap | Magnetic hanging strap. | 1010-013 | ||
Case | Blow moulded case. | 1007-169 | ||
Pouch | Test and carry pouch (MIT400 Mk2 Series). | 1007-887 |