Megger DCM305E Earth Leakage Clamp Meter
Includes: DCM305E Earth Clamp, user manual and carrying case.
The Megger DCM305E is designed to check earth leakage currents; however the upper range enables TRMS AC current measurements of up to 100 A. TRMS meters can measure both pure, undistorted, sinusoidal AC waveforms and non-sinusoidal AC waveforms which can contain pulse trains, triangles, spikes and other ragged waves.
The instrument has six ranges: 6 mA, 60 mA, 600 mA, 6 A, 60 A, 100 A with a minimum resolution of 0.001 mA on the 6 mA range. Either auto or manual ranging can be selected.
Due to the design of the 40 mm jaw the DCM305E allows current measurements on un-insulated conductors and busbars though personal protection against shock should still be maintained.
FEATURES
0.001 mA resolution.
Up to 100 A AC.
TRMS reading.
Low pass filter to aid stability of readings.
Auto, data & peak hold.
40 mm jaw.
Auto power-off (20 min; user-selectable).
The instrument has six ranges: 6 mA, 60 mA, 600 mA, 6 A, 60 A, 100 A with a minimum resolution of 0.001 mA on the 6 mA range. Either auto or manual ranging can be selected.
Due to the design of the 40 mm jaw the DCM305E allows current measurements on un-insulated conductors and busbars though personal protection against shock should still be maintained.
FEATURES
0.001 mA resolution.
Up to 100 A AC.
TRMS reading.
Low pass filter to aid stability of readings.
Auto, data & peak hold.
40 mm jaw.
Auto power-off (20 min; user-selectable).
Megger DCM305E Specifications
Measuring function | TRMS Leakage current and load current. | |||
Display | 6000 count. | |||
Ranges | 6.000 mA / 60.00 mA / 600.00 mA / 6.000 A / 60.00 A / 100.0 A. | |||
Basic Accuracy | ± (1.0 % + 3d). | |||
AC Voltage | Range | Resolution | Accuracy | |
6 mA | 0.001 mA | 0 ~ 10 A ±(1 % reading + 8 digits) | ||
60 mA | 0.01 mA | 0 ~ 10 A ±(1 % reading + 8 digits) | ||
600 mA | 0.1 mA | 0 ~ 10 A ±(1 % reading + 8 digits) | ||
6 A | 0.001 A | 0 ~ 10 A ±(1 % reading + 8 digits) | ||
60 A | 0.01 A | 0 ~ 10 A ±(1 % reading + 8 digits) | ||
100 A | 0.1 A | 0 ~ 10 A ±(1 % reading + 8 digits) | ||
Operating frequency range | 50 - 400 Hz. | |||
Sampling rate | 5 times / second. | |||
Data, auto, peak hold | User Selectable. | |||
Low pass filter | 50 / 60 Hz. | |||
Jaw size | 40 mm (750 mm conductor size). | |||
Maximum jaw opening | 43 mm. | |||
Overload | “OL”. | |||
Auto power off | 20 minutes of inactivity. | |||
Operating temperature | 0 °C - 50 °C. | |||
Power Supply | 2 x 1.5 V alkaline AAA / LR03. | |||
Battery life | 60 hours. | |||
Safety | EN61010-1 CAT III 300 V. | |||
Dimensions | 78 mm (W) x 203 mm (H) x 42 mm (D). | |||
Weight | 300 g. | |||
Megger DCM305E warranty | 1 Years. |