FEATURES
Insulation test voltages 500 V, 1000 V.
Insulation test: 0.1 MΩ to 600 MΩ.
Auto discharge of capacitive voltage.
AC/DC Voltage.
DC millivolts.
AC/DC milliamps.
Resistance (0.1 Ω to 50 MΩ).
Continuity.
Three-year warranty.
Remote probe, test leads, alligator clips.
Rugged, utility hard case.
Auto power off to save battery power.
True RMS.
Large display with backlight.
Live circuit detection prevents insulation test if voltage > 30 V is detected for added user protection.
CAT III 1000V, CAT IV 600V measurement category.
Accepts optional Fluke TPAKTM magnetic hanging system to free your hands for other work.
Voltage DC | Maximum voltage | 1000 V. |
Accuracy | ±(0.2%+2). | |
Maximum resolution | 0.001 V. | |
Voltage AC | Maximum voltage | 1000 V. |
Accuracy | ±(2%+3). | |
Maximum resolution | 0.1 mV. | |
Current DC | Maximum amp | 400 mA. |
Amps accuracy | ±(1.0%+2). | |
Maximum resolution | 0.01 mA. | |
Current AC | Maximum amp | 400 mA. |
Amps accuracy | ±(2.0%+2)*. | |
Maximum resolution | 0.01 mA. | |
Resistance | Maximum resistance | 50 MΩ. |
Accuracy | ±(1.2%+2). | |
maximum resolution | 0.1Ω. | |
Insulation Test | ||
Minimum test current @ 1kΩ/V | 1 mA. | |
Test voltages | 500, 1000 V. | |
Maximum resistance per test voltage | 50 V | |
100 V | ||
250 V | ||
500 V | ||
1000 V | 600 MΩ. | |
Maximum resolution per test voltage | 50 V | 0.01 MΩ. |
100 V | 0.01 MΩ. | |
250 V | 0.1 MΩ. | |
500 V | 0.1 MΩ. | |
1000 V | 0.1 MΩ. | |
Accuracy per test voltage | 50 V | ±(3% + 5). |
100 V | ±(3% + 5). | |
250 V | ±(1.5% + 5). | |
500 V | ±(2.0% + 5). | |
1000 V | ±(2.0% + 5). | |
Environmental Specifications | ||
Operating temperature | –20°C to +55°C. | |
Storage temperature | -40°C to +60°C. | |
Humidity (without condensation) | 0% - 95% (10°C – 30°C) 0% - 75% (30°C – 40°C) 0% - 40% (40°C – 55°C). |
|
Operating altitude | 2000 m. | |
Safety Specifications | ||
Overvoltage category | Complies with ANSI/ISA 82.02.01 (61010-1) 2004, CAN/CSA-C22.2 NO. 61010-1-04, and IEC/EN 61010-1 2nd Edition for measurement CAT III 1000 V and CAT IV 600 V. | |
Agency approvals | 2000 m CAT III 1000 V, CAT IV 600 V; 3000 m CAT II 1000 V, CAT III 600 V. | |
Mechanical and General Specifications | ||
Dimensions | 203 x 100 x 50 mm (with holster). | |
Weight | 624 g. | |
Fluke 1577 Warranty | 3 years. | |
Battery life alkaline | Meter use | 1000 hours. |
Insulation test use | Meter can perform at least 1000 insulation tests with fresh alkaline batteries at room temperature. These are standard tests of 1000 V into 1 MΩ with a duty cycle of 5 seconds on and 25 seconds off. | |
IP rating | IP40. |
No customer reviews for the moment.
COMPONENT |
DESCRIPTION | PART No. | ||
C25 | Soft meter case. | 681114 | ||
C550 | Tool bag. | 1547919 | ||
AC285 | SureGrip™ Alligator Clips. | 1610159 | ||
TPAK | ToolPak™ Magnetic Meter Hanger Kit includes: 9 inch hook and loop strap Universal hanger clip Hook hanger for non magnetic surfaces Strong magnet. |
1281997 | ||
TL27 | Heavy Duty Test Lead Set. | 668571 | ||
TLK-225 | SureGrip™ Master Accessory Set. | 3971234 | ||
i200 | i200 AC Current Clamp (200A). | 664755 | ||
80PK-8 | Pipe Clamp Temperature Probe (Type-K thermocouple). | 200360 |