- Hamilton01698 829711
- Leeds0113 235 1356
- Belfast02890 830302
ETI Legionnaire's Thermometer Kit
Includes: 1 x 221-041 Therma 1 thermometer, 1 x 123-160 penetration probe, 1 x 123-030 precision ribbon surface probe, 1 x 133-362 PTFE wire probe, 1 x 806-150 countdown timer, 1 x tub of 70 MiniWipes (836-022), 1 x 834-150 ABS carrying case.
The ETI Legionnaire's Thermometer Kit (or Legionella thermometer kit) can be used to monitor the temperature of both standing water and the surface of pipes and tanks that form part of the water system. This kit comes with a traceable certificate of calibration.
What is Legionnaires' disease?
Legionnaires' disease is a potentially fatal form of pneumonia. The cause of the disease is a bacterium called legionella pneumophila.
How is it caught?
Legionnaires' disease is caught by inhaling small droplets of water suspended in the air which contain the legionella bacterium, e.g. spray from showers and taps.
What are the sources of legionella bacterium?
The legionella bacterium is found mainly in stagnant water, e.g. ponds and rivers or buildings containing cooling tower, evaporation condensers, air conditioning and industrial cooling systems, humidifiers, spa baths and hot and cold water systems. Incorrect water temperature is a key risk factor for legionella growth. The legionella bacteria multiply in water at temperatures between 20 to 45°C, particularly if a supply of nutrients is present, such as scale, rust, sludge or algae. A typical method of control is to store cold water below 20°C. Hot water should be stored above 60°C and distributed at above 50°C.
FEATURES
0.1°C resolution.
Wide temperature measurement range.
Water resistant timer.
Minimum five-years battery life.
Free traceable certificate of calibration included.
Therma 1 Thermometer | |||
Temperature Range 0.1 °C | -99.9 to 299.9 °C. | ||
Temperature Range 1 °C | 300 to 1372 °C. | ||
Resolution | 0.1 °C / 1 °C. | ||
Accuracy | ±0.4°C ±0.1%. | ||
General Specifications | |||
Sensor type | K thermocouple. | ||
Display | 12 mm LCD. | ||
Case material | ABS plastic with Biomaster anti-bacterial additive. | ||
Power | 3 x 1.5 volt AAA. | ||
Battery life | minimum 5 years (10,000 hours). | ||
Dimensions | 25 x 56 x 128mm. | ||
Weight | 130 grams. | ||
ETI Legionnaires Kit warranty | 2 years. |
No customer reviews for the moment.
COMPONENT |
DESCRIPTION | PART No. | ||
Probe | Penetration temperature probe for liquids & solids. Ø3.3 x 130mm, range -75 to 250°C. | 123-160 | ||
Probe | Ribbon surface temperature probe. Ø15 x 130 mm, fast response, range -75 to 250°C. | 123-030 | ||
Probe | PTFE wire temperature probe. Ø1.5 x 1000mm / 2000mm, temperature range -75 to 250°C. | 133-362 | ||
Case | ABS carrying case. | 834-150 |